Comet U8415 Скачать руководство пользователя страница 2

 

COMET SYSTEM

, s.r.o., Bezrucova  2901 

 

Specifications are subject to change without notice. 

756 61 Roznov pod Radhostem, Czech Republic

 

 

  ie-lgr-U8415-01

 

 

LED flashing when the device is 

switched On

 indicates

 

the following conditions: 

The factory settings from the manufacturer (most settings 

 number of beeps, limits,... can be configured by user with using o

COMET Vision

 software): 

 

Optical signaling (color and status of the LEDs) / Acoustic signaling (number of beeps)

 

battery

 powered 

with 

external

 power 

status information: 

 flashes at 5s interval / without sound 

 lights up permanently / without sound 

up to 1000 ppm 

 

normal

 CO

concentration 

   color change / 2 beeps 

   color change / 2 beeps 

the moment of crossing the preset limit, 

increased CO

2

 

concentration”

 

 flashes at 5s interval / without sound 

 flashes at 2s interval / without sound 

1001  to  1400  ppm 

 

increased 

CO

2

 

concentration, would be advisable to ventilate 

   color change / 3 beeps 

   color change / 3 beeps 

the moment of crossing the preset limit

, „

high 

CO

2

 

concentration”

 

 flashes at 5s interval / without sound 

 flashes at 2s interval / without sound 

1401 and more 

 

high

 CO

2

 concentration, it is 

necessary to ensure a supply of fresh air 

If the battery charge level drops below 20% during device operation, this is indicated by an increase in the number of beeps  by 
an acoustic signal by two

 (ie instead of two standard beeps, beeps 4x, instead of three 5x, etc.) 

and the battery needs to be charged!

 

 

Used battery type: BAT26001S2P Li-ion 2 pack US18650VTC5 5200 mAh SONY (2x 2600mAh) 

The operating time when powering from the battery

 depends on the user's settings of the device and the environment in which it is located 

(frequency of beeping). The theoretical battery life with default device configuration from the manufacturer (permanently on) is 6 months on 
a single battery charge. A longer interval can be achieved with the use of the On/Off timer (time program). The device contains rechargeable 
battery, check the battery status indication and 

recharge it when necessary

It is necessary to prevent the battery from deep discharge, 

otherwise it may become permanently damaged

Recommended power adapter model

: supplied with the device, commonly used chargers with USB Type C connector, e.g. Sunny SYS 1561-105. 

 

SETTING OF THE DEVICE PARAMETERS 

 

 

for the device configuration use computer running Windows 7 or higher, with minimal CPU speeds 1,4 GHz and min. 1 GB RAM memory. 

 

install th

COMET Vision

 software, which is free to download. 

 

connect the device to your computer. Use the USB cable with maximal length of 3m with USB-C terminal.  

 

run the installed softwar

COMET Vision

 and select the device you want to set up from the list of devices. 

 

if the device is connected properly, the home page of the device displays its current status. 

 

to change the device configuration, 

click “Configuration” button

. Then you can modify the device configuration item preset: 

 

configure automatic On/Off Timer 

to automatically switch the device On and Off to save the battery life during periods when there is no 

need to measure, e.g. during the night. You can choose days of the week (e.g. Monday to Friday) and the time (e.g. from 08:00 to 15:00) 
when the device is to be switched On. Outside the specified time interval, it always switches Off automatically. In the period outside the set 

time program, the device can be switched on manually using the ON button - if control by the button is enabled in the device settings. 
By pressing the ON button, the device will be switched on 

and

 

will continue to follow the set time program

 (it will switch off when the 

set switch-off time is reached, it will switch on again at the set switch-on time). 

 

manually switch on the device using the ON button on the device

. If disabled, the device can only be switched on usin

COMET Vision

 software 

or by automatic On/Off Timer. The option is used to prevent undesired manual operation of the device at the installation site. 

 

manually switch off the device by using the OFF button 

on the device. If disabled, the device can only be switched off usin

COMET Vision

 

software or On/Off Timer. The option is used to prevent undesired manual switching off of the device at the installation site. 

Attention, switching 

off using the OFF button will switch Off the device PERMANENTLY, 

regardless of any On/Off Timer setting

.

 

 

CO

2

 concentration limits change for green, orange, and red LEDs. 

 

number of beeps of acoustic signaling when switching from green to orange (standard preset to two). 

 

number of beeps of acoustic signaling when switching from orange to red (standard preset to three). 

 

possibility to set the time interval for periodic repetition of acoustic signaling when orange or red level is active. 

 

time setting 

 for automatic On/Off Timer function, the time in the device needs to be set correctly. 

 

save the new configuration to the device (press Save button), disconnect the device from the computer and close the USB connector with a plug 

 

SAFETY INSTRUCTIONS 

 

 

Installation,  electrical  connection,  and  commissioning  should  be 
performed by qualified personnel only. 

 

The  device  contains  an

  internal  Li-ion  rechargeable  battery

Observe the permitted storage and operating conditions and ensure 

that the device is not exposed to temperatures higher than 60 °

C. If the 

batteries  are  damaged  or  destroyed,  move  it  immediately  from  the 
possible range of fire, high temperature and water to a safe and non-
flammable place. Protect yourself and your surroundings from escaping 
gases or splashes of battery electrolyte.

 

 

Use  the  charger  that  has  been  recommended  to  charge  the  battery. 
During the charging procedure the device must be in an indoor room

 

with 

a relative humidity (RH) up to 85 %. The charging will proceed at an

 

indoor temperature ranging between 0°C and +40°C

 

 

 

Devices  contain  electronic  components;  it  needs  to  liquidate  them 
according to legal requirements. 

 

Do not try to repair the device yourself. Any repairs 

including battery 

exchange

 may be carried out by suitably instructed service personnel 

only. If the device shows signs of unusual behaviour, screw off the rear 
cover  to  disconnect  the  battery  connector.  Avoid  the  disconnected 
battery contacting any metallic parts. Contact the distributor you have 

bought the device from.

 

TECHNICAL SUPPORT AND DEVICE SERVICE 

 

Technical support and service is provided by the distributor of this device. 

The contact is listed in the warranty certificate of the device. If you have 
some  questions  to  your  device,  send  this  question  together  with 
"Diagnostic file" which is to download in Comet Vision software, it contains 
necessary information about the device.

 

Отзывы: