TROUBLESHOOTING

If the air handler fails to operate, check the following:

•  Is the electric turned on?

•  Is the thermostat operating properly?

•  Are the blower compartment door(s) in place?

•  Is the air handler disconnect closed?

•  Has the circuit breaker tripped or the control board fuse 

burned open?

•  Are any manual reset switches open?

•  Is the filter dirty or plugged?

•  Is the LED on both control boards constantly ON? If 

not, refer to Tables 3 or 4 to determine fault condition.

RED LED (AN2)

DIAGNOSTIC

OFF

Control Fault (No Power)

Flash

Blower Fault

ON

Normal Operation

Table 3. Air handler Control Board Fault Conditions

FURNACE SIZE (BTUH)

FILTER SIZE

24K & 30K

12 x 20 x 1

36K & 42K

18 x 20 x 1

48K & 60K

20 x 20 x 1

Table 2. Filter Sizes

UNIT MAINTENANCE

Proper maintenance is most important to achieve the best 
performance from a air handler. Some of the components 
and their locations are shown in Figure 13 (page 18). If 
any component of the air handler must be replaced, use 
only factory authorized replacement parts specified in the 
Replacement Parts List provided online.

 WARNING:

ELECTRICAL SHOCK, FIRE OR EXPLOSION 

HAZARD

Failure to follow safety warnings exactly could 
result in serious injury or property damage.
Improper servicing could result in dangerous 
operation, serious injury, death or property 
damage.

• Before servicing, disconnect all electrical power 

to air handler.

• When servicing controls, label all wires prior 

to disconnecting. Reconnect wires correctly

.

• Verify proper operation after servicing.

•  These maintenance instructions are primarily intended 

to assist qualified technicians experienced in the proper 

maintenance and operation of this appliance.

•  Always  reinstall  the  doors  on  the  air  handler  after 

servicing or cleaning/changing the filters. 

Do not operate 

the air handler without all doors and covers in place.

•  Verify that the thermostat is properly installed and is 

not being affected by drafts or heat from lamps or other 

appliances.

•  To  achieve  the  best  performance  and  minimize 

equipment failure, it is recommended that a yearly 

maintenance checkup be performed. At a minimum, 

this check should include the following items:

Air Filter(s)

HMG**F1E, HMG**X1E & HCG**V1E series air handlers 
are not supplied with a single air filter when shipped from 
the factory. It is recommended that the filter be cleaned 
or replaced monthly. Newly built or recently renovated 
homes may require more frequent changing until the 
construction dust has minimized. Filter sizes shown in 
Table 2 are available at most local retailers.

 WARNING:

Never operate the air handler without a filter in 

place. Dust and lint in the return air can build 

up on internal components, resulting in loss of 

efficiency, equipment damage, and possible fire.

Filters designed to remove smaller particles such as 
pollen, may require additional maintenance.

Blower Compartment

Dirt and lint can create excessive loads on the motor 
resulting in higher than normal operating temperatures 
and shortened service life. It is recommended that the 
blower compartment be cleaned of dirt or lint that may 
have accumulated in the compartment or on the blower 
and motor as part of the annual inspection.

Blower Fan Wheel

Inspect the blower wheel blades for accumulations of dirt 
and clean if necessary. Inspect mounting nut for tightness 
when done.

Blower Motor & Assembly

Inspect the blower assembly and motor mounting 
brackets for tightness and corrosion. Correct deficiencies 
if necessary. The blower motor contains sealed bearings 
and under normal operating conditions, no maintenance 
is necessary for the life of the equipment.

Table 4. Motor Control Board Fault Conditions

DIAGNOSTIC

GREEN

LED

RED

LED

Fixed

Speed

Furnaces

Control Fault (No Power)

Off

Off

Normal Operation

On

On

Motor Fault

On

Flash

Twin Fault (no motor fault)

Flash

On

Communications Fault

Flash

Flash

Variable

Speed

Furnaces

Control Fault (No Power)

Off

Off

Normal Operation

On

On

Motor Fault

On

Flash

Communications Fault

Flash

Flash

Содержание HCG V1E Series

Страница 1: ...e adjustment or maintenance may cause explosion fire electrical shock or other hazardous conditions which may result in personal injury or property damage Unless otherwise noted in these instructions...

Страница 2: ...nuously 14 Selecting Continuous Low Spd Fan Operation 14 Turning the Blower Off 14 System Cooling 14 System Heating 14 Selecting minimum Electric Heat Airflow 14 Blower Configurations 14 Determining N...

Страница 3: ...Unqualified individuals should not attempt to interpret these instructions or install this equipment Failure to follow safety recommendations could result in possible damage to the equipment serious p...

Страница 4: ...s may require additional clearance to equipment Refer to applicable building codes for details Static pressure drop through louvered openings and through return air plenums should be considered in the...

Страница 5: ...ely sized to the return air duct opening or filter rack located in the bottom of the unit Accessing the filter does not require tools and can be removed from the front of the unit by removing the filt...

Страница 6: ...r installations require a 1 4 thick noncombustible resilient gasket to be used whenever the supplyorreturnairductspassthroughthefloor Thegasket should be positioned between the duct unit and floor Upf...

Страница 7: ...of the unit to block bypass air 4 Remove the corresponding drain line knockout from the coil access door to allow access to the horizontal drain 5 Replace the door and attach the drain line Horizonta...

Страница 8: ...er suitable material where they pass against sharp sheet metal edges HMG F1E HMG X1E HCG V1ESeriesairhandlers are charged through service valves on the end of the liquid tube for each circuit These mu...

Страница 9: ...rform steps 1 9 to confirm that the orifice size meets the requirements outlined in the outdoor unit installation manual 1 Remove the cap from the end of the liquid line 2 Verify pressurization by dep...

Страница 10: ...ld maintain a minimum horizontal slope in the direction of discharge of not less than 1 vertical for every 10 ft of horizontal run If the air handler is located in or above a living space where damage...

Страница 11: ...ine voltage power supply to this unit Use proper code agency listed conduit and a conduit connector for connecting the supply wires to the unit Aluminum supply wire may be used if a heater kit is inst...

Страница 12: ...ling See Figures 14 or 15 page 23 and Table 12 pages 29 31 for control board modes and actions Twinning HMG F1E series air handler s are not supplied with a built in twinning capability To connect two...

Страница 13: ...stallation instructions included with the kit Wire the humidistat through the low voltage wire entrance in the air handler to the control board terminal marked DEHUM Wirethehumidistattoopenonriseinhum...

Страница 14: ...the register s Ensure that there are no obstructions at the registers or in the ducts Selecting continuous low speed fan operation Standard Blower The air handler is equipped with an option of contin...

Страница 15: ...rflow setting will increase the energy efficiency and capacity but will also decrease the supply air temperature For maximum capacity and energy efficiency select an airflow at or near the top of the...

Страница 16: ...g affected by drafts or heat from lamps or other appliances To achieve the best performance and minimize equipment failure it is recommended that a yearly maintenance checkup be performed At a minimum...

Страница 17: ...5 8 17 8 11 4 3 1 4 2 5 8 11 8 K O typ 13 4 K O typ 1 7 8 3 5 8 5 5 8 DETAIL D 3 1 4 2 1 4 15 1 4 13 SUCTION LIQUID W 1 1 8 1 7 8 7 8 K O H 22 A FURNACE SIZE BTUH H W A Detail D 24K 30K 43 5 16 14 3 1...

Страница 18: ...Blower Motor Transformer Capacitor Circuit Breaker 60A Heating Element Assembly Filter Tracks Blower Wheel Blower Housing Motor Control Board Control Board Filter Door Upper Door Assembly Lower Door...

Страница 19: ...03 0 15 0 28 0 41 0 54 0 68 High 1427 1385 1333 1270 1196 1113 1018 913 Corrected ESP1 0 00 0 00 0 00 0 09 0 23 0 36 0 50 0 64 HMG42F1E Low 1324 1302 1271 1233 1187 1134 1072 1003 Corrected ESP1 0 00...

Страница 20: ...50 1 1 1 0 1155 1105 1060 1010 965 920 870 825 0 0 0 1 1230 1185 1140 1090 1045 1010 965 920 1 0 0 1 1285 1260 1210 1165 1125 1080 1040 1010 0 1 0 1 1330 1290 1245 1205 1170 1125 1085 1045 1 1 0 1 139...

Страница 21: ...0 1 1 4 TON 700 0 1 0 0 1350 0 1 0 0 750 0 1 0 1 1400 0 1 0 1 800 0 1 1 0 2 5 TON 1450 0 1 1 0 850 0 1 1 1 1500 0 1 1 1 875 1 0 0 0 1550 1 0 0 0 950 1 0 0 1 1600 1 0 0 1 5 TON 1050 1 0 1 0 3 TON 1650...

Страница 22: ...750 1 20 1500 1 0 1 1 0 800 1 25 n a 1 0 1 1 1 850 1 30 n a 1 1 0 0 0 875 1 1 0 0 1 950 1 1 0 1 0 1050 1 1 0 1 1 1150 1 1 1 0 0 1250 1 1 1 0 1 1350 1 1 1 1 0 1400 1 1 1 1 1 1600 HCG48V1E HCG60V1E Cool...

Страница 23: ...TC_R HEAT COOL EAC L 1 L 2 P2 R C G W Y 3A Fuse HEATER P1 C R G Y2 Y O 1W 2W 1Y L LED 1 HEATER P1 L 2 HUM EAC P2 3A Fuse P3 Figure 14 Single Stage Control Board Figure 15 Two Stage Control Board ELECT...

Страница 24: ...W C EXPANSION PORT R RED GREEN TEST PORT BLOWER MOTOR RED INPUTS COOL HEAT FAN SPEED OUTPUTS STATUS LIGHTS 2 3 4 5 6 7 8 OFF ON A B GREEN RED STATUS NOT USED TEST PORT BLOWER MOTOR R C Y1 TWIN DEHUM...

Страница 25: ...PLUG HOUSING WHEN HEATER KIT NOT INSTALLED BLACK RED WHITE BROWN BROWN BLACK WHITE RED GRAY YELLOW WHITE GREEN GRAY RED NOTES 1 The blower motor speed tap connection may not be as shown See the Instal...

Страница 26: ...BLACK WHITE GRAY RED BLACK RED WHITE BLACK MOTOR 6 PIN PLUG HARNESS WHITE BLACK BLUE GREEN YELLOW ORANGE RED BROWN BLUE GREEN ORANGE RED BROWN YELLOW CUT WIRES TO REMOVE PLUG HOUSING WHEN HEATER KIT N...

Страница 27: ...R BLACK WHITE 6 PIN PLUG 6 PIN PLUG BLACK WHITE BLACK WHITE GRAY RED BLACK HARNESS HARNESS GREEN BROWN RED ORANGE YELLOW GREEN BLUE BROWN RED ORANGE YELLOW GREEN BLUE RED CUT WIRES TO REMOVE PLUG HOUS...

Страница 28: ...009Q XX 29 7 30 26 1 30 015Q XX 45 9 50 40 2 45 HMG42F1E None 3 1 3 1 15 15 3 1 3 1 15 15 005H XX 28 1 28 1 30 30 24 8 24 8 25 25 008H XX 42 7 42 7 45 45 37 4 37 4 40 40 010H XX 53 1 53 1 60 60 46 5...

Страница 29: ...B CIRCUIT C SINGLE CIRCUIT CIRCUIT A CIRCUIT B CIRCUIT C SINGLE CIRCUIT CIRCUIT A CIRCUIT B CIRCUIT C SINGLE CIRCUIT CIRCUIT A CIRCUIT B CIRCUIT C SINGLE CIRCUIT HMG24X1E HMG30X1E HCG24V1E HCG30V1E No...

Страница 30: ...seconds delay Stage 3 Heat on after 10 seconds delay Stage 4 Heat on after 15 seconds delay Stage 5 Heat on after 20 seconds delay Stage 6 Heat on after 25 seconds delay OFF Heat stages off instantly...

Страница 31: ...econd delay Stage 2 Heat on after 5 seconds delay Stage 3 Heat on after 10 seconds delay Stage 4 Heat on after 15 seconds delay Stage 5 Heat on after 20 seconds delay 30 KW Stage 1Heat on instantly Co...

Страница 32: ...ing common sense plays an important role as well Pay attention to all safetywarningsandanyotherspecialnoteshighlightedinthemanual Improper installation of the air handler or failure to follow safety w...

Отзывы: