![ComAp InteliNano NT Plus Скачать руководство пользователя страница 83](http://html.mh-extra.com/html/comap/intelinano-nt-plus/intelinano-nt-plus_reference-manual_2638959083.webp)
InteliNano-NT Plus, SW version 2.0.1.x,
©ComAp – July 2015
83
12.3.5
Inactive confirmed shutdown
O04 Alarm
output is opened. It is possible to start engine when all shutdowns are inactive and
confirmed.
Figure 12.9
INACTIVE CONFIRMED SHUTDOWN
–
E
MERGENCY
S
TOP
12.3.6
Possible shutdown alarms
Emergency Stop
The binary input
Emergency Stop
was activated.
Overspeed
The protection comes active if the speed is greater than 115% of nominal engine
RPM, which is derived from generator frequency.
Underspeed
Low engine RPM. This alarm will be issued when the gen-set is running and then
stops by itself, i.e. the RPM drops under the nominal engine RPM.
The underspeed alarm starts to be evaluated 5 sec after successful gen-set start and
is being evaluated all the time the
Low Oil Pressure
Engine will stop when oil pressure declined to or less than 1 bar or binary input
Low Oil Pressure
is active.
High Coolant temperature
Engine will stop when temperature of coolant exceed
Coolant Temperature Shutdown
threshold.
External Shutdown 1
External Shutdown 2
Содержание InteliNano NT Plus
Страница 36: ...InteliNano NT Plus SW version 2 0 1 x ComAp July 2015 36 Figure 8 1 BINARY OUTPUT SETTING EXAMPLE ...
Страница 45: ...InteliNano NT Plus SW version 2 0 1 x ComAp July 2015 45 Figure 9 1 BINARY INPUT SETTING EXAMPLE ...
Страница 46: ...InteliNano NT Plus SW version 2 0 1 x ComAp July 2015 46 3x 3x Figure 9 2 ANALOG INPUT SETTING EXAMPLE ...
Страница 77: ...InteliNano NT Plus SW version 2 0 1 x ComAp July 2015 77 Figure 12 2 ...