Before calling for service, review this list. It may save you time and expense. This list includes common
occurrences that are not the result of defective workman-ship or materials in this appliance.

Solution

Air conditioner
does not start

Wall plug disconnected. Push plug firmly into wall outlet.

House fuse blown or circuit breaker tripped. Replace fuse with time delay type or
reset circuit breaker.

Plug Current Device Tripped. Press the RESET button.

TROUBLESHOOTING TIPS

Problem

Air from unit does
not feel cold
enough

Reset to a Lower temperature.

Room temperature below 17 C(62 F). Cooling may not occur until room temperature
rises above 17 C(62 F).

Thermostat set too cold for night-time cooling. To defrost the coil, set to FAN ONLY
mode. Then, set temperature to a Higher setting.

Temperature sensing element touching cold coil, located behind air filter. Straighten
tube away from coil.

Air filter may be dirty. Clean filter. Refer to Care and Cleaning section. To defrost,
set to FAN ONLY mode.

Dirty air filter- air restricted. Clean air filter. Refer to Care and Cleaning section.

Unit recently turned on in hot room. Allow additional time to remove Stored heat from
walls, ceiling, floor and furniture.

Control is OFF. Turn Control ON and set to desired setting.

O

O

O

O

Air conditioner
cooling, but room
is too warm- ice
forming on cooling
coil behind
decorative front.

Outdoor temperature below 18 C(64 F). To defrost the coil, set FAN ONLY mode.

O

O

Air conditioner
cooling, but room
is too warm- NO
ice forming on
cooling coil behind
decorative front.

Temperature is set too High, set temperature to a Lower setting.

Air directional louvers positioned improperly. Position louvers for better air distribution.

Front of units is blocked by drapes, blinds, furniture, etc. - restricts air distribution.
Clear blockage in front of unit.

Doors, windows, registers, etc. Open- cold air escapes. Close doors, windows, registers.

Compressor shut-off by changing modes. Wait approximately 3 minutes and listen for
compressor to restart when set in the COOL mode.

Air conditioner turns on
and off rapidly

Noise when unit is
cooling

Water dripping
INSIDE when

unit is cooling.

Improper installation. Tilt air conditioner slightly to the outside to allow water drainage.
Refer to installation instructions - check with installer.

Dirty air filter- air restricted. Clean air filter.

Air movement sound. This is normal . If too loud, set to a slower FAN setting.

Outside temperature extremely hot. Set FAN speed to a Higher setting to bring air past
cooling coils more frequently.

Window vibration - poor installation. Refer to installation instructions or check with installer.

15

the rear/outside to allow water drainage.

Blown fuse or circuit breaker has tripped. Replace fuse with time delay type of reset 

circuit breaker.

Current device has tripped on plug. Press the RESET button.

Unit control is OFF. Turn control ON and set to desired setting.

Cooling may not occur until room temperature rises above 62°F (17°C), as unit will not 

work below room air temperature of 62°F (17°C)

Temperature sensing element may be touching the coil, located behind air filter. Straight

-

en sensing tube away from coil.

Reset to a lower temperature set point on unit control.

When mode button is pressed, the compressor may shut off. Wait approximately 3 minutes 

for compressor to turn on after time delay when in cool mode.

Outdoor temp. may be below 62°F (17°C). To defrost coil, set unit to FAN ONLY mode.

Air filter may be dirty, clean filter. Refer to Care and Cleaning section. To defrost, set unit to 

FAN ONLY mode.

Thermostat set too cold for cooling. To defrost the coil, set unit to FAN ONLY mode. Then, 

set temperature to a higher setting.

Dirty air filter/air restricted. Clean air filter and remove any obstacles blocking air flow.

Before calling for service, review this list. It may save you time and unnecessary expense. This list includes 

common occurrences that are not the result of defective workman-ship or materials in this appliance.

Louvers positioned improperly. Position louvers for better air distribution. Ensure louvers are not closed.

faster.

Doors, windows, registers, etc., are open allowing air to escape. Close those open areas.

Front of units may be blocked by drapes, blinds, furniture, etc., restricting air distribution. 

Clear blockage in front of unit.

move air past

17

Water dripping
OUTSIDE when

unit is cooling.

Unit removing large quantity of moisture from humid room. This is normal during
excessively humid days.

Remote Sensing
Deactivating
Prematurely
(some models)

Remote control not located within range. Place remote control within 20 feet & 180 ,
radius of the front of the unit.

Remote control signal obstructed. Remove obstruction.

Room too cold

Set temperature too low. Increase set temperature.

Содержание REG-123M

Страница 1: ...www marsdelivers com 1900 Wellworth Ave Jackson MI 49203 517 787 2100 www marsdelivers com OWNER S MANUAL Room Air Conditioner with R 410A REG 81M REG 123M REG 81J REG 123J ...

Страница 2: ...er for installation of this unit If the power cord needs to be replaced replacement work shall be performed by authorized service personnel only Installation work must be performed in accordance with the national and local electric codes and must be performed by authorized personnel only NOTE All the illustrations in this manual are for explanation purposes only Your air conditioner may be slightl...

Страница 3: ...er cord close to heating appliances Do not damage or use an unspecified power cord Do not direct airflow at room occupants only Always install circuit breaker and a dedicated power circuit Do not open the unit during operation Do not use the power cord near flammable gas or combustibles such as gasoline benzene thinner etc Do not disassemble or modify unit WARNING 2 Otherwise it may cause electric...

