Installation Instructions  

PS2/PS2BB

The PS2 series is designed to power Command Access modified exit devices, Von 

Duprin EL devices, or Dor-o-matic EL devices. The PS2 series is a regulated, linear 

power supply rated at 2 Amps @ 24VDC. It’s state-of-the-art, solid-state design offers 

a flexible and cost effective solution. Its built-in surge capabilities allow it to power 

up to two latch-retracting exit devices, when used with Command Access power 

modules. The PS2 series is a feature-rich 24VDC power supply that offers solid-state 

Inputs/Outputs, fire alarm link, optional battery charging circuitry and other standard 

features to give you the flexibility and control to do the job right.

SPECIFICATIONS

• Input - 120 VAC, 60Hz, 700mA

• Measured Output Range – 24Vdc  

+/- 

5%, 1 amp

• UL294, Class 2 Output

•  Priority Sensing - When two devices are triggered simultaneously, output 1 will fire first, 

output 2 will fire within 500ms.

•  Electronic over load & temperature detection- Each channel has high speed 

electronic over load & temperature protection that functions independent of the 

other channel.

•  Input trigger - Dry contact 

•  LEDs - Red=AC Power indicator, Green=Output Indicator 

• Temperature range - 0 to 49°c

• Enclosure - 12.5”W x 15”H x 4”D (Holds (2) 7AH Batteries)

• Fuses - AC= 2A Slow Blow 5mm x 20mm   

• Fire Alarm Link

• “Euro-style” removable terminal blocks used

• Factory installed Option BB-Battery charging - Regulated, independent battery charging

• Factory installed Option BB-Battery backup - Automatic uninterrupted battery backup.  

• Batteries not included (requires 2 each 7AH 12V batteries)

• Intended Access Control Level is Class 1

• Maximum Humidity - 85%

DESCRIPTION 

Command Access Technologies | 22901 La Palma Ave, Yorba Linda, CA 92887

| Phone: (888) 6-ACCESS Fax: (888) 622-2302

 Symptom

Possible Cause

Solution

• Power supply makes a

  beeping sound

Possibilty 1- Power supply is too hot, 

microprocessor is shutting the power 

supply down.

Possibility 2- Fire alarm link removed or 

Fire alarm contact broken or loose

Check to see current draw is exceeding the 2 Amps 

continuous rating. If so, eliminate one device that’s 

connected and check current draw.

EL Exit device can’t fully 

retract latch

Possibility 1- Wire gauge from power 

supply to exit device too small

Possibility 2- Distance from Power 

Supply. to exit device is too far

Possibility 3- Exit device out of 

adjustment

Check with your device manager’s wiring 

specifications.

Green channel LED won’t 

light up, channel isn’t 

working

Possibility 1- Dead short or overload

Possibility 2- Bad solenoid in exit device, 

or defective interface device between 

solenoid and power supply.

Shut off power, detect short, restore power, 

channel will reset.

Power supply not working 

and red LED not lit.

Possibility 1-  AC fuse blown 

Replace fuse with 2A Slow Blow 250VAC 

5mm x 20mm

TROUBLESHOOTING

Re-adjust exit device according to manufacturer’s 

mechanical recommendations.

Check with your device manager’s wiring 

specifications.

Check solenoid coil resistance and compare to 

manufacturer spec. If not close, contact service 

represenative.

• 

• 

• 

If not hooked up to fire/life-safety system, make sure 

jumper wire for the fire alarm is properly connected.

If hooked up to fire/life-safety system, make sure system 

is functioning correctly

Doc. #20020_A

Possibility 2-  Short Circuit

If replacement fuse has blown then there 

is likely a short circuit in the board & it 

will need to be replaced.

Connecting to the Fire Alarm Link (if needed)

1.   Shut off the 120 VAC to the power supply.

2.    Remove the jumper wire from “FIRE” 

terminal. (see fig 5) 

3.    Connect to normally closed fire alarm relay.

4.   Restore AC voltage to power supply

fig. 5

FUSE  F1

2.0A

  250V

SLOW BLOW

LINE

NEUTRAL

+   -

IN

1

+   -

OUT

+   -

IN

2

+   -

OUT

+   -

FIRE

+

-

+   -

BAT

RED POWER LED

GREEN 

CHANNEL 2 

LED

GREEN 

CHANNEL 1 

LED

WIRE JUMPER INSTALLED

WHEN NO FIRE ALARM RELAY

IS CONNECTED

REMOVEABLE

CONNECTORS

WHEN BATTERY BACKUP OPTION IS USED,

TWO 7AH 12V BATTERIES MUST BE INSTALLED IN SERIES.

BLACK

GREEN

120VAC

60Hz

0.64A

WHITE

COMMAND ACCESS PS2BB 

ACCESS CONTROL 

CLASS 2 

POWER SUPPLY

BUZZER

+ -

NORMALLY OPEN

DRY CONTACT FROM 

ACCESS CONTROL 

SYSTEM

NO VOLTAGE

DEVICE 1

(24VDC 700mA MAX)

DEVICE 2

(24VDC 700mA MAX)

+

-

NORMALLY OPEN

DRY CONTACT FROM 

ACCESS CONTROL SYSTEM

NO VOLTAGE

+

-

OPTIONAL

7AH 12V BATTERY

CAUTION! 

RISK OF FIRE!

CHARGE ONLY 12V

LEAD ACID

GEL-CELL TYPE

RECHARGEABLE

BATTERIES.

OPTIONAL

7 AH 12V BATTERY

(24VDC)