Step 1
-
Press the device push pad to the desired setting. (this can be fully
depressed or less than fully depressed).
Step 2
-
While depressing the push pad, apply power. (i.e. presenting the
credential to the reader).
Step 3
-
Continue to keep pad depressed, the device will beep 6 times. After the
beeps have stopped, release the pad and now the adjustment is complete.
If not to your liking repeat the three steps. That’s all there is to it.
S
etting
PtS
MM4 Switches
2 Beeps
3 Beeps
5 Beeps
6 Beeps
7 Beeps
B
eePS
e
xPlanation
S
olution
Over Voltage
Under Voltage
Forced Release
Push pad is depressed. Device is
re-adjusting
Over-travel or mechanical
obstruction
> 28V unit will shut down. Check voltage & adjust to 24 V.
< 22V unit will shut down. Check voltage & adjust to 24 V.
Device will automatically re-engage within 5 seconds.
Check to make sure the push pad is not stuck or catching on
anything.
t
rouBleShooting
& D
iagnoSticS
4 Beeps Failed Sensor
Verify all 3 sensor wires are installed correctly. Replace sensor if
problem persists by contacting CAT tech support.
• Input Voltage: 24VDC +/- 10%
• Average Latch Retraction Current: 1 Amp
• Average Holding Current: 170 mA
• Wire gauge: Minimum 20 gauge
If mechanical obstruction, remove & push pad down until
beeping stops to reset. If no obstruction, the pad may have
been pushed in too far during PTS calibration. Recalibrate
with the pad slightly out. If problem persists, verify the
magnet is within 1/4” of the sensor at the end of travel.
**
Important Info
**
Make sure to set PTS before finishing installation!