InteliMains
NT
, SW version 3.2.0
InteliMains-NT-MCB-MGCB-3.2.0-Reference Guide.pdf,
©ComAp – April 2015
175
11.2.1.32
Setpoint: MultiSoftStart
Group
ProcessControl
Range [units]
DISABLED, ENABLED [-]
Related FW
standard v3.1.0
Description
This setpoint enables StartUpSynchronization of a group of gen-sets with
closed MGCB prior to getting healthy voltage measurement on the bus.
DISABLED
There is no change in the controller behavior.
ENABLED
The controller will close MGCB in AUT and MAN right
after at least one of gen-set controllers in its control group
closes GCB and indicates StartUpSynchro sequence.
MGCB is not closed if MCB is closed (e.g. due to healthy
Mains)
11.2.1.33
Setpoint: Watched Contr
Group
Process Control
Range [units]
0 .. 16 [min]
Related FW
standard v3.1.0
Description
This setpoint is used at redundant controller to specify the address of the
related main controller in CAN-based rendundant systems. Adjust this
setpoint to 0 if the controller is not used as redundant or if wired rendundancy
system is used.
N
OTE
:
Learn more about redundant systems in the chapter
Redundant controllers
.
11.2.2 Group: Basic settings
11.2.2.1
Setpoint: Vm VT ratio
Group
Basic Settings
Range [units]
0.10 .. 500.00 [V/V]
Содержание InteliMains NT IM-NT
Страница 150: ...InteliMains NT SW version 3 2 0 InteliMains NT MCB MGCB 3 2 0 Reference Guide pdf ComAp April 2015 150 APPENDIX...
Страница 435: ...InteliMains NT SW version 3 2 0 InteliMains NT MCB MGCB 3 2 0 Reference Guide pdf ComAp April 2015 435 16 User Notes...
Страница 436: ...InteliMains NT SW version 3 2 0 InteliMains NT MCB MGCB 3 2 0 Reference Guide pdf ComAp April 2015 436...
Страница 437: ...InteliMains NT SW version 3 2 0 InteliMains NT MCB MGCB 3 2 0 Reference Guide pdf ComAp April 2015 437...