background image

InteliLite Global Guide

458

Value group

Engine

Related FW

1.9.0

Units

RPM

Comm object

10123

Related applications

AMF, MRS

Description

This value contains the current engine speed. The value is obtained from one of the following sources:

ECU, if an ECU is configured

Pickup input

Generator frequency

RPM

6

back to List of values

Value group

Engine

Related FW

1.9.0

Units

%

Comm object

10137

Related applications

AMF, MRS

Description

Engine speed control via CAN bus.

Speed request

Requested speed

Accelerator pedal position

0%

1350 RPM

0%

50%

1500 RPM

50%

100%

1650 RPM

100%

Speed Request

6

back to List of values

Value group

Engine

Related FW

1.9.0

Units

RPM

Comm object

10006

Related applications

AMF, MRS

Description

Requested engine speed.

Speed Required RPM

6

back to List of values

Group: Generator

Value group

Generator

Related FW

1.9.0

Units

Hz

Comm object

8210

Related applications

AMF, MRS

Description

Frequency of generator.

Generator Frequency

6

back to List of values

Содержание InteliLite AMF25

Страница 1: ...420 246 012 111 E mail info comap control com www comap control com Global Guide InteliLite MRS16 Controller for single gen set applications SW version 1 9 0 1 Document information 6 2 System overview 11 3 Applications overview 20 4 Installation and wiring 21 5 Controller setup 51 6 Communication 138 7 Technical data 165 8 Appendix 167 ...

Страница 2: ...ual 10 2 System overview 11 2 1 General description 11 2 1 1 The key features of InteliLite 11 2 2 True RMS measurement 11 2 3 Configurability and monitoring 11 2 3 1 Supported configuration and monitoring tools 12 2 3 2 Configuration parts 12 2 4 PC Tools 13 2 4 1 InteliConfig 13 2 4 2 WebSupervisor 13 2 4 3 WinScope 14 2 5 Plug in Modules 14 2 5 1 CM Ethernet 14 2 5 2 CM 4G GPS 15 2 5 3 CM GPRS ...

Страница 3: ...9 4 4 8 Emergency stop 40 4 4 9 Analog inputs 40 4 4 10 CAN bus and RS485 wiring 44 4 4 11 USB 47 4 4 12 Example of MRS Wiring 47 4 4 13 Analog as binary or tristate inputs 48 4 5 Plug in module installation 48 4 5 1 Installation 48 4 6 Maintenance 50 4 6 1 Backup battery replacement 50 5 Controller setup 51 5 1 Default configuration 51 5 1 1 Binary inputs 51 5 1 2 Binary outputs 51 5 1 3 Analog i...

Страница 4: ...p sequence 87 5 5 2 Operating Modes 89 5 5 3 Engine start 90 5 5 4 Stabilization 94 5 5 5 Connecting to load 94 5 5 6 MRS operation 94 5 5 7 Dual Operation 95 5 5 8 Engine cool down and stop 97 5 5 9 Alarm management 97 5 5 10 History log 103 5 5 11 Breaker control 104 5 5 12 Exercise timers 107 5 5 13 Rental Timers 114 5 5 14 Service timers 115 5 5 15 Analog switches 115 5 5 16 Additional running...

Страница 5: ... 2 2 MODBUS RTU MODBUS TCP 153 7 Technical data 165 8 Appendix 167 8 1 Controller objects 168 8 1 1 Setpoints 169 8 1 2 Values 451 8 1 3 Logical binary inputs 497 8 1 4 Logical binary outputs 538 8 1 5 Logical analog inputs 602 8 1 6 PLC 634 8 2 Alarms 647 8 2 1 Alarms level 1 647 8 2 2 Alarms level 2 671 8 2 3 Fail sensor and other types 689 8 3 Modules 691 8 3 1 Plug In modules 692 8 3 2 CAN mod...

Страница 6: ...rs This manual provides general information how to install and operate InteliLite controllers This manual is dedicated for Operators of gen sets Gen set control panel builders For everybody who is concerned with installation operation and maintenance of the gen set 1 3 Legal notice This End User s Guide Manual as part of the Documentation is an inseparable part of ComAp s Product and may be used e...

Страница 7: ... reduce the risk of damage ComAp does not take any responsibility for the actions of persons responsible for cyber attacks nor for any damage caused by the cyber attack However ComAp is prepared to provide technical support to resolve problems arising from such actions including but not limited to restoring settings prior to the cyber attacks backing up data recommending other preventive measures ...

Страница 8: ...ystem cannot be effected To be sure Disconnect remote control Disconnect binary outputs 1 4 2 SW and HW versions compatibility Be aware to use proper combination of SW and HW versions 1 4 3 Dangerous voltage In no case touch the terminals for voltage and current measurement Always connect grounding terminals In any case do not disconnect controller CT terminals 1 4 4 Adjust the setpoints All param...

Страница 9: ... 1 EN 60068 2 1 20 C 16 h for std 40 C 16 h for LT version EN 60068 2 2 70 C 16 h EN 60068 2 6 2 25 Hz 1 6 mm 25 100 Hz 4 0 g EN 60068 2 27 a 500 m s2 T 6 ms EN 60068 2 30 2005 25 55 C RH 95 48hours EN 60529 front panel IP65 back side IP20 1 6 Document history Revision number Related sw version Date Author 11 1 9 0 23 9 2019 Michal Slavata 10 1 8 0 21 5 2019 Michal Slavata 9 1 7 0 22 8 2018 Michal...

Страница 10: ...t measuring Diode Ethernet male Ethernet female Fuel solenoid Fuse Fuse switch Generator Generator schematic Grounding GSM GSM modem IG AVRi IG AVRi TRANS Jumper Load Mains Mains Mobile provider Passive current sensor Pick up Relay coil Relay coil of slow operating Resistor Resistor adjustable Resistive sensor RPTC RS 232 male RS 232 female Starter Switch manually operated Transformer USB type B m...

Страница 11: ...ns Various customizations are possible thanks to its configurability Excellent remote communication capabilities High level of support for EFI engines most world producers High reliability 2 2 True RMS measurement This controller measures AC values based on True RMS principle This principle corresponds exactly to the physical definition of alternating voltage effective values Under normal circumst...

Страница 12: ...ctions are required at the same time on the same gen set and also the controller hardware does not have so many input and output terminals One of the main tasks of the configuration is mapping of logical firmware inputs and outputs to the physical hardware inputs and outputs 2 3 2 Configuration parts Mapping of logical binary inputs functions or assigning alarms to physical binary input terminals ...

Страница 13: ...llers i e preparing controllers with identical configuration and settings 2 4 PC Tools 2 4 1 InteliConfig Configuration and monitoring tool for InteliLite controllers See more in InteliConfig Reference Guide This tool provides the following functions Direct or internet communication with the controller Offline or online controller configuration Controller firmware upgrade Reading writing adjustmen...

Страница 14: ...ds in controller On line change of controllers parameters for easy regulator setup 2 5 Plug in Modules 2 5 1 CM Ethernet Internet Ethernet module including web server 10 100 Mbit ethernet interface in RJ45 socket Web interface for monitoring and adjustment of the controller Direct IP and or AirGate connection for remote access from InteliConfig MODBUS TCP and SNMP protocols for integration of the ...

Страница 15: ...rsity WCDMA HSDPA HSUPA HSPA Band 1 Band 2 Band 5 Band 8 all bands with diversity GPRS multi slot class 10 TCP IP communication over GPRS 2 5 3 CM GPRS GSM GPRS Internet module Wireless integrated solution Quick and easy installation Support of WebSupervisor Instant alarm SMS notification System control over SMS Quad Band GPRS EDGE modem 850 900 1800 1900 MHz GPRS multi slot class 10 TCP IP commun...

Страница 16: ...figure the unit to have 8 binary inputs 8 binary outputs and 2 analog outputs or 16 binary inputs 0 binary outputs and 2 analog outputs via switches inside the controller Configuration 8 8 8 Binary inputs options pull up or pull down logic 8 Binary outputs options Low side switch LSS or High side switch HSS 2 Analog outputs options voltage 0 10V current 0 20mA and PWM 5V adjustable frequency 200Hz...

Страница 17: ...0Ω 0 2400Ω 0 10kΩ Temperature sensor Pt100 Pt1000 Ni100 Ni1000 Current active or passive sensors 20mA 0 20mA 4 20mA Voltage 1V 0 2 4V 0 5V 0 10V Lambda probes Thermocouples are not supported the measuring loop was designed for lambda probes what caused non support of thermocouples 2 6 3 Inteli AIN8TC 8 Analog Channels Module 8 analog input channels for measuring temperature by thermocouples ...

Страница 18: ... output 2 6 5 IGS PTM The unit offers the user the flexibility to configure the unit to have 8 binary inputs 8 binary outputs 4 analog inputs and 1 analog outputs Configurable 8 binary and 4 analog inputs Configurable 8 binary and 1 analog output LEDs indicate the state of binary inputs outputs Measures values from Pt100 and Ni100 sensors Analog inputs resistance range 0 250 Ohms voltage range 0 1...

Страница 19: ... programmable LEDs with configurable colors red green yellow Lamp test function with status LED Customizable labels Local horn output Maximal distance 200 m from the controller Up to 4 units can be connected to the controller UL certified 6 back to System overview ...

Страница 20: ...MRS Manual Remote Start The typical scheme of Manual Remote Start application is shown below The controller controls one breaker a generator breaker Feedback from breaker isn t necessary InteliLite controllers can also work without breaker feedback Image 3 1 MRS application overview 6 back to Applications overview ...

Страница 21: ...ng 24 4 5 Plug in module installation 48 4 6 Maintenance 50 6 back to Table of contents 4 1 Package content The package contains Controller Mounting holders Terminal blocks Note The package does not contain a communication or extension modules The required modules should be ordered separately 4 2 Controller installation 4 2 1 Dimensions Plug in module ...

Страница 22: ...ions of InteliLite 4 2 2 Mounting The controller is to be mounted onto the switchboard door Requested cutout size is 187 x 132 mm Use the screw holders delivered with the controller to fix the controller into the door as described on pictures below Recommended torque for holders is 0 15 N m Panel door mounting Note Enclosure Type rating with mounting instruction For use on a Flat surface of a type...

Страница 23: ...1 T44 BIN2 T30 L2 T37 L2 T45 BIN3 T31 L3 T38 L3 T46 BIN4 T47 BIN5 T48 BIN6 T49 BIN7 Image 4 1 Terminal diagram for InteliLite MRS16 CAN1 ANALOG INPUTS BINARY OUTPUTS POWER SUPPLY D T25 L T15 RPM GND T04 BOUT1 T01 BATT T26 COM T16 RPM IN T05 BOUT2 T02 D T27 H T17 A COM T06 BOUT3 T03 BATT T18 A01 T07 BOUT4 T19 A02 T08 BOUT5 T20 A03 T09 BOUT6 T21 A04 T10 BOUT7 ...

Страница 24: ...ng page 30 Binary inputs 43 49 Binary inputs page 38 CAN bus and RS485 H COM L CAN bus and RS485 wiring page 44 Analog inputs 15 21 Analog inputs page 40 Binary outputs 04 10 Binary Outputs page 39 Power supply D Power supply page 25 USB USB page 47 Note Wiring terminal markings to included tightening torque 0 5 N m 4 5 lb in and wire size 2 mm2 12 26AWG ...

Страница 25: ...tening torque 0 79 nm 7 0 In lb Use only diameter 2 0 0 5 mm 12 26 AWG conductor rated for 75 C minimum use copper conductors only 4 4 2 Grounding The shortest possible length of wire should be used for controller grounding Use cable min 2 5 mm2 The negative battery terminal must be properly grounded Switchboard and engine must be grounded at common point Use as short cable as possible to the grou...

Страница 26: ...be temporarily switched off and after recovering to 4 V back on IMPORTANT When the controller is power up only by USB and the USB is disconnected then the actual statistics can be lost Note Suitable conductor protection shall be provided in accordance with NFPA 70 Article 240 Note Low voltage circuits 35 volts or less shall be supplied from the engine starting battery or an isolated secondary circ...

Страница 27: ...e 176 PT Ratio page 180 and CT Ratio page 177 by appropriate setpoints in the Basic Settings group IMPORTANT Risk of personal injury due to electric shock when manipulating voltage terminals under voltage Be sure the terminals are not under voltage before touching them Do not open the secondary circuit of current transformers when the primary circuit is closed Open the primary circuit first Curren...

Страница 28: ... ensure that potential difference between current COM terminal and power supply terminal is maximally 2 V There are 2 options how to ensure this Red option properly ground both terminals Blue option interconnect these two terminals Always apply only one option Never realize both options on one installation ...

Страница 29: ... is normally connected the third phase IMPORTANT It is necessary to ensure that potential difference between current COM terminal and power supply terminal is maximally 2 V There are 2 options how to ensure this Red option properly ground both terminals Blue option interconnect these two terminals Always apply only one option Never realize both options on one installation ...

Страница 30: ... these two terminals Always apply only one option Never realize both options on one installation Voltage measurement MRS wiring There are 4 voltage measurement Connection Type setpoint Connection type page 177 3Ph4Wire 3Ph3Wire Split Ph Mono Ph options every type matches to corresponding generator connection type Note For fusing of voltage measurement input use T1A or T2A fuse The generator protec...

Страница 31: ...InteliLite Global Guide 31 ConnectionType 3 Phase 4 Wires Image 4 5 3 phase application with neutral Image 4 6 Typical 3 Phase 4 Wires generator wiring ...

Страница 32: ...InteliLite Global Guide 32 ConnectionType High Leg D Image 4 7 High Leg Delta application Image 4 8 Typical High Leg D generator wiring ...

Страница 33: ...InteliLite Global Guide 33 ConnectionType 3 Phase 3 Wires Image 4 9 3 phase application without neutral Image 4 10 Typical 3 Phase 3 Wires generator wiring ...

Страница 34: ...InteliLite Global Guide 34 ConnectionType SplPhL1L2 Image 4 11 Split phase L1L2 application ...

Страница 35: ...e 4 12 Typical Split Phase generator wiring ConnectionType SplPhL1L3 Image 4 13 Split phase L1L3 application IMPORTANT The second phase of split phase connection is connected to the terminal where is usually connected the third phase ...

Страница 36: ...InteliLite Global Guide 36 Image 4 14 Typical Split Phase generator wiring ...

Страница 37: ...mon method of engine speed measurement To use this method mount the pickup opposite to the engine flywheel connect the cable to the controller as shown on the picture below and adjust the setpoint Gear Teeth page 181 according to the number of teeth on the flywheel For the details about the pick up input parameters see Technical data on page 165 IMPORTANT To ensure proper function use a shielded c...

Страница 38: ...g RPM is measured from the generator voltage Gear Teeth 0 Controller is measuring some voltage value on input terminals due to open fusing If RPM 0 the controller will be put into a Not ready state and the engine will not be allowed to start 4 4 6 Binary inputs Use minimally 1 mm2 cables for wiring of Binary inputs Image 4 17 Wiring binary inputs Note The name and function or alarm type for each b...

Страница 39: ...IMPORTANT Use suppression diodes on all relays and other inductive loads Note Every single low current binary output can provide up to 0 5 A of steady current Note Binary output 1 terminal 4 and binary output 2 terminal 5 are high current outputs 5 A for long term IMPORTANT When operating temperature is higher than 60 C it is strongly recommended to limit output current of high current binary outp...

Страница 40: ...cy stop IMPORTANT Suppression diodes are not indicated but required 4 4 9 Analog inputs The analog inputs are designed for resistive automotive type sensors like VDO or DATCON The sensors are connected either by one wire the second pole is the sensor body or by two wires In the case of grounded sensors connect the AI COM terminal to the engine body as near to the sensors as possible In the case of...

Страница 41: ...on overview not actual wiring Note The name sensor characteristic and alarm types for each analog input have to be assigned during configuration Analog inputs with voltage current sensors On each analog input there is a possibility to connect voltage or current output sensor instead of resistive one Recommended wiring connection for these measurements and recommended curves are bellow Voltage sens...

Страница 42: ... 465 V 16 18 20 22 24 26 28 30 Ω 543 633 735 853 993 1154 1350 1589 0 70 V V 0 2 4 6 8 10 12 14 16 18 20 22 Ω 99 117 137 155 175 196 219 242 266 291 318 346 V 24 26 28 30 32 34 36 38 40 42 44 46 Ω 375 406 439 473 510 549 589 633 679 729 781 838 V 48 50 52 54 56 58 60 62 64 66 68 70 Ω 873 963 1033 1110 1193 1283 1383 1492 1612 1748 1896 2065 Tables for HW versions 1 2 and higher 0 10 V V 0 1 2 3 4 ...

Страница 43: ... 38 40 42 44 46 Ω 179 188 198 208 219 231 243 256 269 284 300 316 V 48 50 52 54 56 58 60 62 64 66 68 70 Ω 334 354 375 398 422 449 479 511 547 587 631 681 Note This is a conversion of voltage from voltage sensor to appropriate resistance value Use resistance values in InteliConfig to create your specific curve These values should be used in Ohm column Current sensors Sensor s output range mA R Ω 0 ...

Страница 44: ...s on the communication speed For a speed of 250 kbps which is used on the CAN1 bus extension modules ECU the maximum length is 200 m The bus must be wired in linear form with termination resistors at both ends No nodes are allowed except on the controller terminals Shielded cable1 has to be used shielding has to be connected to the terminal T01 Grounding External units can be connected on the CAN ...

Страница 45: ... CAN bus wiring for shorter distances Note Shielding shall be grounded at one end only Shielding shall not be connected to CAN COM terminal For longer distances or in case of surge hazard connection out of building in case of storm etc Image 4 25 CAN bus wiring for longer distances Recommended PT5 HF 12DC ST1 1Protections recommended Phoenix Contact http www phoenixcontact com PT 5 HF 12DC ST with...

Страница 46: ...d by 120 Ohm resistors at both ends For shorter distances connection within one building Image 4 26 RS485 wiring for shorter distances For longer distances or in case of surge hazard connection out of building in case of storm etc Image 4 27 RS485 wiring for longer distances Recommended PT5HF 5DC ST2 Note Communication circuits shall be connected to communication circuits of Listed equipment 1Reco...

Страница 47: ...e Image 4 28 USB connection Controller can by also power by USB only for service purpose like a uploading firmware change of configuration etc IMPORTANT Power supply by USB is only for service purpose Binary inputs and outputs are in logical 0 Also plug in modules are not working 4 4 12 Example of MRS Wiring ...

Страница 48: ...es over 2400 Ω are evaluated as sensor failure short or open circuit Image 4 29 Analog inputs as tristate Image 4 30 Analog inputs as binary Note The name sensor characteristic and alarm types for each analog input have to be assigned during configuration Note Tristate and binary sensors are not suitable for Analog Switch functions 4 5 Plug in module installation 4 5 1 Installation Remove the back...

Страница 49: ... navigation After inserting plug in module under holders 1 press it down to holders marked by symbol 2 which locks the module Insert the plug in module under holders marked by symbol 1 After locking the plug in module into holders place back the back cover small cover for connectors has to be removed from back cover Finally insert the small cover for connectors Small covers are unique for each plu...

Страница 50: ...hboard Remove the back cover and all plug in modules Release the rear cover using a flat screwdriver or another suitable tool The battery is located in a holder on the circuit board Remove the old battery with a small sharp screwdriver and push with a finger the new battery into the holder Put the rear cover back Use slight pressure to lock the snaps into the housing Pay attention that the cover i...

Страница 51: ...ssion of alarms SD OVERRIDE PAGE 537 BIN6 Control lock keyswitch REMOTE CTRL LOCK PAGE 535 BIN7 Free slot NOT USED PAGE 533 5 1 2 Binary outputs Number Description Function BOUT1 Starter motor control STARTER PAGE 597 BOUT2 Fuel solenoid valve FUEL SOLENOID PAGE 572 BOUT3 Indication of breaker state GCB CLOSE OPEN PAGE 574 BOUT4 Activation of any devices before start PRESTART PAGE 585 BOUT5 Gen se...

Страница 52: ...ction of various PC tools to the controller If you require detailed information on each PC tool please use the included Help in those PC tools or download their Reference Guides 5 2 1 USB You may connect to the controller using the USB port In this case standard USB A to B cable should be used Connection using InteliConfig Image 5 1 First screen of InteliConfig select connect to controller Image 5...

Страница 53: ...t to the controller using RS232 or RS485 direct connection serial port or USB to RS232 RS485 converter may be used The following settings need to be checked in the controller COM1 Mode page 343 Direct has to be set to the same value as in the PC tool Connection using InteliConfig Image 5 4 First screen of InteliConfig select connect to controller ...

Страница 54: ...7600 speeds 5 2 3 Ethernet It is possible to connect to the controller using ethernet port either directly or using ComAp s AirGate service Direct connection When you use direct connection the controller needs to be reachable directly from the PC you use i e one LAN or WAN without any firewalls and other points that may not allow the connection The following settings need to be checked in the cont...

Страница 55: ...ess page 378 is either set automatically or it can be adjusted to a specific requested value Subnet Mask page 379 is either set automatically or it can be adjusted to a specific requested Gateway IP page 379 can be set here when it is used ComAp TCP Port page 384 number is 23 Make sure that this port is open for communication in your network Connection using InteliConfig Image 5 7 First screen of ...

Страница 56: ...ope Image 5 9 WinScope screen AirGate connection You can use ComAp s AirGate service that allows you to connect to any controller via internet no matter what are the restrictions of the local network if the controller can connect to the internet AirGate service will work The following setpoints have to be adjusted ...

Страница 57: ...y or it can be adjusted to a specific requested value Subnet Mask page 379 is either set automatically or it can be adjusted to a specific requested Gateway IP page 379 can be set here when it is used AirGate Connection page 383 has to be set to Enabled AirGate Address page 384 currently there is one AirGate server running at URL airgate comap cz enter this URL into the setpoint Connection using I...

Страница 58: ...InteliLite Global Guide 58 Image 5 11 Second screen of InteliConfig select AirGate Connection using WinScope WinScope doesn t support connection via AirGate ...

Страница 59: ...s Position Picture Description LEFT button Use this button to move left or to change the mode The button can change the mode only if the main screen with the indicator of currently selected mode is displayed Note This button will not change the mode if the controller mode is forced by one of binary inputs listed in the Reference Guide Operating modes chapter RIGHT button Use this button to move ri...

Страница 60: ...utton to initiate the stop sequence of the gen set Repeated pressing of button will cancel current phase of stop sequence like cooling and next phase will continue GCB button Works in MAN and TEST modes only Press this button to open or close the GCB Indicators and others Position Description GENERATOR status indicator There are two states Gen set OK indicator is green and Gen set failure indicato...

Страница 61: ...tains all setpoints organized to groups and also a special group for entering password The page History log shows the history log in the order that the last record is displayed first Main Screen Symbols Padlock active when LBI ACCESS LOCK is active R active when there is active remote connection to controller Exclamation mark active when there is any alarm in alarmlist Measurement Screens Note Use...

Страница 62: ...Up and Down button to move between measurement pages Note Use Up and Down button to move between measurement pages Note Use Up and Down button to move between measurement pages Note Use Up and Down button to move between measurement pages ...

Страница 63: ...Up and Down button to move between measurement pages Note Use Up and Down button to move between measurement pages Note Use Up and Down button to move between measurement pages Note Use Up and Down button to move between measurement pages ...

Страница 64: ...Up and Down button to move between measurement pages Note Use Up and Down button to move between measurement pages Note Use Up and Down button to move between measurement pages Note Use Up and Down button to move between measurement pages ...

Страница 65: ...Up and Down button to move between measurement pages Note Use Up and Down button to move between measurement pages Note Use Up and Down button to move between measurement pages Note Use Up and Down button to move between measurement pages ...

Страница 66: ...Up and Down button to move between measurement pages Note Use Up and Down button to move between measurement pages Note Use Up and Down button to move between measurement pages Note Use Up and Down button to move between measurement pages ...

Страница 67: ...e Use Up and Down button to move between measurement pages Note From all of these pages it is possible to switch seamlessly to the setpoint group page by pressing Page button Note There can be some additional screens and also some screens can be hidden Screen s visibility depends on actual configuration usage of extension or communication modules ECU etc ...

Страница 68: ...luently go to the setpoint group page by pressing Page button Note Use Up and Down button to select required setpoint group Note Use Enter button to enter selected setpoint group Note Use Left and Right button to select required setpoint Note Use Enter button to enter selected setpoint ...

Страница 69: ...s value and to return to the list of setpoints of selected group IMPORTANT Cannot change setpoint Setpoints marked with an padlock are password protected Enter password as described in the chapter Password page 74 History Log Note From all measurement pages we can fluently go to the setpoint group page by pressing Page button Note From setpoint group page we can fluently go to the history log page...

Страница 70: ...e Up and Down button to select required alarm reason Note Use Enter button to move to the next page of history log Note Use Up and Down button to select required alarm reason Note Use Enter button to move to the next page of history log Note Use Up and Down button to select required alarm reason Note Use Enter button to move to the next page of history log ...

Страница 71: ...e Up and Down button to select required alarm reason Note Use Enter button to move to the next page of history log Note Use Up and Down button to select required alarm reason Note Use Enter button to move to the next page of history log Note Use Up and Down button to select required alarm reason Note Use Enter button to move to the next page of history log ...

Страница 72: ...e Up and Down button to select required alarm reason Note Use Enter button to move to the next page of history log Note Use Up and Down button to select required alarm reason Note Use Enter button to move to the next page of history log Note Use Up and Down button to select required alarm reason Note Use Enter button to move to the next page of history log ...

Страница 73: ...on to move to the first page of history log IMPORTANT The records are numbered in reverse order i e the latest newest record is 0 and older records have 1 2 etc Note This is only basic history record There can be some additional screens in case that in controller is extension module or ECU is configured Also it depends on connection type 5 3 3 Browsing alarms Note Use Up button to move to alarmlis...

Страница 74: ...und It means the alarm is no more active i e the appropriate alarm conditions are gone Not confirmed alarms are displayed with an asterisk It means the alarm is still not acknowledged confirmed ECU alarms SPN FMI OC SC SPN Suspect parameter number FMI type of protection OC number of errors SC source of error 5 3 4 Password Enter password Note From all measurement pages we can fluently go to the se...

Страница 75: ...oup Password Note Use Up and Down button to select Enter Password Note Use Enter button to enter selected setpoint Note Use Up and Down button to set required value of selected setpoint Note Use Left and Right button to move between digits Note Use Enter button to confirm the password or Page button to cancel entering the password ...

Страница 76: ... to menu Change password Note From all measurement pages we can fluently go to the setpoint group page by pressing Page button Note Use Up and Down button to select setpoint group Password Note Use Enter button to enter setpoint group Password Note Use Up and Down button to select Change Password Note Use Enter button to enter selected setpoint ...

Страница 77: ... Note Use Left and Right button to move between digits Note After setting new password use Enter button to confirm adjusted password Note Use Up and Down button to set required value of password again Note Use Left and Right button to move between digits Note After setting new password again use Enter button to confirm adjusted password or Page button to discard changes and to cancel changing pass...

Страница 78: ...ord has to be entered before changing the password Log out from controller Note From all measurement pages we can fluently go to the setpoint group page by pressing Page button Note Use Up and Down button to select setpoint group Password Note Use Enter button to enter setpoint group Password Note Use Up and Down button to select Enter Password Note Use Enter button to enter selected setpoint ...

Страница 79: ... brute force The protection works at every controller interface separately 1 When an invalid password is entered 5 times after each other independently on the time period elapsed between the attempts the controller will be blocked after the 5th unsuccessful attempt for 1 minute at the particular interface 2 While the controller is blocked it refuses any further attempts to enter password 3 When un...

Страница 80: ...ote On Main measurement screen press Enter and Page button together Enter button has to be pressed first Note Use Page button to move to the next page Note Use Page button to move to the next page Note Use Up button to move back to main measurement screen ...

Страница 81: ...tion Note On Main measurement screen press Enter and Page button together Enter button has to be pressed first Note Use Page button to move to the next page Note Use Page button to move to the next page Note Use Page button to move to the next page ...

Страница 82: ...t Note On any measurement screen press Enter and Up button together for higher contrast Note After setting a contrast no another action is needed 6 back to Controller setup 5 4 Remote Display This chapter describes Remote display firmware IL3 RD which is designed as a remote signaling and control software for InteliLite family controllers It is the optional software which is possible to upload int...

Страница 83: ...as default option Thus it is necessary use More options button to pick IL3 RD firmware for uploading to controller See details on picture below Note IL3 RD consists firmware only there is no archive included Note When IL3 RD firmware is uploaded to controller there is only possible connect InteliConfig using USB connection InteliConfig serves only for firmware update when connected to Remote displ...

Страница 84: ...o use standard Null modem cable crossover cable although three wires TxD RxD GND RS 232 connection is enough for communication RS485 It is necessary to use CM RS232 485 communication module on both Master controller and Remote display COM 2 communication channel is used with these settings COM 2 Mode Direct COM 2 Communication Speed 57600 or 115200 bps Controller Address 1 32 The maximal distance ...

Страница 85: ...atible configuration type is found in detected controller the message Unknown cfg format COM x Addr yy is displayed on screen for 5 seconds and detecting continues with next address in the range When detecting finishes with no compatible Master controller found the message No connection is displayed on screen for 5 seconds and detecting process starts from the beginning and continues until compati...

Страница 86: ... to above mentioned limitation considered Master device is always able to work without connected Remote display Disconnecting of the serial line between Master controller and Remote display has no effect to the Master controller When the serial line between Master controller and Remote display is disconnected or communication cannot be established Remote display shows it s own Init screen and mess...

Страница 87: ...ence detection 117 5 5 18 Gen set operation states 118 5 5 19 Sensor curves 120 5 5 20 PLC 122 5 5 21 Geo fencing 129 5 5 22 Tier 4 Final 129 5 5 23 Alternate configuration 132 5 5 24 ECU Frequency selection 133 5 5 25 Cybernetic security 133 6 back to Controller setup 5 5 1 Start stop sequence State Condition of the transition Action Next state Ready Start request PRESTART PAGE 585 on Prestart Ti...

Страница 88: ... elapsed STARTER PAGE 597 on FUEL SOLENOID PAGE 572 on STOP SOLENOID PAGE 598 off Maximum Cranking Time page 190 counter started Cranking Starting Idle Time page 198 elapsed Minimal Stabilization Time page 200 and Maximal Stabilization Time page 201 counter started Running any shutdown condition FUEL SOLENOID PAGE 572 off STOP SOLENOID PAGE 598 on Shutdown all cranking attempts elapsed FUEL SOLENO...

Страница 89: ...to change the mode Note The mode cannot be changed if Access Lock input is active The following binary inputs can be used to force one respective operating mode independent of the mode setpoint selection Remote OFF page 536 Remote MAN page 536 Remote AUTO page 535 If the respective input is active the controller will change the mode to the respective position according to the active input If multi...

Страница 90: ...e 117 signals becomes active The controller remains in the Starting phase until the engine speed exceeds the value of Starting RPM page 191 after that it is considered as started and the Idle period will follow The maximum duration that the output STARTER PAGE 597 is energized is determined by the setpoint Maximum Cranking Time page 190 If the engine does not start within this period the output ST...

Страница 91: ...InteliLite Global Guide 91 Image 5 13 Flowchart of start of diesel engine ...

Страница 92: ... period will follow IMPORTANT Additional running engine indications page 117 signals are not evaluated during the start of a gas engine The Pickup must be used in any case The maximum duration that the output STARTER PAGE 597 is energized is determined by the setpoint Maximum Cranking Time page 190 If the engine does not start within this period outputs STARTER PAGE 597 and FUEL SOLENOID PAGE 572 ...

Страница 93: ...InteliLite Global Guide 93 Image 5 14 Flowchart of start of gas engine ...

Страница 94: ... page 201 period the appropriate protection s will be activated and the gen set will be cooled down and stopped Note The limits for the generator voltage and frequency are given by setpoints in the Group Generator settings page 227 Note The value of the Minimal Stabilization Time page 200 setpoint has to be lower than the value of Maximal Stabilization Time page 201 setpoint 5 5 5 Connecting to lo...

Страница 95: ...hich role controller has in Dual Operation IMPORTANT For correct communication it is necessary to have one Master and one Slave controller on the same communication line IMPORTANT There are no shared setpoints It is necessary to have the same settings of engine timers in both controllers In case of communication fail between controllers alarm Dual Operation Fail page 665 is activated This alarm is...

Страница 96: ...nt Running Hours Base page 240 This setpoint can add or remove additional running hours to value from statistics This modified value of running hours is used in dual operation function Note In case that both gen sets have the same running hours Master controller has higher priority Note Switching of gen sets can be inhibit by setpoint Swap Gen sets page 240 or by binary input DUAL SWAP GEN SETS PA...

Страница 97: ...8 is energized The engine will stop within the time period determined by the setpoint Stop Time page 203 If the engine does not stop within this time the alarm Wrn Stop Fail page 663 will be issued The output STOP SOLENOID PAGE 598 is energized until the engine is stopped but at least for the duration of Stop Time page 203 If the Stop Time page 203 has elapsed and the engine has still not stopped ...

Страница 98: ...ished Only Generator under overvoltage Generator voltage unbalance and Generator under overfrequency belong to this category This category is not configurable to binary and analog input alarms If an alarm is being evaluated and the appropriate alarm condition is fulfilled the delay of evaluation will start to run The delay is adjustable by a setpoint in the case of built in alarms analog input ala...

Страница 99: ...81 and ALARM PAGE 552 Alarm indication only The alarm indication only alarm does not perform any actions regarding gen set control Alarm is only displayed in alarmlist History record only HistRecOnl The event is recorded into the history Standard alarm outputs HORN PAGE 581 and ALARM PAGE 552 are not activated Alarm types Level 2 The level 2 level alarm indicates that a critical level of the respe...

Страница 100: ...RL Note Sometimes there can be problem with lower limit of valid range which can be counted as negative number In this case the lower limit is set as one half of the RL point of the sensor curve characteristic Image 5 17 Sensor fail detection principle Remote alarm messaging If communication plug in module is connected to the controller the controller can send SMS messages and emails at the moment...

Страница 101: ...the prefix can be omitted User configured alarms An alarm message in the alarmlist begins with a prefix which represents the alarm type e g Wrn Sd BOC Alarm type is selected by user during the configuration of binary or analog input as alarm Then the alarm name follows Name is adjusted by user during the configuration of binary or analog input as alarm ECU alarms The ECU alarms are received from t...

Страница 102: ... tried without success Parameters Fail NONE Wrong check sum of parameters Happens typically after downloading new firmware or changing of the parameter The controller stays in INIT mode Check all parameters change value of at least one parameter Sd Gen Lx V BOC Gen Lx V where x 1 2 3 SD BOC The generator voltage is out of limits given by Gen V BOC and Gen V Sd setpoints BOC Gen V Unbalance BOC The...

Страница 103: ...int The protection comes if counter reaches zero Wrn Maintenance 2 WRN The period for servicing is set by the Maintenance Timer 2 page 220 setpoint The protection comes if counter reaches zero Wrn Maintenance 3 WRN The period for servicing is set by the Maintenance Timer 3 page 220 setpoint The protection comes if counter reaches zero Charge Alternator Fail WRN Failure of alternator for charging t...

Страница 104: ...tage Vg31 Generator voltage Ph31 Generator Current Ig1 Generator current Ph1 Generator Current Ig2 Generator current Ph2 Generator Current Ig3 Generator current Ph3 Voltage Battery VBat Voltage of battery Analog Input 1 Ain1 Analog input 1 Analog Input 2 Ain2 Analog input 2 Analog Input 3 Ain3 Analog input 3 Analog Input 4 Ain4 Analog input 4 Binary Inputs BIN Controller binary inputs Binary Outpu...

Страница 105: ...control of a contactor Its state represents the breaker position requested by the controller The breaker must react within 2 seconds to a close or open command otherwise an alarm is issued ON coil An output giving a 2 second pulse in the moment the breaker has to be closed The output is intended for control of close coils of circuit breakers OFF coil An output giving a pulse in the moment the brea...

Страница 106: ... different time delays for breaker fail detection see following diagrams When binary output breaker close open is in steady state and breaker feedback is changed the breaker fail is detected immediately no delay Image 5 19 Breaker fail breaker close open in steady position open Image 5 20 Breaker fail breaker close open in steady position close When binary output breaker close open opens there is ...

Страница 107: ...eriodic tests of the gen set scheduled transfer of the load to the gen set prior to an expected disconnection of the mains etc Related setpoints for timer 1 are Timer 1 Function page 303 Timer 1 Repetition page 304 Timer 1 First Occur Date page 305 Timer 1 First Occur Time page 305 Timer 1 Duration page 305 Timer 1 Repeated page 306 Timer 1 Repeat Day page 309 Timer 1 Day page 308 Timer 1 Repeated...

Страница 108: ...xcluded E g the timer can be adjusted to every 2nd day excluding Saturdays and Sundays Weekly The timer is activated every x th week on selected weekdays The week period x is adjustable E g the timer can be adjusted to every 2nd week on Monday and Friday Monthly The timer is activated every x th month on the selected day The requested day can be selected either as y th day in the month or as y th ...

Страница 109: ...etpoint Than go to Timer 1 Setup and press enter button In Timer 1 Repetition page 304 setpoint select Once mode Than adjust Timer 1 First Occur Date page 305 Timer 1 First Occur Time page 305 and Timer 1 Duration page 305 Note Use left and right buttons to move between timer setpoints Daily mode Set up via InteliConfig To set up timer via InteliConfig go to the setpoint ribbon setpoint group sche...

Страница 110: ...o to the Scheduler setpoint group Select the function of timer via Timer 1 Function page 303 setpoint Than go to Timer 1 Setup and press enter button In Timer 1 Repetition page 304 setpoint select Repeated mode Than adjust Timer 1 First Occur Date page 305 Timer 1 First Occur Time page 305 and Timer 1 Duration page 305 In setpoint Timer 1 Repeated page 306 select Daily and adjust Timer 1 Refresh P...

Страница 111: ...oller go to the Scheduler setpoint group Select the function of timer via Timer 1 Function page 303 setpoint Than go to Timer 1 Setup and press enter button In Timer 1 Repetition page 304 setpoint select Repeated mode Than adjust Timer 1 First Occur Date page 305 Timer 1 First Occur Time page 305 and Timer 1 Duration page 305 In setpoint Timer 1 Repeated page 306 select Weekly and adjust Timer 1 D...

Страница 112: ...ttings adjust date and time of first occurrence of timer Also adjust the duration of each occurrence of timer Than select the type of monthly repetition and the x th day of repetition Timer 1 Repeat Day In Month page 309 Than select the x th month of repetition Example On image example first start of timer will be 1 1 2016 at 12 00 Duration will be 1 hour Timer will be again activated every 2nd da...

Страница 113: ...nt select Repeated mode Than adjust Timer 1 First Occur Date page 305 Timer 1 First Occur Time page 305 and Timer 1 Duration page 305 In setpoint Timer 1 Repeated page 306 select Monthly and adjust type of monthly repetition via Timer 1 Repeat Day page 309 Timer 1 Refresh Period page 307 x th month of repetition and Timer 1 Repeat Day In Month page 309 concrete day in repeated months Second type o...

Страница 114: ...timer will be 1 1 2016 at 12 00 Duration will be 1 hour Timer will be again activated every 4th hour for 1 hour Set up via controller interface In controller go to the Scheduler setpoint group Select the function of timer via Timer 1 Function page 303 setpoint Than go to Timer 1 Setup and press enter button In Timer 1 Repetition page 304 setpoint select Repeated mode Than adjust Timer 1 First Occu...

Страница 115: ...value of counters is located either as the same setpoints Maintenance Timer 1 page 219 Maintenance Timer 2 page 220 and Maintenance Timer 3 page 220 or as values Maintenance 1 page 469 Maintenance 2 page 469 and Maintenance 3 page 470 When the value of counter reaches 0 the alarm Wrn Maintenance 1 page 661 or Wrn Maintenance 2 page 662 or Wrn Maintenance 3 page 662 is active until the respective c...

Страница 116: ...itch 12 Off page 277 AIN SWITCH12 PAGE 558 AIN SWITCH 13 PAGE 628 Analog Switch 13 On page 279 Analog Switch 13 Off page 280 AIN SWITCH13 PAGE 559 AIN SWITCH 14 PAGE 628 Analog Switch 14 On page 282 Analog Switch 14 Off page 283 AIN SWITCH14 PAGE 559 AIN SWITCH 15 PAGE 628 Analog Switch 15 On page 285 Analog Switch 15 Off page 286 AIN SWITCH15 PAGE 560 AIN SWITCH 16 PAGE 629 Analog Switch 16 On pa...

Страница 117: ...ckup is not used and frequency is not detected on the pickup input Connect the pickup input to the W terminal of the charging alternator if you do not use pickup and the W terminal is available If not leave the input unconnected Oil pressure Starting Oil Pressure page 192 setpoint The oil pressure is evaluated from the analog input or from the ECU if an ECU is configured Binary input OIL PRESSURE ...

