InteliMains 210 Global Guide
180
Subgroup: Phase rotation
Setpoint group
Basic settings
Related FW
2.0.0
Range [units]
Clockwise / CounterCCW [-]
Default value
Clockwise
Alternative config
NO
Step
[-]
Comm object
15122
Related applications
MCB, MGCB, BTB
Description
This setpoint adjust the phase sequence of voltage terminals.
Phase Rotation
Subgroup: Battery Protections
Setpoint group
Engine settings
Related FW
2.0.0
Range [units]
8,0 V ..
Battery Overvoltage (page 180)
[V]
Default value
18,0 V
Alternative config
NO
Step
0,1 V
Comm object
8387
Related applications
MCB, MGCB, BTB
Description
Warning threshold for low battery voltage.
Battery Undervoltage
Setpoint group
Engine settings
Related FW
2.0.0
Range [units]
Battery Undervoltage (page 180)
.. 40,0 [V]
Default value
36,0 V
Alternative config
NO
Step
0,1 V
Comm object
9587
Related applications
MCB, MGCB, BTB
Description
Warning threshold for high battery voltage.
Battery Overvoltage