InteliLite Global Guide
60
Note:
This button will not change the mode if the controller mode is forced by
one of binary inputs listed in the Reference Guide – “Operating modes” chapter.
HORN RESET
button. Use this button to deactivate the horn output without
acknowledging the alarms.
FAULT RESET
button. Use this button to acknowledge alarms and deactivate the
horn output. Inactive alarms will disappear immediately and status of active alarms
will be changed to "confirmed" so they will disappear as soon as their reasons
dismiss.
UP
button. Use this button to move up or increase value.
PAGE
button. Use this button to switch over display pages.
DOWN
button. Use this button to move down or decrease value.
ENTER
button. Use this button to finish editing a setpoint or moving right in the
history page.
START
button. Works in MAN mode only. Press this button to initiate the start
sequence of the engine.
STOP
button. Works in MAN mode only. Press this button to initiate the stop
sequence of the gen-set. Repeated pressing of button will cancel current phase of
stop sequence (like cooling) and next phase will continue.
GCB
button. Works in MAN and TEST modes only. Press this button to open or
close the GCB.
Indicators and others
Position
Description
GENERATOR
status indicator. There are two states - Gen-set OK (indicator is green) and Gen-
set failure (indicator is red). Green LED is on if the generator voltage is present and within limits.
Red LED starts flashing when gen-set failure occurs. After FAULT RESET button is pressed,
goes to steady light (if an alarm is still active) or is off (if no alarm is active).
GCB ON
. Green LEDs are on if GCB is closed and Gen-set is healthy. If Gen-set is not healthy
and GCB is closed than middle LED is on. It is driven by GCB CLOSE/OPEN output or by GCB
feedback signal.
LOAD
. Green LED is ON if load is supplied by generator. It means, that Gen-set is OK and
circuit breaker is closed.
Graphic B/W display, 132x64 pixels.
5.3.2 Display screens and pages structure
The displayed information is structured into "pages" and "screens". Use PAGE button to switch over the pages.
Содержание InteliLite AMF25
Страница 34: ...InteliLite Global Guide 34 ConnectionType SplPhL1L2 Image 4 11 Split phase L1L2 application ...
Страница 36: ...InteliLite Global Guide 36 Image 4 14 Typical Split Phase generator wiring ...
Страница 91: ...InteliLite Global Guide 91 Image 5 13 Flowchart of start of diesel engine ...
Страница 93: ...InteliLite Global Guide 93 Image 5 14 Flowchart of start of gas engine ...
Страница 199: ...InteliLite Global Guide 199 nominal speed Image 8 3 Idle Time 1 Image 8 4 Idle Time 2 6 back to List of setpoints ...
Страница 638: ...InteliLite Global Guide 638 Image 9 1 Configuration of OR AND block 6 back to List of PLC blocks ...
Страница 708: ...InteliLite Global Guide 708 Image 9 30 Inteli AIN8 Image 9 31 Inteli AIN8 dimensions Note All dimensions are in mm ...
Страница 714: ...InteliLite Global Guide 714 Image 9 32 Inteli IO8 8 Image 9 33 Inteli IO8 8 dimensions Note All dimensions are in mm ...
Страница 721: ...InteliLite Global Guide 721 Image 9 34 IGS PTM Image 9 35 IGS PTM dimensions ...
Страница 727: ...InteliLite Global Guide 727 Image 9 36 Inteli AIN8TC Image 9 37 Inteli AIN8TC dimensions ...
Страница 731: ...InteliLite Global Guide 731 Image 9 38 Inteli AIO9 1 Image 9 39 Inteli AIO9 1 dimensions ...