Страница 118: ...574 is closed Stop Stop Example Automatic or manual stop command was issued engine is stopping Shutdown Shut down alarm activated Ready Gen set is ready to run Cooling Gen set is cooling before stop EmergMan EMERGENCY MAN PAGE 527 gen set operation Example Used for bypass the controller and engine manual start Engine started conditions Engine speed RPM Starting RPM page 191 or Oil pressure Startin...

Страница 119: ...l voltage Wrn Stop Fail has delay 1 s for generator voltage 50 of nominal voltage Wrn Stop Fail has delay 200 ms Oil pressure Starting Oil Pressure page 192 Wrn Stop Fail has delay 1 s Binary input OIL PRESSURE PAGE 534 is in logical 0 Wrn Stop Fail has delay 1 s for detected RPM there is no delay Stop engine conditions If no engine running conditions are validated than the controller will wait ex...

Страница 120: ...ration page 329 directly to the calculated value at analog input Note The calibration must be done at the operational point of the analog input e g 80 C 4 0Bar etc Default sensor curves There are 16 default resistive curves available The following table provides information on minimum maximum values of respective sensors Actual values especially of temperature curves may differ Meaning is to prolo...

Страница 121: ...eneral line 10 0 1000 ohm General line 11 0 1000 ohm General line 12 0 1000 ohm General line 13 0 1000 ohm Note Curves can be modified via InteliConfig In InteliConfig are also prepared some standard curves IMPORTANT For right behavior of function curve for this analog input has to be in percentage and setpoint Fuel Tank Volume page 216 has to be adjusted correctly 6 back to Functions ...

Страница 122: ...has graphical interface to have user interface easy to use Image 5 32 PLC Editor main page List of available PLC blocks PLC block Number of blocks OR AND 16 XOR RS 2 Comparator with hysteresis Comp Hyst 2 Comparator with delay Comp Time 2 Timer 1 Delay 4 Force history record Force Hist 2 Force protection Force Prot 2 ...

Страница 123: ...efine inputs and outputs page 124 for more information Create connections between inputs blocks and outputs See Creating wires page 127 for more information Adjust properties of the blocks See List of PLC blocks page 636 for more information about blocks Working with sheets Drag the sheet edges to re size the sheet according to your needs Image 5 33 Adjusting PLC sheet Adding PLC blocks Adding PLC...

Страница 124: ...t is also possible to connected inputs and outputs via properties of selected PLC block Image 5 34 Adding PLC blocks Note To delete PLC block just click on it and press delete button Also delete selection function can by used Note To see context help for selected PLC block just press F1 button Define inputs and outputs Image 5 35 Blank sheet of PLC editor ...

Страница 125: ...contains all PLC blocks binary outputs available in the controller If you create an analog input you can select a source from following categories Ana Values this category contains all analog values available in the controller as analog inputs electrical values values from ECU etc All Setpoints this category contains all setpoints of the controller except the dedicated PLC setpoints Names resoluti...

Страница 126: ...ocedure below to add or edit an input Doubleclick on a free output position to add new sheet output Doubleclick on an already created output to configure the output onto a controller output terminal or a logical binary input first of all some PLC block output has to be connected to this output to enable configuration of output ...

Страница 127: ...rt from inputs Wires between blocks and outputs have to start from blocks Follow the procedure below to create wire Locate the mouse pointer over the starting point of the wire If the area under the mouse pointer is a connection point the pointer will change the color fill of pointer will be white Press and hold the left mouse button and drag the wire to the destination of required connection poin...

Страница 128: ...ete selection function can by used PLC logic execution rules The PLC program is executed every 100 ms The blocks are executed in order according to block numbers item numbers which are indicated in each block The block numbers are assigned automatically according to position on sheet Image 5 38 PLC execution logic IMPORTANT Please always check that the blocks are ordered correctly especially if yo...

Страница 129: ... geographic area with centre common for both geo circles named Home Position adjusted via setpoints Home Latitude page 322 and Home Longitude page 322 and radius named Fence Radius adjusted via setpoints Fence Radius 1 page 323 and Fence Radius 2 page 323 Protections can be different for both circles Protection are adjusted via setpoints Fence 1 Protection page 325 and Fence 2 Protection page 326 ...

Страница 130: ...n Image 5 40 Example of inactive Tier 4 Final screen Universal lamps icons Universal lamp icons are shown on the After Treatment screen Based on specific value read in specific frame with specific SPN is every lamp icon either shown hidden blinking slow 1 Hz blinking fast 2 Hz Note Lamp icon blinking is defined as displaying active lamp icon and inverse colored active lamp icon in required frequen...

Страница 131: ...ter Treatment page 664 Exhaust system high temperature lamp command Note This lamp also activates alarm After Treatment page 664 Malfunction indicator lamp Note This value can light or blink on both frequencies This lamp also activates alarm After Treatment page 664 Fluid tank low level indicator Note This lamp also activates alarm After Treatment page 664 DPF regeneration inhibited Note Indicates...

Страница 132: ...ency 2 page 335 Nominal Voltage Ph N 2 page 336 Nominal Voltage Ph Ph 2 page 336 Nominal Current 2 page 335 Connection type 2 page 333 ECU Speed Adjustment 2 page 342 Nominal Power Split Phase 3 page 341 Nominal Power 3 page 341 Nominal RPM 3 page 340 Nominal Frequency 3 page 339 Nominal Voltage Ph N 3 page 340 Nominal Voltage Ph Ph 3 page 340 Nominal Current 3 page 339 Connection type 3 page 337 ...

Страница 133: ... Protection against a brute force attack to the password Secure method to reset the password A new technology of encryption of the remote communication Web interface can be disabled IMPORTANT Due to this we do not recommend performing a rollback from FW 1 8 0 to FW version 1 7 2 or older Hardening the storage of a credentials The user credentials passwords and access code have been moved to a hard...

Страница 134: ...ult value as described below Note Blocking of the controller for entering the password have no influence to controller genset operation Note Permanent blocking cannot occur accidentally just by user mistake It can be practically triggered only by a focused activity Resetting the administrator password If the administrator password is lost or controller is permanently locked due to brute force atta...

Страница 135: ...Lite Global Guide 135 Reset password procedure 1 Connect InteliConfig You may connect remotely if you know Access Code 2 Get the password reset request code and send it via e mail to support comap control com ...

Страница 136: ...InteliLite Global Guide 136 3 Once you receive the reply from ComAp copy the code from the e mail all characters inside the box as indicated below ...

Страница 137: ...t AirGate This technology is based on strong and proven cryptographic algorithms and has passed successfully penetration tests and cybersecurity audit Web interface can be disabled A setpoint has been added to disable the CM ETHERNET built in web interface IMPORTANT As the web interface is using HTTP protocol it is recommended to disable the web interface unless the controller is connected into a ...

Страница 138: ...a RS232 connection The module is plugged into the slot located on the rear side of the controller To find more information about installation of the modules see Plug in module installation on page 48 RS232 interface uses COM1 Mode page 343 port of the controller Use a cross wired serial communication cable with DB9 female connectors and signals Rx Tx GND Note Also USB RS232 convertor can be used I...

Страница 139: ...about installation of the modules see Plug in module installation on page 48 This connection type is used for communication with the controller from InteliConfig or any other PC tool This connection can be used regardless of AirGate is switched on or off Only three remote clients can be connected at the same time via AirGate only two remote clients at the same time To connect your PC tool to the c...

Страница 140: ... address First way is to switch theCM Ethernet to manual IP address mode Adjust the setpoint IP Address Mode page 378 to FIXED In that case all setpoints of IP settings IP Address page 378 Subnet Mask page 379 Gateway IP page 379 DNS IP Address 1 page 380 have to be adjusted manually If this method is used several basic rules should be kept to avoid conflicts with the remaining network infrastruct...

Страница 141: ...CM Ethernet at the port specified for ComAp protocol Different port numbers can be used to create multiple port forwarding rules in the same local network AirGate This connection type is intended for remote connection from InteliConfig or any other ComAp PC tool over the Internet in situations where obtaining fixed public IP address is not possible Only two remote clients can be connected at the s...

Страница 142: ...setting of setpoints Wrn Message page 375 Sd Messages page 375 BOC Message page 375 Note Firstly setpoint Telephone Number 1 page 368 has to be adjusted Message structure Gen set Name AL Alarm 1 Alarm 2 Alarm x Note Asterisk means that alarm is unconfirmed and exclamation mark means that alarm is active SMS commands To control the gen set equipped with InteliLite controller and CM GPRS or CM 4G GP...

Страница 143: ...cb open stop auto Controller mode will be changed to MANUAL mode The engine will be started and GCB will close Then GCB will open the engine will stop and it will go into AUTO mode again The controller will send back the SMS controller will respond to SMS after every command has been finished not sooner InteliLite Test OK OK OK OK OK OK The value OK or ERROR means if the command has been performed...

Страница 144: ... Email The InteliLite controller equipped with the CM Ethernet communication module is able to send Alarm Emails according to the setting of setpoints Wrn Message page 375 Sd Messages page 375 BOC Message page 375 Note Firstly setpoints Email Address 1 page 371 and SMTP Sender Address page 365 for CM GPRS or SMTP Sender Address page 377 for CM Ethernet have to be adjusted Note Summer Time Mode pag...

Страница 145: ...n XXX Application XXX Appl version XXX Date dd mm yyyy Time hh mm ss Alarm list Alarm 1 Alarm 2 Alarm 3 History events 0 dd mm yyyy hh mm ss 0 Event 1 1 dd mm yyyy hh mm ss 0 Event 2 2 dd mm yyyy hh mm ss 0 Event 3 Note Asterisk means that alarm is unconfirmed and exclamation mark means that alarm is active ...

Страница 146: ...e browser to display the main controller web page like http 192 168 1 254 You will be asked for the controller access code prior to entering the web pages IMPORTANT Do not use the browser navigation buttons as Back Forward or Reload Use the links and the reload button located in the toolbar instead Note Only two remote clients can be connected to the Web Server at one moment If you close your web ...

Страница 147: ... SCADA link in the toolbar to display the scada page The scada page is also the main page which is displayed by default if you just put the CM Ethernet address into the browser after entering the right access code Image 6 8 Web Server Scada screen ...

Страница 148: ...toolbar to display the measurement page Then click to the required group name in the left box to display values of the group in the right box Note The measurement page is automatically refreshed every 60 seconds this time cannot be changed Image 6 9 Web Server measurement screen ...

Страница 149: ...o display setpoints of the group in the right box Click to the required setpoint name or value to change the value If the respective setpoint is protected by password which is indicated by a lock icon by the setpoint name you have to click on the Controller password icon located in the toolbar and then enter valid password Image 6 10 Web Server Setpoints screen ...

