![ComAp InteliMains NT IM-NT Скачать руководство пользователя страница 321](http://html1.mh-extra.com/html/comap/intelimains-nt-im-nt/intelimains-nt-im-nt_reference-manual_2638901321.webp)
InteliMains
NT
, SW version 3.2.0
InteliMains-NT-MCB-MGCB-3.2.0-Reference Guide.pdf,
©ComAp – April 2015
321
Description
This value shows the sum of nominal powers of all gensets that are available
for power management (in any state - stopped, running etc.). See also values
and
For more information on power management please refer to the chapter
Power management
.
12.1.7.4
Value: TotRunPnom
Group
Pwr management
Units
kW
Related FW
standard v3.1.0
Description
This value shows the sum of nominal powers of all running gensets that are
participating in power management. See also values
For more information on power management please refer to the chapter
Power management
.
12.1.7.5
Value: Act Reserve
Group
Pwr management
Units
-
Related FW
standard v3.1.0
Description
Actual
absolute reserve
.
12.1.7.6
Value: LoadRes Start
Group
Pwr management
Units
kX
Related FW
standard v3.1.0
Description
If the actual absolute reserve is lower than this value the next gen-set which
is about to be started in
power managament
is started. This value is the
exact copy of setpoint
#LoadResStrt X
.
Содержание InteliMains NT IM-NT
Страница 150: ...InteliMains NT SW version 3 2 0 InteliMains NT MCB MGCB 3 2 0 Reference Guide pdf ComAp April 2015 150 APPENDIX...
Страница 435: ...InteliMains NT SW version 3 2 0 InteliMains NT MCB MGCB 3 2 0 Reference Guide pdf ComAp April 2015 435 16 User Notes...
Страница 436: ...InteliMains NT SW version 3 2 0 InteliMains NT MCB MGCB 3 2 0 Reference Guide pdf ComAp April 2015 436...
Страница 437: ...InteliMains NT SW version 3 2 0 InteliMains NT MCB MGCB 3 2 0 Reference Guide pdf ComAp April 2015 437...