Tech Setup Steps
LCD Will Show Adjustment Options
Default
Room Temperature
Calibration
You can adjust the
room temperature
display to read up to 4˚
above or below the
factory calibrated
reading.
Pair
Transmitter and
receiver pair code
F or C
Select for Fahrenheit
temperature read out
select C for Celsius
read out.
Compressor
Short Cycle
Delay
The compressor short
cycle delay protects the
compressor from short
cycling. This feature will
not allow the compressor
to be turned on for 5
minutes after it was last
turned off.
Change Over Valve
Selection
Select 0 for a changeover
valve that energizes in
cooling. Select b for a
change over valve that
energizes in heating.
Heat Pump
When turned on the
thermostat will operate
a heat pump.Y will be
the first stage of heat &
cool, W will be the
second stage of heat.
Heating Temperature
Setpoint Limit
This feature allows you
to set a maximum heat
setpoint value.The
setpoint temperature
cannot be raised above
this value.
Cooling Temperature
Setpoint Limit
This feature allows you
to set a minimum cool
setpoint valve. The
setpoint temperature
cannot be lowered
below this value.
44.0˚ - 90.0˚ F
7.0˚ - 32.0˚ C
44.0˚ - 90.0˚ F
7.0˚ - 32.0˚ C
OFF configures the
thermostat for non
heat pump systems.
ON configures the
thermostat for heat
pump systems.
0 for cooling changeover
valve.b for heating
changeover valve.
Calibration
Com
Delay
F for Fahrenheit
C for Celsius
Selecting ON will not
allow the compressor to
be turned on for 5
minutes after the last time
the compressor was
switched off. Select OFF
to remove this delay.
Press and hold
“+” for 3 seconds
until “LE” is flashed.
Then release