InteliLite Global Guide
529
Related FW
1.9.0
Related applications
AMF, MRS
Comm object
626
Description
Binary input for
protection.
Monitoring
Binary input is not used for protection or any other function. Signal is only
monitored.
HistRecOnl
Binary input is not used for protection. Only history record is made if binary input is
active.
Wrn
Binary input is used for warning protection only.
BOC
Binary input is used for BOC (Breaker Open and Cooling) protection.
Sd
Binary input is used for shutdown protection.
Protection types
Fuel Level
back to Logical binary inputs alphabetically
Related FW
1.9.0
Related applications
AMF, MRS
Comm object
694
Description
This binary input is used for manual control of binary output
. The output is
deactivated automatically as soon as fuel level reaches 100%.
Note:
This binary input is basically designed for ON and OFF switch (switch with arrestment in these
positions) because controller reacts to rising and falling edge of signal in this input.
IMPORTANT: When binary input
is configured then binary
output
is control by this binary input. Setpoints
and
are not evaluated!
IMPORTANT: It is necessary to configure analog input
for proper
function of this binary input.
Fuel Pump On/Off
back to Logical binary inputs alphabetically
LBI: G
Related FW
1.9.0
Related applications
AMF, MRS
Comm object
193
Description
Binary input has the same function as GCB button
on the InteliLite front panel. It is evaluated in MAN
mode only.
GCB Button
Содержание InteliLite AMF25
Страница 34: ...InteliLite Global Guide 34 ConnectionType SplPhL1L2 Image 4 11 Split phase L1L2 application ...
Страница 36: ...InteliLite Global Guide 36 Image 4 14 Typical Split Phase generator wiring ...
Страница 91: ...InteliLite Global Guide 91 Image 5 13 Flowchart of start of diesel engine ...
Страница 93: ...InteliLite Global Guide 93 Image 5 14 Flowchart of start of gas engine ...
Страница 199: ...InteliLite Global Guide 199 nominal speed Image 8 3 Idle Time 1 Image 8 4 Idle Time 2 6 back to List of setpoints ...
Страница 638: ...InteliLite Global Guide 638 Image 9 1 Configuration of OR AND block 6 back to List of PLC blocks ...
Страница 708: ...InteliLite Global Guide 708 Image 9 30 Inteli AIN8 Image 9 31 Inteli AIN8 dimensions Note All dimensions are in mm ...
Страница 714: ...InteliLite Global Guide 714 Image 9 32 Inteli IO8 8 Image 9 33 Inteli IO8 8 dimensions Note All dimensions are in mm ...
Страница 721: ...InteliLite Global Guide 721 Image 9 34 IGS PTM Image 9 35 IGS PTM dimensions ...
Страница 727: ...InteliLite Global Guide 727 Image 9 36 Inteli AIN8TC Image 9 37 Inteli AIN8TC dimensions ...
Страница 731: ...InteliLite Global Guide 731 Image 9 38 Inteli AIO9 1 Image 9 39 Inteli AIO9 1 dimensions ...