9.3.10 Inverter compressor drive error diagnosis and solution
(P4)
Error Code
P4
Malfunction conditions
An abnormal inverter compressor drive is detected by a special
detection circuit, including communication signal detection,
voltage detection, compressor rotation speed signal detection
and so on.
Possible
causes
●
Wiring
error
●
IPM malfunction
●
Outdoor fan ass
embl
y faulty
●
Compressor malfunction
●
Outdoor PCB faulty
Troubleshooting:
Check if the wiring between
main PCB and compressor
connected well?
Correct the connection or
replace the wires and
connectors.
No
Check if the IPM installed correctly.
Correct the installation,
tighten the screws and
apply silicon grease.
No
IPM continuity check. Check if the
IPM terminal resistance values are
uniform.
Yes
Replace the IPM board or replace
the main PCB if the IPM board and
main PCB are integrated together.
No
Check if the outdoor fan runs
properly or the outdoor unit
ventilation is good.
Yes
No
Please refer to the solution of
【
Fan
Speed Has Been Out Of Control
】
malfunction
Yes
Check if the compressor resistance
values are uniform .
No
Replace the compressor.
Yes
Replace the outdoor main PCB if the
main PCB and IPM are separate.
Check the reactor or
i
nduct
or
.
Is it normal?
No
Replace the reactor
or
in
duct
or
Yes
Yes
Содержание A-SVH09SA-0
Страница 7: ...Service Manual SVH 09 12 18 24 Series 7 2 2 Indoor Outdoor units ...
Страница 10: ...Service Manual SVH 09 12 18 24 Series 10 For Mounting Plate D ...
Страница 29: ...Service Manual SVH 09 12 18 24 Series 29 9 2 Outdoor unit error display TBD For A SVH09SA 0 A SVH12SA 0 ...
Страница 30: ...Service Manual SVH 09 12 18 24 Series 30 For A SVH09SA 1 A SVH12SA 1 ...
Страница 31: ...Service Manual SVH 09 12 18 24 Series 31 For A SVH18SA 1 A SVH24SA 1 ...
Страница 44: ...Service Manual SVH 09 12 18 24 Series 44 P W N U ...
Страница 45: ...Service Manual SVH 09 12 18 24 Series 45 41 N V N W ...