command is issued. This makes it easier to bring the gen-sets to the mains-
parallel operation. If MGCB should stay open until all required gen-sets are
synchronized on the generator bus (without load), adjust the setpoint
14.2.1.2
Binary output: MGCB close/open
Related FW
standard v3.1.0
Description
MGCB application only
This output is intended for control of the MGCB if a
contactor
is used as
MGCB. The output provides continuous signal while the MGCB has to be
closed. See timing diagram of all available breaker control outputs in the
description of the
N
OTE
:
Use
invert
function when configuring the output in GenConfig to obtain
inverted function
of the output, i.e. output is closed while the MGCB has to
be open.
There are also other outputs availabe for MGCB control:
14.2.1.3
Binary output: MGCB ON Coil
Related FW
standard v3.1.0
Description
This output is intended for closing of the MGCB using ON coil if a
circuit
breaker
is used as MGCB. The output provides 2 sec pulse when the MGCB
has to close. If synchronizing is disabled with the particular breaker, the pulse
length is extended to 5sec. See timing diagram of all available breaker
control outputs in the description of the
There are also other outputs availabe for MGCB control:
Содержание InteliMains NT IM-NT
Страница 150: ...InteliMains NT SW version 3 2 0 InteliMains NT MCB MGCB 3 2 0 Reference Guide pdf ComAp April 2015 150 APPENDIX...
Страница 435: ...InteliMains NT SW version 3 2 0 InteliMains NT MCB MGCB 3 2 0 Reference Guide pdf ComAp April 2015 435 16 User Notes...
Страница 436: ...InteliMains NT SW version 3 2 0 InteliMains NT MCB MGCB 3 2 0 Reference Guide pdf ComAp April 2015 436...
Страница 437: ...InteliMains NT SW version 3 2 0 InteliMains NT MCB MGCB 3 2 0 Reference Guide pdf ComAp April 2015 437...