 COMEX S.A. 

 

 

 

 

CMX: 

201402.03 PL

 

UPS COVER Basic 1K (EPO) 

Quick Start Guide 

 

Appearance and connection 
 

 

COVER Basic 1K (EPO) power supply - rear view 

 

Power socket. 

UPS power circuit fuse. 

USB communication port. 

RS-232 communication port. 

Communication port slot (SNMP). 

Output outlets. 

Remote Emergency power off (EPO) input. 

 

EPO connector - emergency stop switch against fire 
 

To the connector marked EPO connect the emergency switch against fire. 

 

The standard configuration of the EPO is an NC (normally closed) type connector, i.e. for the correct 
operation of the UPS it is necessary to leave the jumper in the connector or connect a circuit breaker 
ensuring short circuit. Opening the EPO connector immediately disconnects the UPS output voltage 
and switches the UPS to Stand-By mode. 

 

NOTE:  If  it  is  necessary  to  change  the  EPO  configuration  to  NO  (normally  open)  please  contact  an 
authorized service center or supplier. 

 

 

Содержание COVER Basic 1K

Страница 1: ...h against fire To the connector marked EPO connect the emergency switch against fire The standard configuration of the EPO is an NC normally closed type connector i e for the correct operation of the...

Страница 2: ...UPS to activate the test OFF ENTER UPS shutdown Press and hold for 2 seconds to turn off the UPS or switch to Bypass mode depending on the selected operation configuration options Confirm Selection P...

Страница 3: ...on programmable outputs Indicates whether a programmable socket group is configured Information about the operating mode Indicates that the UPS is connected to the 230V mains Indicates the UPS is runn...

Страница 4: ...erter available not available ENA Converter function available DIS Converter function unavailable default 03 Frequency setting Frequency setting for battery operation BAT 50 50Hz output frequency BAT...

Страница 5: ...olds results in the inaccessibility of the bypass path HLS Bypass high voltage threshold Using the arrow keys it is possible to select the voltage of 230V 264V default 264V LLS Bypass low threshold Us...

Страница 6: ...the range of 40 70Hz it is possible to set a fixed value of the output voltage frequency of 50 or 60Hz This mode also charges the batteries Battery operation mode In the event of a power failure or w...

Страница 7: ...s Battery failure Beep every 2 seconds UPS off Bypass out of tolerance Beep every 2 seconds Bypass frequency unstable Beep every 2 seconds Error EEPROM Beep every 2 seconds Fan error Beep every 2 seco...

Страница 8: ...tion follow the instructions on the computer screen You must restart your computer after the installation process is complete Restarting the computer will automatically launch ViewPower as shown by th...