3.2.2  Inactive warning  

When a warning becomes inactive, 

O04 Alarm

 and 

O15 Common Warning

 output will open, the red 

LED above 

STOP

 button will stop blinking, and the warning symbol   on main screen will go out. 

 

 

Figure 3.5 

inactive warning 

– Low Battery 

 

3.3 

 Shutdowns  

3.3.1  Shutdown procedure 

The 

InteliNano

NT

 controller opens outputs 

O05 GCB Close/Open

O01 Starter

O08 Prestart

 

and

 

O02 Fuel Solenoid

 

and closes 

O03 Stop Solenoid

 

to stop the engine immediately. 

O04 Alarm

 and 

O16 Common Shutdown

 outputs are closed. Active or not confirmed shutdowns are blocking next 

start of gen-set. 

3.3.2  Active unconfirmed shutdown 

When a shutdown occurs, the 

Shutdown procedure

 will start, the red LED above 

STOP

 button 

blinks, the shutdown symbol   will blink in the upper right corner of LCD, and the proper shutdown 
symbol is displayed in history with running hours stamp. The record in history is inversed, see 

Figure 

3.6

.

 

For shutdown alarm confirmation press

 

STOP

 button. 

 

 

Figure 3.6 

active unconfirmed shutdown 

– Emergency Stop 

 

3.3.3  Active confirmed shutdown 

When an active shutdown is confirmed the red LED above the 

STOP

 button stops blinking. The record 

in history stays inversed with confirmation symbol at the end. 

O04 Alarm

 and 

O16 Common 

Shutdown 

outputs are open. 

 

 

Figure 3.7 

active confirmed shutdown 

– Emergency Stop 

 

3.3.4  Inactive unconfirmed shutdown 

O04 Alarm

 and 

O16 Common Shutdown

o utputs are closed, red LED above 

STOP

 button blinks. 

Shutdown symbol   is displayed in upper-right corner of the LCD, and proper warning symbol is 
displayed in history with running hours stamp. See 

Figure 3.8

.

 

For shutdown alarm confirmation press

 

STOP

 button.

 

 

 

Figure 3.8 

inactive unconfirmed shutdown 

– Emergency Stop 

 

Содержание InteliNano MRS 3

Страница 1: ...istory 7 3 1 Events 8 3 2 Warnings 8 3 3 Shutdowns 9 3 4 ECU Messages 10 4 Start and Stop engine 11 4 1 MANUAL mode 11 4 2 AUTO mode 11 InteliNanoNT MRS 3 Single small gen set controller Single small gen set controller for prime power applications Copyright 2017 ComAp a s ComAp a s U Uranie 1612 14a Prague 7 Czech Republic Tel 420 246 012 111 E mail info comap control com www comap control com ...

Страница 2: ...mode only This button is also used to confirm changes in setup mode 2 Auto AUTO button is dedicated for switching between auto and manual operating mode 3 Stop STOP button Press this button to initiate the stop sequence of the gen set when engine is running in Manual operating mode only This button is also used to cancel changes in setup mode to go back or to exit and for alarm confirmation 4 Up b...

Страница 3: ... engine is running and is loaded or ready to load 7 Operating mode When the green LED is on the controller is in Auto operating mode When is off the controller is in Manual mode 8 Alarm red LED The LED will blink when there is one or more active warning or active shutdown alarm The LED is on when the active shutdown alarm is confirmed and the engine can t be started 9 Graphic B W display 128x64 pi...

Страница 4: ...ic information about voltage and frequency measurement There is also displayed position status of GCB running hours counter and RPM information When any alarm occurs the general alarm symbol will be displayed on the LCD s upper right corner Second screen contains detailed voltage and frequency information Third screen shows the senders information oil pressure coolant temperature fuel level and ba...

Страница 5: ...InteliNanoNT MRS 3 Operator Guide ComAp July 2017 5 2 2 Main screens structure CT connected Figure 2 2 ...

Страница 6: ...l be displayed on the LCD s upper right corner Second screen contains detailed voltage and frequency information Third screen shows measured current for individual phases For each current bar graph is shown Fourth screen shows real and apparent power with power factor for individual phases and totals are also displayed Fifth screen shows senders information oil pressure coolant temperature fuel le...

Страница 7: ...e displayed simultaneously on the LCD screen Total capacity is 15 records The Figure 3 1 is an example of how the history is organized The last screen in this example is showing the four latest events To view further history records you have to wait 3 seconds till down arrow stops blink then press button see Figure 3 2 For alarm shutdown confirmation press STOP button Figure 3 1 ...

Страница 8: ... Power On 3 2 Warnings 3 2 1 Active warning When a warning occurs O04 Alarm and O15 Common Warning outputs will close and the red LED above STOP button will blink Warning symbol will blink in the upper right corner of the LCD and the proper warning symbol will be displayed in the history with running hours stamp Active warning can t be confirmed Figure 3 4 active warning Low Battery ...

Страница 9: ...down symbol will blink in the upper right corner of LCD and the proper shutdown symbol is displayed in history with running hours stamp The record in history is inversed see Figure 3 6 For shutdown alarm confirmation press STOP button Figure 3 6 active unconfirmed shutdown Emergency Stop 3 3 3 Active confirmed shutdown When an active shutdown is confirmed the red LED above the STOP button stops bl...

Страница 10: ...aage ECU Message Diagnostic messages are read and displayed in the history behind the ECU Warning symbol For Standard J1939 SPN Suspect Parameter Number and FMI Failure Mode Identifier are shown Detail SPN FMI code specification see in SAE Truck and Bus Control and Communications Network Standards Manual SAE HS 1939 Publication Or refer to corresponding engine manufacturer s ECU error codes list C...

Страница 11: ...onfigured Press STOP button to stop the engine First press will open the GCB and next press start cooling and stopping procedure When you press this button again the controller will stop the engine immediately For fast engine stop press and hold STOP button till engine stops 4 2 AUTO mode Green LED above AUTO button is on controller is in AUTO mode You can t start the engine or connect the load by...

Отзывы: