Mains pro 1.6.1 Global Guide
55
12.1.2 Group: V <>, A.V <>
V>, V>>, V<, V<<, A.V>, A.V>>, A.V<, A.V<< [V]
Threshold of 1st and 2nd stage overvoltage, and 1st and 2nd stage undervoltage protection, respectively.
Range
1..999 V
0
= OFF, the appropriate stage of voltage protection is not enabled
Default setting
V>
262 V
V>>
273 V
V<
184 V
V<<
0 V
Note:
Please note, that the indicated setting is adjusted for "Star" connection of the measured voltage, i.e. ph-
to-N voltage measurement. In case of using "Delta" connection, the appropriate change of the setpoints to ph-
ph voltage is necessary.
V> del, V>> del, V< del, V<< del [s]
Delay of the appropriate stage of the voltage protection.
Range
0.00..600.00 s
Default setting
V> Del
1.00 s
V>> Del
0.50 s
V< Del
2.50 s
V<< Del
0.50 s
Avg V> [V]
Limit for
Floating 10 minutes average overvoltage (page 34)
protection.
Range
0..34000 V
0
= OFF, the 10 minutes average overvoltage protection is not enabled
Default setting
0 (OFF)