Clima Flex Two-pipe One-way Cassette
25
panel and so on.
Display part of the panel should be installed at the pipe side of the unit body.
There are 6 panel installation screws, after confirmation then to be fastened.
10.3 Drainpipe installation
When connecting the pipe, please use the sealing material and pipe glove.
The drain pipe of indoor unit must be heat insulated, or it will condense dew, as well as the connections of
the indoor unit.
Make sure the connections are no leakage.
With the connection part to the indoor unit, please note not to impose pressure on the side of indoor unit
pipes.
When the declivity of the drain pipe downwards is over 1/100,there should not be any winding.
The total length of the drain pipe when pulled out breadthwise shall not exceed 20m. When the pipe is
over long, a bracket must be installed to prevent winding.
Refer to the following figures to install the pipes.
Drainage system type
Centralized drainage of several air conditioners
Single air conditioner drainage
Drainage system design requirement
Between climbing section length(L) and pipe inner diameter(d) should satisfy the relation: L
×
d
2
≤
650000 (unit: mm). That is water in the climbing section can’t more than 500 mL, otherwise will cause
poor drainage, flowing water leakage problems.
It must accord to the requirement to install the water pipe. Suggest using water pipe with the inner
diameter 25mm, and the climbing length is not over than 1m.
Please according to the tube hardness to choose proper support density, do not appear obvious
dropping and deformation situation. Dropping part will save the water and lead to poor drainage and
Gradient is more than 1/100
Gradient is more
than 1/100