7 HOMEDEPOT.com
Please contact 1-877-527-0313 for further assistance.
Installation (continued)
6
Connecting the wiring
□
Make wire connections using the wire nuts (BB).
□
For 120 V applications, use the black and white
wires. Connect the black supply wire to the
black fixture wire. Connect the white supply
wire to the white fixture wire.
□
For 277 V applications, use the red and white
wires. Connect the red supply wire to the red
fixture wire. Connect the white supply wire to
the white fixture wire.
□
Cap unused wires using a wire nut (BB).
BB
7
Completing the installation
□
Snap the faceplate(s) (A) onto the frame (B).
□
Restore power to the circuit.
□
Allow 24 hours for the back-up battery to fully
charge.
A
B
Maintenance
NOTE:
National Electric Code (NEC) and NFPA life safety code
regulations require that routine tests need to be performed.
TESTING OPERATION
With AC Power applied to the unit, the EXIT sign and A/C Power LED indicator should illuminate. When pushing the
TEST button (I), the LED indicator should turn off, the EXIT sign will remain illuminated.
TESTING THE BATTERY
Test the unit’s battery once per month. Additionally, every 12 months, a full 90-minute test should be performed.
While disconnected from the main power supply, the EXIT sign should illuminate for a minimum of 90 minutes on
battery back up power.
TEST
I