InteliMains
NT
, SW version 3.2.0
InteliMains-NT-MCB-MGCB-3.2.0-Reference Guide.pdf,
©ComAp – April 2015
276
Related FW
standard v3.1.0
Force value
possible
YES
Description
This setpoint is used to adjust the relative frequency level for load shedding
stage 3 (in % of nominal system frequency given by setpoints
and
Nom frq offset
). When the frequency goes below this level for more than
time the next load shedding output is closed.
N
OTE
:
Learn more about load shedding in the separate chapter
Load shedding
.
11.2.13.11
Setpoint: Ld shedDelay1
Group
Load shedding
Range [units]
0.0 .. 600.0 [s]
Related FW
standard v3.1.0
Force value
possible
YES
Description
This setpoint is used to adjust time period for load shedding stage 1, that the
shedding output.
N
OTE
:
Learn more about load shedding in the separate chapter
Load shedding
.
11.2.13.12
Setpoint: Ld shedDelay2
Group
Load shedding
Range [units]
0.0 .. 600.0 [s]
Related FW
standard v3.1.0
Force value
possible
YES
Description
This setpoint is used to adjust time period for the load shedding stage 2, that
the
must be above the
load shedding output.
N
OTE
:
Learn more about load shedding in the separate chapter
Load shedding
.
Содержание InteliMains NT IM-NT
Страница 150: ...InteliMains NT SW version 3 2 0 InteliMains NT MCB MGCB 3 2 0 Reference Guide pdf ComAp April 2015 150 APPENDIX...
Страница 435: ...InteliMains NT SW version 3 2 0 InteliMains NT MCB MGCB 3 2 0 Reference Guide pdf ComAp April 2015 435 16 User Notes...
Страница 436: ...InteliMains NT SW version 3 2 0 InteliMains NT MCB MGCB 3 2 0 Reference Guide pdf ComAp April 2015 436...
Страница 437: ...InteliMains NT SW version 3 2 0 InteliMains NT MCB MGCB 3 2 0 Reference Guide pdf ComAp April 2015 437...