6.3 Installing a Cable
1. Loosely secure fiber cable to equipment rack upright approximately 3 inches (76mm) above or
below panel, using cable tie or hook-and-loop strip. Leave approximately 48-inch (2.1m) length
of cable to route into panel.
2. Fiber cables may enter panel from either right side, left side or rear apron. Carefully loop fiber
cable to rear of panel on either side and continue to feed cable over top of rear apron.
3. Temporarily store slack fibers in panel.
4. Remove plug from appropriate size opening in panel to accommodate cable gland on fiber
cable. Select an opening on rear apron or either right or left side that will be most
advantageous for cable entry.
5. Completely loosen gland nut from cable gland.
6. Feed fibers and subunit tubes through panel opening. Temporarily coil fibers loosely in panel.
7. Insert threaded body of cable gland into opening and tighten gland nut onto threaded section
to secure cable gland unit to panel.
Note:
These instructions cover only the cable gland method of securing fiber cables.