6. Product Troubleshooting 

After power on, the indicator does not light up
No power

Check whether the power supply 

and the route are well connected

Wrong connection of 

power supply

Check whether the positive and 

negative poles of the power supply 

are connected incorrectly

Incorrect power 

supply voltage

Confirm whether the power supply 

voltage is within the normal power 

supply range of the detector, 

the normal power supply of the 

detector is DC10~24V

The access power is 

alternating current 

(AC) instead of direct 

current (DC)

Confirm whether the connected 

power supply is a direct current 

(DC) power supply, if not, please 

replace it

Self-check failed after power-on
Power supply voltage 

is too low

Need to replace the power supply

The buzzer does not sound or the volume is low after 

the alarm
The buzzer is broken 

or there is no power

Confirm whether the red light is on 

when alarming, if it is on, it means 

the detector buzzer is abnormal, 

if the light is off, it means that the 

detector is not powered on

After power-on, the yellow light flashes slowly and the 

buzzer sounds once for 2 seconds
Sensor fault or 

detector is too dirty

First rule out whether the detector 

is oily or the detector sensor is too 

dirty. If the problem persists after 

cleaning, it means the sensor is 

broken

The red light flashes slowly after power on, and the 

buzzer sounds every 10 seconds
Power supply voltage 

is too low

Need to replace the power supply

After a period of time, the red light flashes slowly and 

the buzzer sounds every 10 seconds
Power supply voltage 

is too low

Confirm whether the power supply 

voltage is lower than the detector 

working voltage range, if the power 

supply is normal, it means the 

detector is broken

The buzzer keeps on and the red light flashes quickly
There is a gas leak or 

oily smoke entering 

the detector

Eliminate gas leakage and ensure 

that no oily smoke or other gas 

enters the detector

7. Notice

1. 

Please do not install the detector in places with 

high temperature, high humidity, oily smoke, and 

dust, and keep the air environment around the 

detector clean.

2. 

Avoid installing the detector near a place where 

there are a lot of paint, thinner and other items 

that produce colloidal suspension, so as not to 

affect the normal monitoring of the detector.

3. 

This product is a combustible gas detector. 

When it encounters a combustible gas leak, it 

can give an audible and visual alarm but cannot 

extinguish the fire. We do not accept any legal 

responsibility for the fire and any property loss 

caused by the gas leak.

8. Product Maintenance

1. 

After the detector is installed and used, you 

need to press the detector test button to test the 

detector every month. If a fault is found (such as 

long pressing the test button, the buzzer does 

not sound and the indicator light does not light), 

it should be checked in time.

2. 

After the detector is installed, it should be 

kept properly and corresponding dust-proof, 

moisture-proof and anti-corrosion measures 

should be taken to extend the service life of the 

detector.

3. 

In the event of a detector fault or other 

problems, do not disassemble the detector 

privately for maintenance. Please disconnect the 

power supply and contact your local dealer for 

maintenance.

4. 

When encountering a gas leak detector alarm, 

all power sources should be cut off immediately, 

and the gas source should be turned off to avoid 

accidents such as fire or explosion, and bring 

greater losses to users.