MU 03.20 IT EN rev.2 ed. 12/2016 

Cod. 3810101

 

4 / 4

 

 

 

Label 

Displayed parameter 

Note 

 

Power factor (cos

φ) 

 

Line voltage [V] 

 

RMS current measured by CT [A] 

 

DELTA 

missing reactive power to compensate 
[kvar] 

 

SENS 

sampling time of the measurements 
[s]; values 5 .. 100. It must be SENS < 
A04 

(1) 

SET 

P.F. 

Target power factor (cos

φ); values: 

-0.95 .. -0.99 (CAP), 0.85 .. 1 (IND) 

(1) 

THD I 

Measured THDi % 

 

TEMP 

Measured temperature 

 

 

Note: 
(1) When viewing the parameter you can change the 
value by pressing the buttons 

▲ o ▼.

 

 

Manual operation 

Press the MAN / AUT button until the MAN LED is ON. 
In this mode you can connect or disconnect the banks 
manually. This will only be possible if there are not 
displayed alarms (ALM LED on). Press the SET button 
until you turn off the ALM LED, to reset alarms. 

 

Press the 

▲ or ▼ button to select the bank (indicated by 

the corresponding flashing LED), and then press the 
SET button to confirm the selection. 

 

The manual insertion of batteries imply the switching off 
of the automatic regulation function, however allows the 
display of all the other measurements and alarms. The 
bank status manually changed is stored in a non-volatile 
memory, which allows you to restore the banks even 
after a shutdown and subsequent power. 

 

The  safety  measures  of  the  regulator  in  manual 
mode are disabled. It is recommended to always 
return  the  regulator  to  automatic  mode  after 
programming / maintenance. 

 

Automatic operation 

Press the MAN / AUT button until the LED AUT is ON. In 
this mode the regulator connects and disconnects the 
capacitor banks to keep the cos 

φ as close as possible 

to the programmed target. 

 

Alarms  

HIGH VOLTAGE

: line voltage greater than 110% of the 

programmed value for 15 min; disconnects all the banks. 

LOW VOLTAGE:

 line voltage lower than 85% of the 

programmed value for 5 s. 

HIGH CURRENT

: current greater than 110% of the 

programmed value for 2 min 

LOW CURRENT: 

current lower than

 

5% of the 

programmed value for 5 sec (no banks connection and 
disconnection when the alarm persists for more than 2 
min) 

UNDER COMPENS:

 does not compensate the power 

factor for 15 min 

OVER  COMPENS:

 over-compensation of the power 

factor for 2 min (disconnects the banks to safeguard the 
integrity of the capacitors) 

HIGH THD%:

 the average harmonic distortion 

percentage is higher than the programmed threshold; 
intervention of the alarm relay and disconnection in 
sequence of the banks 

OVER THD%: 

the instantaneous harmonic distortion 

percentage is higher than the programmed threshold; 

intervention of the alarm relay and disconnection in 
sequence of the banks 

OVER TEMP: the 

measured temperature exceeds the 

programmed threshold; instant disconnection in 
sequence of the banks 

 

If one of the alarms is present, the ALM LED flashes, the 
display can show the measure of the parameter showed 
in the NAV lit up segments. For example, for a voltage 
alarm, the V segment of the NAV digit will be turned on. 

 

Technical data 

Envelope in self-extinguishing ABS, 96x96x57mm 
Power supply: 400Vac ±10% 
Line frequency: 50/60 Hz 
Burden: 3VA 
Measuring range of the current input: 2.5 

– 110% 

Display: 4 digit with 7 segments 
LED: Output relays status;    MAN/AUT;   IND / CAP; Alarm 
Number of banks output relays: 4 
Contacts capacity: 5A  250V (AC1), max switching 400V 
Terminals: withdrawable 
Operating temperature: -20°C + 55°C 
Front degree protection:  IP41; with cap (available on request) 
IP54-IP65 

 

Other characteristics: 

Current input on CT standard on / 5 

Setting of the primary coil current from 5A to 10000A 

Measurement of cos 

φ 

Measurement of THD I% of the grid 

Measurement of the internal temperature of the cabinet 

Adjustment of the target power factor from 0.85 Ind to 0.95 
Cap 

Adjustment the power for each bank from 0.1 to 6500 

Adjustment of the reconnection time from 5 to 240s 

Adjustment of the measuring mode with 2 or 4 quadrants 

Adjustment of the banks reconnection time 

Display of line voltage true RMS 

Display of the line current true RMS 

Display of the power in 4-quadrant operation 

Threshold adjustment and alarm monitoring of THD I% 

Threshold  adjustment  and  alarm  monitoring  of  the 
temperature 

 

Warranty 

The product is guaranteed for 12 months from date of delivery. 
The  company  accepts  no  responsibility  for  any  damage  that 
may directly or indirectly result to persons, things, and animals 
from: failure to follow all the instructions given in the operating 
instructions, misuse, incorrect installation. 

 

Reference standards 

European directives: Low Voltage and EMC 
 
Standards: 
EN 61000-6-1 

– EN 61000-6-2 

EN 61000-6-3 

– EN 61000-6-4 

EN 60335-1

 

 

 
 

 

UNI EN ISO 9001:2000 

 

 

UNI EN ISO 14001 

 

OHSAS 18001 

 

Содержание BMR4

Страница 1: ...te SET per modificare i valori premere i pulsanti e I parametri impostabili sono A01 corrente del primario A del trasformatore di corrente TA collegato valori 5 10 000 passi 5 10 50 100 A02 potenza nominale kvar della batteria installata nella posizione indicata dai led 1 4 valori 0 1 6500 passi 0 1 0 5 1 2 5 10 A03 tensione nominale della linea V valori 80 1000 passi 5 A04 tempo minimo di riconne...

Страница 2: ...er 2 min disinserzione delle batterie per salvaguardare l integrità dei condensatori HIGH THD distorsione armonica percentuale superiore al limite di soglia impostato intervento del relè di allarme e disinserimento in sequenza delle batterie inserite OVER THD distorsione armonica percentuale massima istantanea superiore al limite di soglia impostato intervento del relè di allarme e disinserimento ...

Страница 3: ...ress the SET button to change the values press the buttons e The programmable parameters are A01 current of the primary coil A of the connected current transformer CT values 5 10 000 steps 5 10 50 100 A02 rated power kvar of the installed capacitor bank in the position showed by the led 1 4 values 0 1 6500 steps 0 1 0 5 1 2 5 10 A03 rated voltage of the grid V values 80 1000 step 5 A04 minimum re ...

Страница 4: ... the capacitors HIGH THD the average harmonic distortion percentage is higher than the programmed threshold intervention of the alarm relay and disconnection in sequence of the banks OVER THD the instantaneous harmonic distortion percentage is higher than the programmed threshold intervention of the alarm relay and disconnection in sequence of the banks OVER TEMP the measured temperature exceeds t...