VENT-FREE NATURAL GAS HEATER

 15,000 TO 28,000 BTU/HR

 WARNING: If the area in which the heater may be operated is smaller than that defined as an unconfined space

or if the building is of unusually tight construction, provide adequate combustion and ventilation air by one of
the methods described in the 

National Fuel Gas Code, ANSI Z223.1, 1992, Section 5.3 or applicable local codes.

AIR FOR
COMBUSTION AND
VENTILATION

Continued

DETERMINING FRESH-AIR FLOW FOR HEATER LOCATION

Determining if You Have a Confined or Unconfined Space

Use this worksheet to determine if you have a confined or unconfined space.

Space:

 Includes the room in which you will install heater plus any adjoining rooms with doorless passageways or ventilation grills between

the rooms.

1.

Determine the volume of the space (length x width x height).

Length x Width x Height = _________________ cu. ft. (volume of space)

Example:

Space size 20 ft. (length) x 16 ft. (width) x 8 ft. (ceiling height) = 2560 cu. ft. (volume of space)

If additional ventilation to adjoining room is supplied with grills or openings, add the volume of these rooms to the total volume of
the space.

2.

Divide the space volume by 50 cubic feet to determine the maximum Btu/Hr the space can support.

______________ (volume of space) 

÷

 50 cu. ft. = (Maximum Btu/Hr

the space can support)

Example:

 2560 cu. ft. (volume of space) 

÷

 50 cu. ft. = 51.2 or 51,200 (maximum Btu/Hr the space can support)

3.

Add the Btu/Hr of all fuel burning appliances in the space.

Vent-free heater

___________________ Btu/Hr

Gas water heater*

___________________ Btu/Hr

Gas furnace

___________________ Btu/Hr

Vented gas heater

___________________ Btu/Hr

Gas fireplace logs

___________________ Btu/Hr

Other gas appliances*

+ __________________ Btu/Hr

Total

= __________________ Btu/Hr

* Do not include direct-vent gas appliances. Direct-vent draws combustion air from the outdoors and vents to the outdoors.

4.

Compare the maximum Btu/Hr the space can support with the actual amount of Btu/Hr used.

___________________ Btu/Hr (maximum the space can support)

___________________ Btu/Hr (actual amount of Btu/Hr used)

Example:

51,200 Btu/Hr (maximum the space can support)

58,000 Btu/Hr (actual amount of Btu/Hr used)

The space in the above example is a confined space because the actual Btu/Hr used is more than the maximum Btu/Hr the space can support.
You must provide additional fresh air. Your options are as follows:

A. Rework worksheet, adding the space of an adjoining room. If the extra space provides an unconfined space, remove door to adjoin-

ing room or add ventilation grills between rooms. See Ventilation Air From Inside Building, page 7.

B. Vent room directly to the outdoors. See Ventilation Air From Outdoors, page 7.

C. Install a lower Btu/Hr heater, if lower Btu/Hr size makes room unconfined.

If the actual Btu/Hr used is less than the maximum Btu/Hr the space can support, the space is an unconfined space. You will need no
additional fresh air ventilation.

Example:

Gas water heater

30,000

Btu/Hr

Vent-free heater +

28,000

Btu/Hr

Total

=

58,000

Btu/Hr

Содержание RADIANT FLAME RFN28TD

Страница 1: ...t Installation and service must be performed by a qualified installer service agency or the gas supplier WARNING Improper installa tion adjustment alteration ser vice or maintenance can cause injury o...

Страница 2: ...le are more affected by carbon monoxide than others These include pregnant women people with heart or lung disease or anemia those under the influence of alcohol and those at high altitudes Natural Ga...

Страница 3: ...pd fA SD FK IG LF JI als kd idk oe m kg o dk irln fg pd f AS DF KI GL FJ I als kd idk oe m kg o dk irln fg pd fA SD FK IG LF JI als kd idk oe m kg o dk irln fg pd f AS DF KI GL FJ I als kd idk oe m kg...

Страница 4: ...ts from inside of front panel Tighten with wrench Truss Head Screw Nut Front Panel Figure 5 Attaching Brass Front Trim to Front Panel Brass Front Trim ASSEMBLY ASSEMBLING HEATER Tools Required Phillip...

Страница 5: ...ally Tight Construction 2 Unconfined Space 3 Confined Space The information on pages 5 through 7 will help you classify your space and provide adequate ventilation Unusually Tight Construction The air...

Страница 6: ...of all fuel burning appliances in the space Vent free heater ___________________ Btu Hr Gas water heater ___________________ Btu Hr Gas furnace ___________________ Btu Hr Vented gas heater __________...

Страница 7: ...d size of ventilation grills or ducts WARNING Rework work sheet adding the space of the adjoining unconfined space The combined spaces must have enough fresh air to supply all appliances in both space...

Страница 8: ...ate heater on floor The optional hearth base is needed You can also install the optional decorative mantel on the heater some mantels require hearth base IMPORTANT Only use optional mantel and hearth...

Страница 9: ...of heater It has been taped there for shipping Remove mounting bracket from back panel 20 3 4 Min 11 Min 16 Adjoining Wall Only Insert Mounting Screws Through Last Hole On Each End Floor Figure13 Moun...

Страница 10: ...s are in hardware package The hard ware package is provided with heater Attaching to wall stud method Forattachingmountingbrackettowallstuds 1 Drill holes at marked locations using 9 64 drill bit 2 Pl...

Страница 11: ...hearth base as shown in Figure 19 7 Assemble brass trim see steps 1 through 7 under Assembling and At taching Brass Trim page 5 8 Slide base trim on heater base Attach brass trim to base with two bras...

Страница 12: ...ly Follow all local codes IMPORTANT Check gas line pressure be fore connecting heater to gas line Gas line pressure must be no greater than 14 inches of water If gas line pressure is higher heater reg...

Страница 13: ...g ure 22 Apply mixture of liquid soap and water to gas joints Bubbles form ing show a leak 5 Correct all leaks at once 6 Light heater see Operating Heater Check all other internal joints for leaks 7 T...

Страница 14: ...anual Lighting Procedure 7 Keep control knob pressed in for 30 seconds after lighting pilot After 30 seconds release control knob If control knob does not pop up when released contact a qualified serv...

Страница 15: ...low for approximately one hour until the log cures NOTICE Do not mistake orange flames with yellow tipping Dirt or other fine particles enter the heater and burn causing brief patches of orange flame...

Страница 16: ...off valve not fully open 5 Thermocouple connection loose at con trol valve 6 Pilot flame not touching thermocouple which allows thermocouple to cool causing pilot flame to go out This prob lem could b...

Страница 17: ...oblem will stop after a few hours of operation 1 Turn control knob to LO position and let warm up for a minute 2 Operate burner until air is removed from line Have gas line checked by local natural ga...

Страница 18: ...ons page 13 1 Refer to Air for Combustion and Venti lation requirements page 5 POSSIBLE CAUSE 1 Metal expanding while heating or con tracting while cooling 1 Heater burning vapors from paint hair spra...

Страница 19: ...ional s Technical Service Depart ment at 1 800 323 5190 When calling DESA International have ready your name your address model number of your heater how heater was malfunctioning typeofgasused propan...

Страница 20: ...N Route 9 Cape May Court NJ 08210 609 624 0678 Baltimore Electric 1348 Dixwell Avenue Hamden CT 06514 1 800 397 7553 203 248 7553 Parts Department Portable Heater Parts 342 N County Rd 400 East Valpar...

Страница 21: ...cluded PRESTIGE MANTEL WITH BUILT IN BASE Unfinished GMC27U Series Finished GMC26F Series Finished Oak GMC28F For use with heater Features built in base sturdy hardwood construction with classic styli...

Страница 22: ...22 104779 VENT FREE NATURAL GAS HEATER 15 000 TO 28 000 BTU HR 12 1 12 2 1 2 9 10 11 12 17 18 19 21 22 23 8 20 7 1 3 5 16 4 25 24 1 6 13 14 15 26 10 ILLUSTRATED PARTS BREAKDOWN RFN28TD...

Страница 23: ...099440 05 ODS Pilot Assembly 1 12 1 098514 01 Thermocouple 1 12 2 098594 01 Ignitor Electrode 1 13 103447 01 Burner 1 14 098517 01 3 16 Pilot Tubing 1 15 103845 07 Injector 1 16 103408 01 Burner Brack...

Страница 24: ...doesnotapplytopartsthatarenotinoriginalconditionbecauseofnormalwearandtear orpartsthatfailorbecome damaged as a result of misuse accidents lack of proper maintenance or defects caused by improper inst...

Отзывы: