COMEPI COND.01 Скачать руководство пользователя страница 3

 

 Operating instructions – Electromagnetic safety limit switch

 

010 ISTR 06 SC 0418-00

 

 
 

COND.07 

Key inserted and 

recognized, subsequent  

RFID loss 

21.6V < V < 26.4V 

ON 

Red 

Red 

Blinking red 

Close + Open 

Open 

COND.08 

Key inserted and 

recognized 

21.6V < V < 26.4V 

With current: 

I < 50mA 

I >250mA 

ON 

Red 

Blinking red 

Green 

Close + Close 

(BM) 

Open + Open 

(BE) 

Closed 

COND.09 

Key not inserted 

16.8V < V < 21.6V 

26.4V < V > 28V 

ON or OFF 

Blinking red 

Off 

Off 

Open + Open 

Open 

COND.10 

Key inserted and 

recognized

 

16.8V < V < 21.6V 

26.4V < V > 28V 

OFF 

Blinking red

 

Off 

Green 

Open + Open 

Closed 

COND.11 

Key inserted and 

recognized

 

16.8V < V < 21.6V 

26.4V < V > 28V 

 

ON 

Blinking red

 

Red 

Green 

Close + Close 

Closed 

COND.12 

Any 

V < 16.8V 

V > 28V 

On or OFF 

Blinking red

 

Blinking red 

Blinking red 

Close +Close 

(BM) 

Open + Open 

(BE) 

Open 

COND.13 

Key inserted, coupling in 

progress 

21.6V < V < 26.4V 

ON or OFF 

Red

 

Off 

Blinking green 

Open + Open 

Open 

 

Problem Solving 

Condition 

Problem solution – Try with the solutions listed in the order described 

COND.04 

1)

 

Make sure the actuator inserted is the correct one. The actuator-device coupling is univocal 

2)

 

Couple the actuator if not coupled yet 

3)

 

Replace the key and repeat the procedure 

4)

 

Replace the device and/or contact the technical support if the problem persists 

COND.05 
COND.06 

1)

 

Check the actuator is still present, mechanically intact and correctly positioned 

2)

 

Replace the key and couple again 

3)

 

Replace the device and/or contact the technical support if the problem persists 

COND.09 
COND.10 
COND.11 

1)

 

Restore the correct device supply 

2)

 

Replace the device if the problem persists 

COND.08 
COND.12 

1)

 

Restore the correct device supply 

2)

 

Replace the device if the problem persists 

NOTE if the problem is solved after point 1, check the device has not been damaged during the maintenance cycle 

 

Wiring diagram of the device 

 

 

Technical data of the version with 8-pole M12 connector 

Insulation voltage Ui 

30Vcc 

Impulse voltage Uimp 

0.8kV 

Operating current Ue 

Contacts 21-22 and 41-42 

2A (24Vcc) 

Thread 

M12x1 

Tightening torque 

0.6Nm 

Connection diagram of the device – Application example with 
safety module series MS1A31 
 
 
 
 
 
 
 
 

Product working logic 
 
 
 
 
 

 
 

 

 

Wiring diagram of the version 
with M12 connector 