Horizontal/Side Discharge Condensing Units

The length of refrigerant lines and the number of 

bends determine the pressure drop which affects 

to the compressor. The outdoor unit connections 

same diameter as the connections provided at 

the service valves. Up sizing of lines can result 

in inadequate oil return to the compressor and 

excessive refrigerant charge and will void the 

warranty 

[See Table 1].

Choose a location that places the condensing 

unit as close to the indoor unit as possible. The 

maximum separation is dependent on model. 

Use only clean refrigeration grade tubing. Avoid 

piping on wet or rainy days. Always keep the tube 

connections. Remove burrs from cut ends of tubing. 

Use tube benders to avoid kinking.

with a wall thickness of at least 3/8”. Support the 

tubing adequately to avoid sags that can trap oil. 

Isolate the tubing so as not to transmit noise to the 

building structure. Avoid sharp edges that could cut 

the tubes. Maximum vertical lift (compressor above 

evaporator) is dependent on model. Trap risers with 

a ‘P’ trap every 10 feet.

REFRIGERANT PIPING

LEAK TEST, 

EVACUATION 

& RELEASE OF 

REFRIGERANT 

The condensing unit is supplied with R-410a 

units. Charge must be added for interconnecting 

tubing.

The unit’s service valves are shipped in the closed 

connections and evacuation are completed. 

The recommended procedure for leak test, 

evacuation, and release of refrigerant is 

outlined below:

indoor and outdoor units using high temperature 

brazing alloy.

2. Connect a charging manifold to the service ports 

provided at the service valves.

3. Pressurize the lines and evaporator with 

nitrogen and leak check all connections with 

soap bubbles. Repair as necessary any 

faulty joints. If brazing is required be sure to 

RELEASE THE NITROGEN FIRST. Re-test as 

needed.

4. Connect a vacuum pump to the manifold center 

connection, start the pump and open the 

manifold valves.

5. Evacuate to 500 microns or less for a minimum 

of 30 minutes. Close the manifold valves and 

shut off the pump. Note the vacuum reading and 

wait 15 minutes. Take a new vacuum reading. A 

reading of 800 microns or higher indicates the 

presence of moisture or a leak.

6. Repair as necessary and repeat steps 3, 4 & 5.

disconnect the vacuum pump.

8. Remove the caps from the services valves. 

Open the valves to the fully ‘back-seat’ position. 

Replace service valve caps and tighten.

WARNING

It is illegal to discharge refrigerant into the 

atmosphere. Use proper reclaiming methods 

and equipment when working on the refrigerant 

containing parts of the unit. Service should be 

performed by a QUALIFIED service agency and 

Refrigerant Piping

Model No.

CMA 18 CMA 24 CMA 30 CMA 36

Liquid-Gas

In. 1/4 - 1/2

3/8 - 3/4

Max. Refrigerant 

Line Length*

Ft.

82

98

Max. Elevation

Vertical Lift**

Ft.

33

49

*Minimum pipe length must not be less that 15 feet.

** “P” trap risers every 10 ft. when outdoor unit is installed 

above indoor unit.

AITONS EQUIPMENT

Содержание CMA18SB-1

Страница 1: ...INSTALLATION OPERATION MAINTENANCE MANUAL Horizontal Side Discharge Condensing Units Models CMA18SB 1 CMA24SB 1 CMA30SB 1 CMA36SB 1 AITONS EQUIPMENT Guelph ON N1H 6H9 1 888 744 2911 www aitons com ...

Страница 2: ...tion and Maintenance TABLE OF CONTENTS Safety Precautions 3 General Operating Instructions 4 General Product Information 5 Outdoor Unit Installation 6 7 Unit Wiring 8 10 Wiring Diagrams 8 10 Refrigerant Piping 11 Leak Test Evacuation Release of Refrigerant 11 Initial Start Up Checks 12 Field Charging 12 Field Inspection 12 ...

Страница 3: ... injury 8 Do not modify the length of the power supply cord or use an extension cord and do not share the single outlet with other electrical appliances Otherwise it may cause fire or electrical shock 1 This equipment must be properly grounded and installed with and ground leakage current breaker electrical shock otherwise it may cause 2 Do not install the unit in place where leakage of flammable ...

Страница 4: ... unit will not cycle more than 10 times per hour If you notice more frequent starts call your service contractor 4 For energy conservation reasons you may want to set your thermostat at a higher temperature when you are away Do not raise the temperature setting by more than 5 degrees Changing the temperature by more than 5 degrees or shutting the unit off can actually cost more than leaving the se...

Страница 5: ...ndensing units are designed to be compatible with most major brands of domestic evaporator coils air handlers Imported ductless air handlers maybe used but often do not include an expansion device A properly sized thermostatic expansion valve is recommended Consult AHRI s THERMOSTAT AND INDOOR FAN TIME DELAY All indoor units should include a fan time delay This may be accomplished by using a digit...

Страница 6: ... unit In climates where snow is a consideration locate the unit away from areas prone to drifting Ensure the location of the unit will not be subject to snow drifts heavy accumulation of snow or leaves or other seasonal debris If unavoidable provide the awning for the unit OUTDOOR UNIT INSTALLATION An awning can be built over the outdoor unit to prevent direct sunlight or rain exposure or snowfall...

Страница 7: ...air inlets and outlets are not obstructed See Fig 4 Anchor the outdoor unit with a 10mm 3 8 inch diameter bolt and nut tightly on a concrete or rigid surface See Fig 5 Anchoring is especially recommended in seaside high wind applications and or areas prone to earthquakes Fig 4 Fig 5 1 Split type outdoor unit clearances 1 Split type outdoor unit dimensions Units in inches AITONS EQUIPMENT ...

Страница 8: ...r improper electrical supply will likely result in failure of the compressor and other electrical components and voids the warranty NOTE The supply voltage must be consistent with the rated voltage of the air conditioner not to exceed 10 Ensure the unit is properly grounded CAUTION Incorrect wiring connections may cause electrical parts to malfunction All wiring must comply with local and national...

Страница 9: ...g Units OUTDOOR UNIT WIRING CONNECTION continued NOTE Please refer to the installation instructions of the 24V thermostat used in conjunction with this unit for additional wiring instructions TERMINAL BLOCK OF OUTDOOR UNIT AITONS EQUIPMENT ...

Страница 10: ...10 Horizontal Side Discharge Condensing Units AITONS EQUIPMENT OUTDOOR UNIT WIRING CONNECTION continued CMA18SB 1 CMA24SB 1 CMA30SB 1 CMA36SB 1 ...

Страница 11: ... leak test evacuation and release of refrigerant is outlined below indoor and outdoor units using high temperature brazing alloy 2 Connect a charging manifold to the service ports provided at the service valves 3 Pressurize the lines and evaporator with nitrogen and leak check all connections with soap bubbles Repair as necessary any faulty joints If brazing is required be sure to RELEASE THE NITR...

Страница 12: ...ple of minutes of run time 4 Proceed to the FIELD CHARGING section of these instructions FIELD CHARGING to a large extent on a proper system charge Time spent on getting the charge right at start up will payoff in the long run Operating conditions and indoor and outdoor temperature and humidity all have an effect on the system pressures and superheat conditions Charge must be added for the interco...

Страница 13: ...13 4 2014 subject to change without notice AITONS EQUIPMENT Guelph ON N1H 6H9 1 888 744 2911 www aitons com ...

Отзывы: