508183-01
Issue 2114
Page 48 of 52
Maintenance
ELECTRICAL SHOCK, FIRE, OR EXPLOSION
HAZARD.
Failure to follow safety warnings exactly could result in
dangerous operation, serious injury, death or property
damage.
Improper servicing could result in dangerous operation,
serious injury, death, or property damage. Before
servicing, disconnect all electrical power to furnace.
When servicing controls, label all wires prior to
disconnecting. Take care to reconnect wires correctly.
Verify proper operation after servicing.
WARNING
At the beginning of each heating season, system should
be checked as follows by a qualified service technician:
Blower
Check the blower wheel for debris and clean if necessary.
The blower motors are prelubricated for extended bearing
life. No further lubrication is needed.
The blower access panel must be securely in place
when the blower and burners are operating. Gas fumes,
which could contain carbon monoxide, can be drawn
into living space resulting in personal injury or death.
WARNING
Filters
All air filters are installed external to the unit. Filters should
be inspected monthly. Clean or replace the filters when
necessary to ensure proper furnace operation. Table 18
lists recommended filter sizes.
If a high-efficiency filter is being installed as part of this
system to ensure better indoor air quality, the filter must
be properly sized. High-efficiency filters have a higher
static pressure drop than standard-efficiency glass/foam
filters. If the pressure drop is too great, system capacity
and performance may be reduced. The pressure drop
may also cause the limit to trip more frequently during
the winter and the indoor coil to freeze in the summer,
resulting in an increase in the number of service calls.
Before using any filter with this system, check the
specifications provided by the filter manufacturer against
the data given in the appropriate Product Specifications.
IMPORTANT
Furnace Cabinet Width
Minimum Filter Size
17-1/2”
16 x 25 x 1 (1)
21”
Table 18.
Exhaust and Air Intake Pipes
Check the exhaust and air intake pipes and all connections
for tightness and to make sure there is no blockage.
NOTE:
After any heavy snow, ice or frozen fog event the
furnace vent pipes may become restricted. Always check
the vent system and remove any snow or ice that may be
obstructing the plastic intake or exhaust pipes.
Electrical
Electric Shock Hazard.
Can cause injury or death. Unit must be
properly grounded in accordance with national
and local codes.
WARNING
Fire Hazard. Use of aluminum wire with this product
may result in a fire, causing property damage, severe
injury or death. Use copper wire only with this product.
WARNING
Failure to use properly sized wiring and circuit breaker
may result in property damage. Size wiring and circuit
breaker(s) per Technical Specifications and unit rating
plate.
WARNING
1.
Check all wiring for loose connections.
2.
Check for the correct voltage at the furnace (furnace
operating).
3.
Check amp-draw on the blower motor.
Motor Nameplate____________ Actual____________
Condensate Hose Screens (Figure 55)
Check the condensate hose screens for blockage and
clean if necessary.
1.
Turn off power to the unit.
2.
Remove hoses from cold end header box. Twist and
pull screens to remove.
3.
Inspect screens and rinse with tap water if needed.