(1): 

To  switch  between  AUTOMATIC  and  MANUAL  mode,  press 

the 

MAN/AUT  

button for 5 secs.   

To  switch  ON  or  OFF  a  bank  manually,  press 

MAN/AUT   

for  5 

secs. (the AUT led turns off and the MAN led lights), press 

UP 

or 

DOWN   

to  select  the  capacitors  bank  desired  then  confirm  with 

SETUP 

button. To verify the status of the bank selected, the power 

(in kvar) appears on the display.  

 
In  the  menu  advanced

  (“MAIN  SETUP”)  you  configure  the 

compensation  equipment  parameters  like:  kvar  power  banks, 
capacitors  rating  voltage,  switching  delay,  network  rating 
frequency,  type  of  network  (single  or  3-phase),  alarm  mode 
relays (NC or NO). 
To enter in the MAIN SETUP: 

 

set the regulator on MANUAL mode (you should read the 
PF on the display); 

 

disconnect all the banks, press and hold the 

SETUP 

button 

until  to  read  PAR  SETUP  onto  digital  display:  press  and 
hold again 

SETUP 

until “MAIN SETUP” is displayed. 

 
MAIN SETUP parameters description: 

POWER CAP n°

 =>  reactive power ratio (kvar) of each bank; 

 

to set a bank in 

FIX

 mode 

(always connected)

 set 

the  power  to  “0,0”  and  press 

DOWN

  to  read 

FIX

” on the display. 

CAP VOLTAGE

 =>  voltage ratio (V) of the capacitors banks 

CAP RC TIME

  =>   switch delay time (sec.) 

-----

 

CAUTION ----- 

Contact the capacitors manufacturer before modify this value. 

ALARM  RELAY

 => 

type of output contact relay (NC, NO 

or FAN mode) in alarm condition. 

EXTERNAL TV => 

set the Voltage Transformer (primary 

and secondary value) if used. 

LINE FREQ

  => 

network rating frequency (50 or 60Hz). 

LINE TYPE

  =>   

network system (single or 3-phase). 

SYSTEM MODE

  =>  

mesurement on 2 or 4 quadrants. 

 

 
USER INTERFACE OPERATION 

 
After the setting procedure, the PF (cos

φ

), the voltage and  the 

current  measured  appears  on  the  display:  you  can  read  the 
reactive  power  needed    to  obtain  the  target  cos

φ

  chosen. 

In  AUTOMATIC  mode,  pressing  the 

SETUP

  button  you  can 

navigate between the pages in the sequence below :

 

MAIN 

 THD 

 FAN 

 SET

cos

φ

 

 

POWER 

 MAX(line )

 

 MAX (power) 

 

MAIN =>

  

network parameters measurements including : 
cos

φ

,  true  RMS  voltage,  true  RMS  current, 

Delta Power (means the reactive power gap to 
target the SET cos

φ

)

 

THD =>

 

total  THD%  current  value,  fundamental 
current 

and 

harmonic 

current 

value 

measurement 

FAN =>

 

real  time  temperature  measured  by  the  probe 
(if connected) in °C 

SET cos

φ

 

=>

 

target  P.F.  (cos

φ

):  in  ATUOMATIC  mode 

you can just check it, in MANUAL mode you 
can set the value by 

UP

 and 

DOWN

 buttons 

POWER =>

 

Active and Reactive Power measurments 

MAX(line) =>

  max values of network parameter measured 

(2)

 

MAX(power) =>   

max network energy values measured 

(2)

 

 
Note:if the POWER FACTOR value on the display is not stable, 
reverse the K-L (C.T. signal) connections.

 

 

(2): 

All the history measurements can be reset by pressing the 

UP

 

and 

DOWN

 buttons at same time. 

The display of the parameter is 30sec., after this time the regulator 
come back to the main display page. 

 
During  the  manual  control  of  the  banks,  the  AUTOMATIC 
control  is  inhibited  but  the  others  control  are  operating 
(measurements and alarms). Moreover, if the voltage supply is 
interrupted, the bank status set in MANUAL mode is stored in a 
non-volatile  memory:  when  the  voltage  supply  is  restored,  the 
regulator switches in the memorised banks. 
 
 

ALARMS:

  The  output  relay  <C1>-<C2>  (see  settings  of  the 

ALARM  RELAY  contact),  switches  when  any  of  following 
conditions occur: 
 

HIGH  VOLTAGE

:  the  voltage  measured  to  the  <L2>-<L3>  

terminals  exceeds  the  110%Un  for  15  min.;  the  alarm 
relay operates in the programmed mode. 

  

LOW VOLTAGE

: the voltage supply is less than 85%Un; and 

the alarm relay operates in the programmed mode. 

 

HIGH  CURRENT

:  the  current  measured  from  the  C.T. 

exceeds  the  110%  In.  the  alarm  relay  operates  in  the 
programmed mode. 

 

LOW CURRENT

: the current  measured from the C.T. is less 

than 6%In for 5secs.: if this conditions during more than 
2 min. the regulator switch OFF all the capacitors banks, 
and the alarm relay operates in the programmed mode. 

 

UNDER  COMPENS

:  this  alarm  appears  when  the  PFC 

equipment  does  not  reach  the  target  cos

φ

  for  15min;  

and the alarm relay operates in the programmed mode. 

 

OVER  COMPENS

:  this  alarm  appears  when  the  cos

φ

  is 

Capacitive for 2 min; the regulator switches OFF all the 
capacitors  banks  and  the  alarm  relay  operates  in  the 
programmed mode. 

 

HIGH THD%

: the harmonic distortion value is more than the 

THERM THD% value set on the PAR SETUP menu; the 
regulator switches OFF all the banks and the alarm relay 
operates in the programmed mode. 

 

OVER  THD%

:  the  harmonic  distortion  value  is  over  the 

instantaneous  OVER  THD%  value  set  on  the  PAR 
SETUP  menu;  the  regulator  switches  OFF  all  the  banks 
and the alarm relay operates in the programmed mode. 

 

OVER    TEMPERATURE

:  the  temperature  measured  by  the 

probe  (if  connected)  is  over  the  value  set  in  the  PAR 
SETUP  menu  the  regulator  switches  OFF  all  the  banks 
and the alarm relay operates in the programmed mode. 

 
The  normal  functions  resume  when  the  alarm  condition  ends 
and the alarm relay is reset.

 

 

Содержание BMR Series

Страница 1: ...i assorbimenti previsti Le uscite di comando devono essere opportu namente collegate ai rispettivi organi di intervento protetti a loro volta come tutte le parti di potenza dell impianto I contatti per il comando delle batterie sono NO con comune C interlacciato mentre il contatto di allarme è settabile NO NC FAN indipendente In base al modello sono presenti i morsetti per il collegamento seriale ...

Страница 2: ...la stessa batteria di condensatori ALARM RELAY impostazione funzionamento relè di allarme NOA NCA FAN solo nel caso di impostazione del relè di allarme in modalità FAN è possibile impostare l ultima batteria del dispositivo in modalità ALARM EXTERNAL TV impostazione per la configurazione dell ingres so voltmetrico con trasformatore tensione su linea esterna se presente inserire i valori del primar...

Страница 3: ... misura su 2 o 4 quadranti Impostazione dei valori primario secondario del trasformatore voltmetrico Impostazione soglia di intervento ventilazione FAN Impostazione soglia di sovratemperatura Impostazione del fattore di potenza da 0 85 Ind a 0 95 Cap Impostazione dei kvar per ogni singola batteria da 0 1 a 6000 Impostazione del tempo di riconnessione da 5 a 240s Impostazione della tensione nominal...

Страница 4: ...temperature probe on P1 P2 leads Be sure to know the harmonics characteristic of the network that must be compensated then ensure the P F C equipment or capacitors you are using are suitable for the network characteristics and if necessary to avoid any safety problem on your equipment adjust the THERM THDI and OVER THDI parameters PROGRAMMING The parameters can be set by two menus a base menu PAR ...

Страница 5: ...ER Active and Reactive Power measurments MAX line max values of network parameter measured 2 MAX power max network energy values measured 2 Note if the POWER FACTOR value on the display is not stable reverse the K L C T signal connections 2 All the history measurements can be reset by pressing the UP and DOWN buttons at same time The display of the parameter is 30sec after this time the regulator ...

Страница 6: ...etting o Weekly power factor value medium o Active reactive power measured on 4 qudrants WARRANTY Comar Condensatori s p a guarantees its products for 12 months from purchase date Technical specifications are valid under normal operating conditions as specified in this document We do not accept any responsibility for any misuse of the product and cannot be held liable for indirect or consequential...

Страница 7: ...our le contrôle des alarmes et la commande des ventilateurs pour lesquels il faudra raccorder la sonde de temperature en P1 P2 Il est trés important de connaître les caracteristiques harmoniques du réseau qui doit être compensé pour verifier la compatibilité du système de compensation utilisé PROGRAMMATION les paramètres sont programmables dans 2 menus menu de base PAR SETUP et avancé MAIN SETUP P...

Страница 8: ... POWER MAX line MAX power MAIN paramètre du réseau cosφ valeur RMS de la tension valeur RMS du courant différence de puissance réactive pour obtenir le cosφ choisi THD THD total en courant valeur du courant fondamental et harmonique FAN T mesurée par la sonde en C si reliée SET cosφ Cosinus phi programmée uniquement pour consultation en mode AUTOMATIQUE modifiable en mode MANUEL à l aide des bouto...

Страница 9: ...parente o Puissance active et réactive sur 4 quadrants o Maximum tension et courant mesurée o Facteur de puissance de la semaine o Puissance active réactive mesurè sur le 4 quardants GARANTIE Comar Condensatori s p a garantie ses produits 12 mois à partir de la date d achat Les caractéristiques techniques sont valables pour un usage normal du matériel Nous n acceptons aucune responsabilité en cas ...

Отзывы: