
InteliMains 210 Global Guide
257
Setpoint group
Scheduler
Related FW
2.0.0
Range [units]
Disable / No Func / TEST / Test OnLd / MFail Blk / Mode OFF [-]
Default value
No Func
Alternative config
NO
Step
[-]
Comm object
15359
Related applications
MCB, MGCB, BTB
Description
It is possible to choose from following Timer functions. Binary output
is
always activated when Timer is active regardless of chosen timer function. Timer functions require controller
running in AUTO mode.
IMPORTANT: Binary output is activated always when timer should be activated e.g. even
when controller is in different mode than AUTO.
Timer 1 has the highest priority. Timer 8 has the lowest priority. So if Timer 1 is configured for OFF mode and
Timer 8 is over the same time configured for AUTO mode, controller will work in OFF mode.
Controller activates timer whenever it is powered up even in period, where timer should be already running.
Disable
The Timer is disabled.
No Func
There is no any other function, only binary output of timer is activated.
TEST
When this option is chosen then the binary output of timer is internally connected to the
binary input Remote TEST.
TEST OnLd
When this option is chosen then the binary output of timer is internally connected to the
Remote TEST On Load binary input.
MFail Blk
When this option is chosen then the binary output of timer is internally connected to the
Mains Fail Block binary input.
Mode OFF
When this option is chosen then the binary output of timer is internally connected to the
Remote OFF binary input.
Timer 2 Function
Setpoint group
Scheduler
Related FW
2.0.0
Range [units]
Off / Once / Repeated [-]
Default value
Off
Alternative config
NO
Step
[-]
Comm object
0
Related applications
MCB, MGCB, BTB
Description
Defines repetition of
.
Off
will not be activated.
Once
will be activated only one time.
Repeated
will be repeatedly activated.
Timer 2 Repetition
Содержание InteliMains 210 BTB
Страница 169: ...PLC Setpoint 61 360 PLC Setpoint 62 361 PLC Setpoint 63 362 PLC Setpoint 64 363 InteliMains 210 Global Guide 169 ...
Страница 366: ...Log Bout 6 385 Log Bout 7 386 Date Time Time 394 Date 394 InteliMains 210 Global Guide 366 ...
Страница 494: ...InteliMains 210 Global Guide 494 Image 8 144 Configuration of OR AND block 6 back to List of PLC blocks ...