Страница 4: ...without filters may cause failure It contains contaminants and could make you sick Always insert the filters securely Clean filter once every two weeks Do not drink water drained from air conditioner It may cause an injury due to sharp edges of components When the air filter is to be removed do not touch the metal parts of the unit Water may enter the unit and degrade the insulation It may cause a...

Страница 5: ...OWNER S MANUAL REG 81M 123M 4 Heat Controller Inc Room Air Conditioner with R 410A Owner s Manual 4 Please refer to the section Operation of Current Device for details ...

Страница 6: ... not have there features and display lights Check the actual unit you purchased to determine if these options apply Owner s Manual Room Air Conditioner with R 410A Heat Controller Inc 5 Cooling operation Outdoor Temp 64 4 109 4 F 18 43 C T1 Environment 69 8 125 6 F 21 52 C T3 Environment Indoor Temp 62 6 89 6 F 17 32 C T1 Environment 62 6 89 6 F 17 32 C T3 Environment Heat operation Outdoor Temp 2...

Страница 7: ... Low Med or High Each time the button is pressed the fan speed mode is shifted When the unit is operating in Dry mode the fan speed is automatically controlled at Low fan speed Press or hold either Temp Timer Up or Down button until the desired temperature is seen on the display This temperature will be automatically maintained anywhere between 62 F 17 C and 86 F 30 C If you want the display to re...

Страница 8: ...om temperature The air conditioner will control room temperature automatically around the temperature set point selected To operate in Fan only Use this function when cooling is not desired such as for room air circulation or to exhaust stale air on some models Remember to open the vent during this function but keep it closed during cooling for maximum cooling efficiency You can choose any fan spe...

Страница 9: ...Conditioner with R 410A Owner s Manual 8 AIR CONDITIONER FEATURES CONTINUED TIMER AUTO START STOP FEATURE Press or hold the Temp Timer UP or DOWN button to change the Auto time by 0 5 hour increments up to 10 hours then count down the time remaining until start ...

Страница 10: ...grees Celsius To convert from one to the other press and hold the Left and Right Temp Timer buttons at the same time for 3 seconds 3 3 AIR CONDITIONER FEATURES CONTINUED The 3 way air directional louvers allow you to direct the air flow up and left or right throughout the room as needed To adjust the air directional louvers side to side use the center handles as you move it side to side ...

Страница 11: ...ith R 410A Owner s Manual 10 Phillips screws Carefully inspect the location where the air conditioner will be installed Be sure it will support the weight of the unit Make sure the air conditioner does not fall and remains upright during installation coils to prevent injury ...

Страница 12: ...AL REG 81M 123M 11 Owner s Manual Room Air Conditioner with R 410A Heat Controller Inc 11 No obstalces blocking air inlets or outlets to 36 91 4 cm max Loosen 1 shipping screw from each side of the cabinet FIG 3 1 ...

Страница 13: ...OWNER S MANUAL REG 81M 123M 12 Heat Controller Inc Room Air Conditioner with R 410A Owner s Manual 12 1 2 3 4 ...

Страница 14: ...OWNER S MANUAL REG 81M 123M 13 Owner s Manual Room Air Conditioner with R 410A Heat Controller Inc 13 ...

Страница 15: ...REG 81M 123M 14 Heat Controller Inc Room Air Conditioner with R 410A Owner s Manual 14 NOTE Do not block the louvers on the air conditioner cabinet or your unit will not perfrom properly SEE NOTE ABOVE SEE NOTE ABOVE ...

Страница 16: ... s Manual Room Air Conditioner with R 410A Heat Controller Inc 15 It is recommended to use 1 2 5 cm or thicker lumber for wood frame For through the wall installations if needed install molding not provided around the room side of cabinet ...

Страница 17: ...OWNER S MANUAL REG 81M 123M 16 Heat Controller Inc Room Air Conditioner with R 410A Owner s Manual 16 104 F 40 C ...

Страница 18: ...ow water drainage Refer to installation instructions check with installer Dirty air filter air restricted Clean air filter Air movement sound This is normal If too loud set to a slower FAN setting Outside temperature extremely hot Set FAN speed to a Higher setting to bring air past cooling coils more frequently Window vibration poor installation Refer to installation instructions or check with ins...

Страница 19: ... warranty begins on the date of shipment from the factory REMEDY PROVIDED BY THE LIMITED EXPRESS WARRANTY The sole remedy under the Limited Warranty is replacement of the defective unit Labor to diagnose and replace the defective unit is not covered by this Limited Express Warranty If for any reason the replacement product is no longer available during the warranty period Comfort Aire shall have t...

Страница 20: ...LWLRQDOO WKH LQVWDOOHU LV UHVSRQVLEOH IRU YHULI LQJ GLPHQVLRQDO GDWD RQ WKH DFWXDO SURGXFW SULRU WR EHJLQQLQJ DQ LQVWDOODWLRQ SUHSDUDWLRQV QFHQWLYH DQG UHEDWH SURJUDPV KDYH SUHFLVH UHTXLUHPHQWV DV WR SURGXFW SHUIRUPDQFH DQG FHUWLILFDWLRQ OO SURGXFWV PHHW DSSOLFDEOH UHJXODWLRQV LQ HIIHFW RQ GDWH RI PDQXIDFWXUH KRZHYHU FHUWLILFDWLRQV DUH QRW QHFHVVDULO JUDQWHG IRU WKH OLIH RI D SURGXFW 7KHUHIRUH LW ...

Отзывы: