InteliMains 210 Global Guide
199
Subgroup: Over Load Next Start Protection
Setpoint group
Power Management
Related FW
2.0.0
Range [units]
Enabled / Disabled [-]
Default value
Enabled
Alternative config
NO
Step
[-]
Comm object
14942
Related applications
MCB, MGCB
Description
This setpoint is intended for activation of the protection against the overloading of the system due to rapid
change of the load. It makes the next gen-set (in priority order) to start when the load excises the value given
by the setpoint
#Overload Next Start Level (page 199)
right after the delay
#Overload Next Start Delay (page
.
#Overload Next Start Protection
Setpoint group
Power Management
Related FW
2.0.0
Range [units]
0 .. 100 [%]
Default value
80 %
Alternative config
NO
Step
1 %
Comm object
14941
Related applications
MCB, MGCB
Description
Threshold level for
#Overload Next Start Protection (page 199)
#Overload Next Start Level
Setpoint group
Power Management
Related FW
2.0.0
Range [units]
0 .. 5 [s]
Default value
1 s
Alternative config
NO
Step
1 s
Comm object
8493
Related applications
MINT
Description
Delay for
#Overload Next Start Protection (page 199)
.
#Overload Next Start Delay