GMT/KLM 125 FUSE PANEL
SETUP AND OPERATION MANUAL
INSTALLATION - PAGE 5
4.4 Input Connections
WARNING
y
INPUTS MUST BE PROTECTED BY A LISTED CIRCUIT
BREAKER OR BRANCH RATED FUSE. THE CIRCUIT
BREAKER OR FUSE MUST BE RATED 125A MAX.
y
MULTIPLE POWER SOURCES ARE PRESENT, ENSURE
ALL INPUT POWER FEEDS ARE NOT ENERGIZED BEFORE
INSTALLING THEM. ELECTRICAL INSTALLATION SHOULD
ONLY BE PERFORMED BY QUALIFIED PERSONNEL WITH
PROPER TOOLS AND PROTECTIVE SAFETY EQUIPMENT.
NOTICE
y
MAKE SURE THAT ALL FEEDER CABLES HAVE
HEAT SHRINK APPLIED PRIOR TO TERMINATION,
AND THAT NO-OXIDE COMPOUND IS APPLIED TO
ALL COPPER-TO-COPPER CONNECTIONS.
y
SEE APPENDIX C ON PAGE 16 FOR COMPRESSION LUG
SPECIFICATIONS, TOOLING, AND ORDERING INFORMATION.
TABLE 2. INPUT SPECIFICATIONS
TERMINATION
TYPE
HOLE/STUD
SIZE
CENTER TO
CENTER
MAX LUG
WIDTH
RECOMMENDED TORQUE
VALUE
Threaded Stud
1/4 in.
5/8 in.
5/8 in.
50 in∙lbs.
Step 1.
Remove the plastic input safety covers by pulling away from panel
(see Figure
7)
.
Step 2.
Install the return cables/lugs to the return input studs located on the rear of
the panel
(see Figure 8)
. Ensure all that hardware is tightened.
Step 3.
Install the hot input cables/lugs to the hot input studs located on the rear of
the panel
(see Figure 9)
. Ensure that all hardware is tightened.
Step 4.
Reinstall the input safety covers from Step 1.
WARNING
FAILURE TO REINSTALL THE INPUT SAFETY COVERS
WILL CREATE AN ELECTRICAL HAZARD.
Figure 7. Input Safety Covers
Figure 8. Return Input Landing
Figure 9. Hot Input Landing
Содержание GMT 125 Fuse Panel
Страница 1: ...SETUP AND OPERATION MANUAL F O R T E L E C O M B R O A D B A N D GMT KLM 125 Fuse Panel ...
Страница 3: ...SETUP AND OPERATION MANUAL F O R T E L E C O M B R O A D B A N D GMT KLM 125 Fuse Panel ...
Страница 6: ...GMT KLM 125 FUSE PANEL SETUP AND OPERATION MANUAL PAGE vi THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 25: ...THIS PAGE INTENTIONALLY LEFT BLANK ...