30
SPLIT SYSTEM HEATING PERFORMANCE
LOW STAGE
*Note: Shaded area is AHRI Rating Conditions at 47° outdoor ambient temperature
EXPANDED PERFORMANCE DATA
MODEL: *SZC160601B* CAPF4961D6 MBVC2000A - LOW STAGE
HEATING OPERATION
Outdoor Ambient Temperature
65
60
55
50
47
45
40
35
30
25
20
17
15
10
5
-5
-10
MBh
49.9
47.3
44.5
41.6
39.7
38.5
35.8
33.0
30.8
28.4
26.2
24.7
23.8
21.3
18.9
16.5
14.1
11.5
T/R
40.2
38.1
35.8
33.5
32.0
31.0
28.8
26.5
24.8
22.9
21.1
19.9
19.2
17.2
15.2
13.3
11.3
9.3
KW
3.51
3.44
3.36
3.29
3.25
3.22
3.15
3.08
3.47
3.38
3.30
3.25
3.22
3.13
3.05
2.96
2.88
2.79
AMPS
18.3
16.9
15.9
14.9
14.4
14.1
13.3
12.7
12.1
11.6
11.1
10.8
10.7
10.1
9.5
8.9
8.3
7.5
COP
4.17
4.03
3.87
3.70
3.58
3.50
3.32
3.14
2.60
2.46
2.32
2.22
2.16
2.00
1.82
1.63
1.43
1.21
EER
14.2
13.8
13.2
12.6
12.2
12.0
11.4
10.7
8.9
8.4
7.9
7.6
7.4
6.8
6.2
5.6
4.9
4.1
HI PR
402
385
370
354
346
339
326
313
300
286
275
268
263
253
244
234
225
217
LO PR
144
134
126
115
109
105
96
86
77
69
61
56
54
46
40
34
29
23