background image

IOM - BALL CHECK VALVES, UNIWAT® 3240/3141

©COMEV

AL

 V

A

L

VE SYSTEMS 

T

e

chnical Dept. Ref. IOM-BALL

 CHECK V

A

L

VES, UNIW

A

T® 3240/3141 - Ed.16/07

Comeval V

alve Systems reserves the right to alter any technical data contained in this Manual without prior notice. Regularly u

pdated data on www

.comeval.es

7. CARE AND MAINTENANCE

The operator must de

¿

 ne maintenance and maintenance-intervals to meet requirements.

- Check for body, seat area and connections tightness, and valve smooth operation without additional tools.

- When reassembling the cover, clean gasket seat surface and use a new gasket if necessary. Then tighten the cover 
bolts evenly crosswise with moderate and uniform torque. Retighten bolts crosswise if any leakage is detected under 
pressure. 
After any maintenance work please refer to chapters 5 and 6 for installation / commissioning.

Recommended Spare parts:

Use only original spare parts.
It is advisable to keep body/cover gaskets and balls as spare parts. Type and number of each spare part to be stored 
according to many factors: service level, valves quantity, etc. In many cases a good choice is to keep complete valves 
as spare part.

8. TROUBLESHOOTING

In the event of malfunction or faulty operating performance, check that the installation and adjustment work has been 
carried out and completed in accordance with this Manual.

9. TROUBLESHOOTING TABLE

Technical support always available through our website www.comeval.es or your local distributor.

 

   

ATTENTION!  

- It is essential that the safety regulations are observed when identifying faults.

Page 5

 

   

ATTENTION!  

- Before disassembling the valve, note chapters 3, 10 & 12.
- There is a crushing hazard between the ball and the body seat area. Ensure the ball is in rest position in 
case a hand is introduced inside the valve.
- Only carry out maintenance work in the pipework when the valve has been secured from operation.

- Check the valve surface inside and outside and retouch coating protection when needed. If advanced 
corrosion or erosion is observed, double check service and valve features and replace the valve properly.

 

   

ATTENTION!

- Read the complete Manual before carrying out installation and repair work.
- Read chapter 6 before recommissioning.

FAULT

POSSIBLE CAUSE

CORRECTING MEASURES

No 

À

 ow

Not enough 

À

 ow

Flange covers or protection not removed

Clear valve entrances

Improper installation position

Check installation position

Piping clogged

Check piping system

Not enough pressure or 

À

 ow

Check working parameters

Ball blocked

Check and try to unblock

Broken 

À

 ange

Bolts not properly tightened        
Mating 

À

 anges not properly aligned

Re-align piping and 

¿

 t new valve

Valve not closing with       
reverse 

À

 ow

Ball surface or seat area damaged                    Check valve components
Very low reverse pressure      

Check the system

Improper installation position

Check installation position

Ball blocked

Check and try to unblock

Ball stick

Fine vacuum service

Use a degassing connection

Leakage between body 
and cover

Cover bolts loose or gasket damaged

Retighten cover bolts or change gasket

Отзывы: