![ComAp InteliNano NT Plus Скачать руководство пользователя страница 40](http://html.mh-extra.com/html/comap/intelinano-nt-plus/intelinano-nt-plus_reference-manual_2638959040.webp)
InteliNano-NT Plus, SW version 2.0.1.x,
©ComAp – July 2015
40
04
Alarm
The output is to be used for external alarm indication. The output is active when at least one
unconfirmed and active alarm is present in the event log.
O05 GCB Close/Open
This output is to be used for a contactor control in case a contactor is used in the GCB position.
GCB position is indicated on the mains screen when feedback is configured.
Wrong breaker / contactor position is indicated on mains screen also.
GCB is opened but has to be close.
GCB is closed but has to be open.
O06 MCB Close/Open
This output is to be used for a contactor control in case a contactor is used in the MCB position.
Output is configured as close-off! When the binary output is inactive (open) the MCB is on-state,
when binary output is active (close) the MCB is open.
Output can also be configured with inverse output logic
– (NC).
O07 Ready To Load
The output is activated when gen-set is running and all electrical values are in limits and no shutdown
alarms are active - it is possible to close GCB or it is already closed. The output opens during cooling
state or when emergency stop or any shutdown is active.
Содержание InteliNano NT Plus
Страница 36: ...InteliNano NT Plus SW version 2 0 1 x ComAp July 2015 36 Figure 8 1 BINARY OUTPUT SETTING EXAMPLE ...
Страница 45: ...InteliNano NT Plus SW version 2 0 1 x ComAp July 2015 45 Figure 9 1 BINARY INPUT SETTING EXAMPLE ...
Страница 46: ...InteliNano NT Plus SW version 2 0 1 x ComAp July 2015 46 3x 3x Figure 9 2 ANALOG INPUT SETTING EXAMPLE ...
Страница 77: ...InteliNano NT Plus SW version 2 0 1 x ComAp July 2015 77 Figure 12 2 ...