Страница 150: ...play the history page Use the control buttons to move within the history file Note The history page is automatically refreshed every 60 seconds If a new record appears in the controller the web page will not show it immediately as e g InteliConfig Image 6 11 Web Server History screen ...

Страница 151: ...US RTU MODBUS TCP 153 6 back to Communication 6 2 1 SNMP SNMP is an UDP based client server protocol used for providing data and events into a supervisory system building management system The controller plays the role of a SNMP Agent while the supervisory system plays the role of a SNMP Manager CM Ethernet module is required for SNMP function Supported versions SNMP v1 and SNMP v2c The SNMP Agent...

Страница 152: ...ent may send to the Manager GroupRdFix contains read only objects that exist in all controller regardless of the firmware version type and configuration GroupRdCfg contains read only objects that depend on the firmware version type and configuration GroupWrFix contains read write objects that exist in all controller regardless of the firmware version type and configuration GroupWrCfg contains read...

Страница 153: ...g tools MODBUS RTU can be used on serial interfaces CM RS232 485 module is required The MODBUS RTU server must be activated by switching the setpoint COM1 Mode page 343 or COM2 Mode page 345 into the Modbus position The serial speed for MODBUS RTU communication is to be adjusted by the setpoint COM1 MODBUS Communication Speed page 344 or COM2 MODBUS Communication Speed page 346 MODBUS TCP can be u...

Страница 154: ...MODBUS messages correctly Data type Meaning Number of registers Data maping Integer8 1 byte signed integer 1 MSB sign extension LSB value Unsigned8 1 byte unsigned integer 1 MSB 0 LSB value Integer16 2 byte signed integer 1 MSB value MSB LSB value LSB Unsigned16 2 byte unsigned integer 1 MSB value MSB LSB value LSB Integer32 4 byte signed integer 2 MSB1 value byte 3 MSB LSB1 value byte 2 MSB2 valu...

Страница 155: ...SB2 ASCII value of the 3 character LSB2 ASCII value of the 4 character Date Date dd mm yy 2 MSB1 BCD dd LSB1 BCD mm MSB2 BCD yy LSB2 0 Time Time hh mm ss 2 MSB1 BCD hh LSB1 BCD mm MSB2 BCD ss LSB2 0 Alarm An item of the Alarmlist 27 MSB1 reserved for future use LSB1 reserved for future use MSB2 Alarm level LSB2 Alarm status MSB3 alarm string LSB3 alarm string MSB4 alarm string LSB5 alarm string 1 ...

Страница 156: ...signed8 Index of the language that is used for text data provided by MODBUS e g alarmlist messages 4205 4206 2 read Unsigned32 Last application error To be read after the device returns the exception code 04 It contains specific information about the error 4207 4208 2 read write Unsigned32 Writing command argument Reading command return value 4209 1 write Unsigned16 Command code 4010 1 Not impleme...

Страница 157: ...esses 4207 4208 Use function 16 3 Write the command code into the register 44210 register address 4209 Use function 6 4 Optional Read the command return value from the registers 44208 44209 register addresses 4207 4208 Use function 3 5 If the command was executed the return value is as listed in the table If the command was accepted but there was an error during execution the return value indicate...

Страница 158: ... read Data 00F0hex 240dec CRC We read value 240 from register 01053 From table of modbus registers we get dimension of read value and Dec Dec 1 means shift one decimal place to the right So battery voltage is 24 0 V Reading Nominal power Export table of values from InteliConfig Table Values Allowed MODBUS functions 03 04 Register s Com Obj Name Dimension Type Len Dec Min Max Group 01228 9018 Nomin...

Страница 159: ...t Numbers in Hex 01 03 04 2C 00 01 44 F3 Controller address Modbus function Register address 042Chex 1068dec Number of registers CRC Response Numbers in Hex 01 03 02 00 12 38 49 Controller address Modbus function Length of data 02hex 2 bytes read Data 0012hex 00010010bin CRC Binary inputs is 00010010 It means Binary input 2 and binary input 5 are active Note You can use modbus function 4 insted of...

Страница 160: ...edback Controller I O 00002 Value 8235 Binary Inputs 3 Emergency Stop Controller I O We will read state of MCB Feedback binary input Request Numbers in Hex 01 01 00 01 00 01 AC 0A Controller address Modbus function Register address 0001hex 0001dec Number of registers CRC Response Numbers in Hex 01 01 01 01 90 48 Controller address Modbus function Length of data 01hex 1 byte read Data 01hex active ...

Страница 161: ... List of commands and arguments page 157 Action Command code Argument Return value Engine start 0x01 0x01FE0000 0x000001FF Engine stop 0x01 0x02FD0000 0x000002FE Request 1 2 Numbers in Hex 01 10 10 6F 00 03 06 Controller address Modbus function 10hex 16dec Register address 106Fhex 4207dec Number of registers Data length in bytes Request 2 2 Numbers in Hex 01 FE 00 00 00 01 68 0B Argument Command c...

Страница 162: ...e the password is 1234 Request Numbers in Hex 01 06 10 73 04 D2 7C D1 Controller address Modbus function Register address 1073hex 4211dec Password 04D2hex 1234dec CRC Response for success Numbers in Hex 01 06 10 73 00 00 7C D1 Controller address Modbus function Register address 1073hex 4211dec Allways zero CRC Response for bad password Numbers in Hex 01 86 04 43 A3 Controller address Modbus except...

Страница 163: ...1 06 0B C0 00 00 8B D2 Controller address Modbus function Register address 0BC0hex 3008dec Allways zero CRC Writen setpoint nominal power is 100 kW CRC calculation The check field allows the receiver to check the validity of the message The check field value is the Cyclical Redundancy Check CRC based on the polynomial x16 x15 x2 1 CRC is counted from all message bytes preceding the check field Onl...

Страница 164: ...gisters Request Numbers in Hex 00 00 00 00 00 06 01 03 04 1D 00 01 transaction identifier usually 0 protocol identifier usually 0 Length of data bytes following Controller address Modbus function Register address 041Dhex 1053dec Number of registers Response Numbers in Hex 00 00 00 00 00 05 01 03 02 00 F0 transaction identifier usually 0 protocol identifier usually 0 Length of data bytes following ...

Страница 165: ...anada Linear measurement and protection range 381 V 660 V Accuracy 1 Frequency range 40 70 Hz accuracy 0 1 Hz Input impedance 0 72 MΩ ph ph 0 36 MΩ ph n Voltage measurement USB port non isolated CAN 1 CAN bus 250 kbps max 200 m 120 Ω termination option non isolated Communications Measurement inputs 3ph Gen current Measurement range 5 A Max allowed current 10 A Accuracy 1 5 for full temperature ran...

Страница 166: ... kHz 6 Vpk pk to 50 Vpk pk in range 1 kHz to 5 kHz 10 Vpk pk to 50 Vpk pk in range 5 kHz to 10 kHz Frequency input range 4 Hz to 10 kHz Frequency measurement tolerance 0 2 from range 10 kHz Magnetic pickup 6 back to Table of contents InteliLite Global Guide 166 ...

Страница 167: ...InteliLite Global Guide 167 8 Appendix 8 1 Controller objects 168 8 2 Alarms 647 8 3 Modules 691 6 back to Table of contents ...

Страница 168: ...InteliLite Global Guide 168 8 1 Controller objects 8 1 1 Setpoints 169 8 1 2 Values 451 8 1 3 Logical binary inputs 497 8 1 4 Logical binary outputs 538 8 1 5 Logical analog inputs 602 8 1 6 PLC 634 ...

Страница 169: ...ORTANT Do not write setpoints repeatedly e g power control from a PLC by repeated writing of baseload setpoint via Modbus The setpoints are stored in EEPROM memory which can be overwritten up to 105 times without risk of damage or data loss but it may become damaged when the allowed number of writing cycles is exceeded List of setpoint groups Group Basic settings 175 Group Engine settings 188 Grou...

Страница 170: ... 202 Cooling Time 203 Stop Time 203 After Cooling Time 204 D Function 204 D Treshold 206 D Delay 206 D Alarm Type 206 Overspeed Sd 207 Underspeed Sd 207 Overspeed Overshot 207 Overspeed Overshot Period 208 Oil Pressure Wrn 208 Oil Pressure Sd 208 Oil Pressure Delay 209 ECU Oil Pressure Wrn 209 ECU Oil Pressure Sd 209 ECU Oil Pressure Delay 210 Coolant Temperature Wrn 210 Coolant Temperature Sd 210...

Страница 171: ...log Protection 2 Wrn 244 Analog Protection 2 Sd 245 Analog Protection 2 Delay 245 Analog Switch 2 On 246 Analog Switch 2 Off 247 Analog Protection 3 Wrn 247 Analog Protection 3 Sd 248 Analog Protection 3 Delay 248 Analog Switch 3 On 249 Analog Switch 3 Off 250 Analog Protection 4 Wrn 250 Analog Protection 4 Sd 251 Analog Protection 4 Delay 251 Analog Switch 4 On 252 Analog Switch 4 Off 253 Analog ...

Страница 172: ...ff 301 Scheduler Time 301 Date 302 Time Stamp Period 302 Summer Time Mode 302 Timer 1 Function 303 Timer 1 Setup 304 Timer 1 Repetition 304 Timer 1 First Occur Date 305 Timer 1 First Occur Time 305 Timer 1 Duration 305 Timer 1 Repeated 306 Timer 1 Refresh Period 307 Timer 1 Weekends 308 Timer 1 Day 308 Timer 1 Repeat Day 309 Timer 1 Repeated Day In Week 309 Timer 1 Repeat Day In Month 309 Timer 1 ...

Страница 173: ...ges 354 Telephone Number 1 355 Telephone Number 2 355 Telephone Number 3 356 Telephone Number 4 356 DNS IP Address 357 AirGate Connection 357 AirGate Address 358 ComAp TCP Port 358 Internet Connection 359 Required Connection Type359 APN Name 360 APN User Name 360 APN User Password 361 Email Address 1 361 Email Address 2 362 Email Address 3 362 Email Address 4 363 Message Language 363 SMTP User Nam...

Страница 174: ...2 408 PLC Setpoint 23 409 PLC Setpoint 24 410 PLC Setpoint 25 411 PLC Setpoint 26 412 PLC Setpoint 27 413 PLC Setpoint 28 414 PLC Setpoint 29 415 PLC Setpoint 30 416 PLC Setpoint 31 417 PLC Setpoint 32 418 PLC Setpoint 33 419 PLC Setpoint 34 420 PLC Setpoint 35 421 PLC Setpoint 36 422 PLC Setpoint 37 423 PLC Setpoint 38 424 PLC Setpoint 39 425 PLC Setpoint 40 426 PLC Setpoint 41 427 PLC Setpoint 4...

Страница 175: ...t of setpoints Subgroup Power settings Setpoint group Basic settings Related FW 1 9 0 Range units 1 5 000 kW Default value 200 kW Alternative config Yes Step 1 kW Comm object 9977 Related applications AMF MRS Config level Standard Setpoint visibility Conditioned by the setpoint Connection type page 177 Description Nominal power of the gen set for detected split phase or mono phase connection Gener...

Страница 176: ...o have to lock setpoint Nominal Power 1 page 333 Nominal Power 2 page 337 and Nominal Power 3 page 341 Nominal Power 6 back to List of setpoints Subgroup Current settings Setpoint group Basic settings Related FW 1 9 0 Range units 1 10 000 A Default value 350 A Alternative config YES Step 1 A Comm object 8275 Related applications AMF MRS Config level Standard Setpoint visibility Conditioned by the ...

Страница 177: ... Range units Mono Phase SplPhL1L2 SplPhL1L3 3Ph3Wire 3Ph4Wire High Leg D Autodetect Default value 3Ph4Wire Alternative config YES Step Comm object 11628 Related applications AMF MRS Config level Standard Setpoint visibility Always Description Connection type Mono Phase Single phase voltage measurement L1 N 1x CT Current Transformer SplitPhase Double Delta connection Split Phase Two phase voltage m...

Страница 178: ...ement L1 L2 L3 with 120 phase shift No neutral is available 3x CT Current Transformer High Leg D High Leg Delta connection Three phase voltage measurement L1 L2 L3 3x CT Current Transformer Autodetect High Leg Delta or L1 100V L1 160V L2 160V L3 100V L3 160V 3PH3Wire or 3Ph4Wire or L1 100V L2 100V L3 100V 3PH Low Y or L1 20V L1 160V L2 20V L2 160V L3 20V L3 160V L1L2 300V L2L3 300V L3L1 300V 3PH H...

Страница 179: ... phase to neutral Note To lock this setpoint against editing you also have to lock setpoint Nominal Voltage Ph N 1 page 332 Nominal Voltage Ph N 2 page 336 and Nominal Voltage Ph N 3 page 340 Nominal Voltage Ph N 6 back to List of setpoints Setpoint group Basic settings Related FW 1 9 0 Range units 80 40 000 V Default value 400 V Alternative config YES Step 1 V Comm object 11657 Related applicatio...

Страница 180: ...ations AMF Config level Advanced Setpoint visibility Conditioned by the setpoint Operation Mode page 183 Description Mains voltage potential transformers ratio If no PTs are used adjust the setpoint to 1 Vm PT Ratio 6 back to List of setpoints Subgroup Frequency settings Setpoint group Basic settings Related FW 1 9 0 Range units 45 65 Hz Default value 50 Hz Alternative config YES Step 1 Hz Comm ob...

Страница 181: ...hould be used to prevent possible overcranking which can occur if at least 25 of nominal generator voltage is not present immediately after exceeding firing speed Gear Teeth 6 back to List of setpoints Setpoint group Basic settings Related FW 1 9 0 Range units 100 4 000 RPM Default value 1 500 RPM Alternative config YES Step 1 RPM Comm object 8253 Related applications AMF MRS Config level Advanced...

Страница 182: ...int group Basic settings Related FW 1 9 0 Range units Previous OFF Default value Previous Alternative config NO Step Comm object 13000 Related applications AMF MRS Config level Advanced Setpoint visibility Always Description This setpoint adjusts controller mode after power on of controller Previous When controller is power on than is switched into last mode before power off OFF When controller is...

Страница 183: ...ode will be able to start by REMOTE START STOP PAGE 536 binary input Operation Mode 6 back to List of setpoints Setpoint group Basic settings Related FW 1 9 0 Range units 1 32 Default value 1 Alternative config NO Step 1 Comm object 24537 Related applications AMF MRS Config level Standard Setpoint visibility Always Description Controller identification number It is possible to set controller addre...

Страница 184: ...matically in specific cases when fault reset button is pressed Example Controller is in AUTO mode and there is red inactive unconfirmed alarm and fault reset button is pressed controller will start automatically Reset To Manual 6 back to List of setpoints Setpoint group Basic settings Related FW 1 9 0 Range units Disabled 1 255 min Default value Disabled Alternative config NO Step 1 min Comm objec...

Страница 185: ...points Setpoint group Basic settings Related FW 1 9 0 Range units Disabled 1 360 min Default value Disabled Alternative config NO Step 1 min Comm object 8548 Related applications AMF MRS Config level Advanced Setpoint visibility Always Description The controller is switched to Zero Power Mode when there is no user interaction with the controller for the preset time period Zero Power Mode is disabl...

Страница 186: ... is some ECU which send valid running hours then this value is used Otherwise value from internal counter is used ECU Running hours are taken from ECU if ECU send valid data It is not possible to set and reset this value in statistics INTERNAL Running hours are taken from internal counter It is possible to set and reset this value in statistics Note It is not necessary to restart controller when t...

Страница 187: ... This setpoint enables disables filter values on CU screen and PC tools List of values which are filtered when filter is ON Generator Voltage L1 L2 Generator Voltage L2 L3 Generator Voltage L3 L1 Generator Voltage L1 N Generator Voltage L2 N Generator Voltage L3 N Generator Frequency Load kVA Load kVA L1 Load kVA L2 Load kVA L3 Load kVAr Load kVAr L1 Load kVAr L2 Load kVAr L3 Load kW Load kW L1 Lo...

Страница 188: ...s Description This setpoint adjusts line 1 on Mains screen Main Screen Line 1 6 back to List of setpoints Setpoint group Basic settings Related FW 1 9 0 Range units RPM PF Run Hours ATT AIN1 Default value RPM Alternative config NO Step Comm object 14628 Related applications AMF MRS Config level Advanced Setpoint visibility Always Description This setpoint adjusts line 2 on Mains screen Main Screen...

Страница 189: ... Lead page 198 The output opens if Emergency Stop comes or gen set is stopped and in pause between repeated starts Gas Gaseous Output closes together with binary output IGNITION PAGE 582 if RPM is over the 30 RPM fixed value Output opens after stop command or in pause between repeated start Fuel Solenoid 6 back to List of setpoints Setpoint group Engine settings Related FW 1 9 0 Range units 1 10 D...

Страница 190: ... case that there are no RPM after 5 seconds of starting cranking is interrupted and cranking fail pause follows Maximum Cranking Time 6 back to List of setpoints Setpoint group Engine settings Related FW 1 9 0 Range units 5 60 s Default value 8 s Alternative config NO Step 1 s Comm object 8257 Related applications AMF MRS Config level Advanced Setpoint visibility Always Description Pause between C...

Страница 191: ...ant to leave the output PRESTART PAGE 585 open Image 8 1 Prestart Time Prestart Time 6 back to List of setpoints Setpoint group Engine settings Related FW 1 9 0 Range units 5 50 Default value 25 Alternative config NO Step 1 of Nominal RPM page 181 Comm object 8254 Related applications AMF MRS Config level Advanced Setpoint visibility Always Description This setpoint defines the firing speed level ...

Страница 192: ... evaluation IMPORTANT Value from analog input has higher priority than value from ECU Starting Oil Pressure 6 back to List of setpoints Setpoint group Engine settings Related FW 1 9 0 Range units 0 Prestart Time page 191 s Default value 0 s Alternative config NO Step 1 s Comm object 14412 Related applications AMF MRS Config level Standard Setpoint visibility Always Description This setpoint define...

Страница 193: ... and Choke Increment page 195 are taken into consideration Choke Function 6 back to List of setpoints Setpoint group Engine settings Related FW 1 9 0 Range units 0 3600 s Default value 0 s Alternative config NO Step 1 s Comm object 13011 Related applications MRS AMF Config level Advanced Setpoint visibility Only when LBO CHOKE PAGE 567 is configured and setpoint Choke Function page 193 Fixed Time ...

Страница 194: ... and setpoint Choke Function page 193 Temp Based Description This setpoint adjust the base temperature for Choke function When temperature will be higher than this setpoint Choke Time will be always 0 When temperature will be lower than this setpoint Choke Time will be calculated by curve adjusted via setpoint Choke Increment page 195 When setpoint Choke Function page 193 is set to Fixed Time valu...

Страница 195: ...567 Calculated time depends on engine coolant temperature Setpoint adjust curve which is used for calculating actual Choke Time When setpoint Choke Function page 193 is set to Fixed Time value setpoint Choke Increment has no effect Note If setpoint Choke Lead page 197 is set to nonzero value total time the CHOKE output is activated still matches calculated value based on actual temperature and set...

Страница 196: ...Description This setpoint adjust threshold level for deactivation of CHOKE PAGE 567 binary output When generator voltage is higher than this level then logical binary output CHOKE is deactivated In multiphase system it is sufficient to deactivate CHOKE LBO when at least one voltage crosses this threshold In case setpoint Choke Voltage is set to Disabled value no voltage is taken into account and C...

Страница 197: ...Only when LBO CHOKE PAGE 567 is configured Description This setpoint adjust the lead of logical binary output CHOKE CHOKE PAGE 567 is activated before logical binary output STARTER PAGE 597 Note In case Choke Lead is longer than 8 s cranking fail pause Choke Lead will be limited to 8 s cranking fail pause time This limitation is applied only for cranking fail pause Choke Lead in Prestart stays unc...

Страница 198: ...l zero when Fuel Solenoid Lead goes to logical one Note This setpoint is used only for diesel Fuel Solenoid page 189 Fuel Solenoid Lead 6 back to List of setpoints Setpoint group Engine settings Related FW 1 9 0 Range units 0 600 s Default value 12 s Alternative config NO Step 1 s Comm object 9097 Related applications AMF MRS Config level Standard Setpoint visibility Always Description Idle Time d...

Страница 199: ...InteliLite Global Guide 199 nominal speed Image 8 3 Idle Time 1 Image 8 4 Idle Time 2 6 back to List of setpoints ...

Страница 200: ...Related applications AMF MRS Config level Standard Setpoint visibility Always Description When the gen set has been started and the idle timer has elapsed the controller will wait for a period adjusted by this setpoint before closing GCB even if the generator voltage and frequency are already in limits Image 8 5 Minimal Stabilization Time Minimal Stabilization Time 6 back to List of setpoints ...

Страница 201: ...ise an appropriate shutdown alarm generator voltage and or frequency is issued Image 8 6 Maximal Stabilization Time Maximal Stabilization Time 6 back to List of setpoints Setpoint group Engine settings Related FW 1 9 0 Range units 0 0 300 0 s Default value 5 0 s Alternative config YES Step 0 1 s Comm object 10023 Related applications AMF MRS Config level Advanced Setpoint visibility Always Descrip...

Страница 202: ... group Engine settings Related FW 1 9 0 Range units Idle Nominal Default value Nominal Alternative config NO Step Comm object 10046 Related applications AMF MRS Config level Advanced Setpoint visibility Always Description Selects the function of the binary output IDLE NOMINAL PAGE 582 during engine cooling state Idle Cooling is executed at Idle speed and generator protections are switched off Nomi...

Страница 203: ... Time 6 back to List of setpoints Setpoint group Engine settings Related FW 1 9 0 Range units 0 600 s Default value 60 s Alternative config NO Step 1 s Comm object 9815 Related applications AMF MRS Config level Advanced Setpoint visibility Always Description Under normal conditions the engine must certainly stop within this period after the FUEL SOLENOID PAGE 572 has been de energized and the STOP...

Страница 204: ...ption Runtime of engine after cooling pump Binary output Cooling pump is closed when the engine starts and opens AfterCool time delayed after gen set stops After Cooling Time 6 back to List of setpoints Subgroup D Function Setpoint group Engine settings Related FW 1 9 0 Range units Enabled ChargeFail Disabled Default value Disabled Alternative config NO Step Comm object 9683 Related applications A...

Страница 205: ...is used for both functions running engine detection and charge fail detection ChargeFail The D terminal is used for charge fail detection only Disabled The D terminal is not used Image 8 9 D Function 1 Image 8 10 D Function 2 6 back to List of setpoints ...

Страница 206: ...4960 Related applications MRS AMF Config level Advanced Setpoint visibility Only if setpoint D Function page 204 is not set to Disabled value Description This setpoint adjusts delay for D function This delay is used for Alarm Charging Alternator Fail For engine running condition disengagement of starter D Delay 6 back to List of setpoints Setpoint group Engine settings Related FW 1 9 0 Range units...

Страница 207: ...p 1 of Nominal RPM page 181 Comm object 8260 Related applications AMF MRS Config level Standard Setpoint visibility Always Description Threshold for underspeed protection Relative to the nominal speed Underspeed Sd 6 back to List of setpoints Setpoint group Engine settings Related FW 1 9 0 Range units 0 50 Default value 20 Alternative config NO Step 1 of Nominal RPM page 181 Comm object 14107 Rela...

Страница 208: ...ed by analog sensor curve Alternative config NO Step the step is defined by analog sensor curve Comm object 12895 Related applications AMF MRS Config level Standard Setpoint visibility Visible only if the logical analog input OIL PRESSURE PAGE 634 is configured Description Warning or history threshold level for OIL PRESSURE PAGE 634 Oil Pressure Wrn 6 back to List of setpoints Setpoint group Engin...

Страница 209: ...ECU sensor curve Alternative config YES Step the step is defined by ECU sensor curve Comm object 14426 Related applications AMF MRS Config level Standard Setpoint visibility Visible only if ECU is configured Description Warning threshold level for Oil pressure which is send from ECU ECU Oil Pressure Wrn 6 back to List of setpoints Setpoint group Engine settings Related FW 1 9 0 Range units the ran...

Страница 210: ... Comm object 12896 Related applications AMF MRS Config level Standard Setpoint visibility Visible only if the logical analog input COOLANT TEMP PAGE 631 is configured Description Warning or history threshold level for COOLANT TEMP PAGE 631 Coolant Temperature Wrn 6 back to List of setpoints Setpoint group Engine settings Related FW 1 9 0 Range units the range is defined by analog sensor curve Defa...

Страница 211: ...ve Alternative config NO Step the step is defined by ECU sensor curve Comm object 14429 Related applications AMF MRS Config level Standard Setpoint visibility Visible only if ECU is configured Description Warning threshold level for Coolant temperature which is send from ECU ECU Coolant Temperature Wrn 6 back to List of setpoints Setpoint group Engine settings Related FW 1 9 0 Range units the rang...

Страница 212: ... Related FW 1 9 0 Range units the range is define by sensor curve analog or ECU Default value the value is defined by sensor curve analog or ECU Alternative config NO Step the step is defined by sensor curve analog or ECU Comm object 8688 Related applications AMF MRS Config level Standard Setpoint visibility Visible only if the logical binary output TEMPERATURE SWITCH PAGE 600 is configured Descri...

Страница 213: ...ry output TEMPERATURE SWITCH PAGE 600 off Note Value from analog input has higher priority than ECU Image 8 12 Temperature Switch Temperature Switch Off 6 back to List of setpoints Setpoint group Engine settings Related FW 1 9 0 Range units the range is defined by analog sensor curve Default value the value is defined by analog sensor curve Alternative config YES Step the step is defined by analog...

Страница 214: ... step is defined by analog sensor curve Comm object 12897 Related applications AMF MRS Config level Standard Setpoint visibility Visible only if the logical analog input FUEL LEVEL PAGE 632 is configured Description Warning or history threshold level for FUEL LEVEL PAGE 632 Fuel Level Wrn 6 back to List of setpoints Setpoint group Engine settings Related FW 1 9 0 Range units the range is defined b...

Страница 215: ... sensor curve Alternative config NO Step the step is defined by ECU sensor curve Comm object 14432 Related applications AMF MRS Config level Standard Setpoint visibility Visible only if ECU is configured Description Warning threshold level for Fuel level which is send from ECU ECU Fuel Level Wrn 6 back to List of setpoints Setpoint group Engine settings Related FW 1 9 0 Range units the range is de...

Страница 216: ...ted applications AMF MRS Config level Advanced Setpoint visibility Visible only if the logical analog input FUEL LEVEL PAGE 632 is or ECU is configured Description Define a capacity of gen set fuel tank Fuel Tank Volume 6 back to List of setpoints Setpoint group Engine settings Related FW 1 9 0 Range units Disabled 1 50 h Default value 25 h Alternative config NO Step 1 h Comm object 12373 Related ...

Страница 217: ... value 20 Alternative config NO Step 1 Comm object 10100 Related applications AMF MRS Config level Advanced Setpoint visibility Visible only if the logical binary output FUEL PUMP PAGE 572 is configured and logical binary input FUEL PUMP ON OFF PAGE 529 isn t configured Description Threshold level for switching the binary output FUEL PUMP PAGE 572 on Image 8 13 Fuel Pump On IMPORTANT When binary i...

Страница 218: ...UEL PUMP ON OFF PAGE 529 isn t configured Description Threshold level for switching the binary output FUEL PUMP PAGE 572 off Image 8 14 Fuel Pump Off IMPORTANT When binary input FUEL PUMP ON OFF PAGE 529 is configured then binary output FUEL PUMP PAGE 572 is control by this binary input Setpoints Fuel Pump On page 217 and Fuel Pump Off are not evaluated Note Value from analog input has higher prio...

Страница 219: ...tely inactive and it will be possible to delete this message by the Fault reset button If the fault is deleted the controller will initiate the transfer again Transfer Wrn Delay 6 back to List of setpoints Subgroup Maintenance Setpoint group Engine settings Related FW 1 9 0 Range units 10 000 9 999 h Disabled Default value 1 000 h Alternative config NO Step 1 h Comm object 11616 Related applicatio...

Страница 220: ... Disabled Default value 1 000 h Alternative config NO Step 1 h Comm object 11618 Related applications AMF MRS Config level Standard Setpoint visibility Always Description Maintenance timer 3 counts down when engine is running If reaches zero an alarm appears but the timer still counting down into negative values When the value 10000 is set than the Maintenance function is disabled and counter does...

Страница 221: ...ault value 5 s Alternative config NO Step 1 s Comm object 8383 Related applications AMF MRS Config level Standard Setpoint visibility Always Description Delay for Battery Undervoltage page 220 and Battery Overvoltage page 221 protection Battery Voltage Delay 6 back to List of setpoints Setpoint group Engine settings Related FW 1 9 0 Range units 0 15 min Default value 5 min Alternative config NO St...

Страница 222: ...Alternator Fail alarm occurred during battery recharging period current battery recharging continues until time is elapsed Next gen set start due to battery undervoltage is blocked until controller is restarted IMPORTANT If controller is in MAN mode and the battery voltage is under the limit more than 5 minutes engine is started immediately when controller is switched to AUT mode Note Low Battery ...

Страница 223: ...t the counter value Pulse Counter 2 page 470 is increased by 0 1 and input pulses counter is reset to 0 Both counter value and input pulses counter are stored in the nonvolatile memory Conversion Coefficient Pulse 2 6 back to List of setpoints Subgroup Power switch Setpoint group Engine settings Related FW 1 9 0 Range units 0 32 000 kW Default value 100 kW Alternative config NO Step 1 kW Comm obje...

Страница 224: ...0 Range units 0 32 000 kW Default value 50 kW Alternative config NO Step 1 kW Comm object 11659 Related applications AMF MRS Config level Advanced Setpoint visibility Visible only if the logical binary output POWER SWITCH PAGE 585 is configured Description Threshold level for switching the binary output POWER SWITCH PAGE 585 on Power Switch Off ...

Страница 225: ...InteliLite Global Guide 225 Image 8 17 Power Switch Level On Level Off Image 8 18 Power Switch Level On Level Off 6 back to List of setpoints ...

Страница 226: ... 600 is activated or deactivated respectively Ventilation Pulse Time 6 back to List of setpoints Subgroup ECU Settings Setpoint group Engine settings Related FW 1 9 0 Range units 0 100 Default value 50 Alternative config NO Step 1 Comm object 9948 Related applications AMF MRS Config level Advanced Setpoint visibility Visible only if ECU is configured Description Enables to adjust engine speed in E...

Страница 227: ... of setpoints Setpoint group Generator settings Related FW 1 9 0 Range units 0 Overload BOC page 227 Default value 120 Alternative config NO Step 1 of Nominal Power page 176 Comm object 9685 Related applications AMF MRS Config level Standard Setpoint visibility Always Description Threshold level for generator overload in of Nominal power protection This is only warning Overload Wrn 6 back to List ...

Страница 228: ...rs when generator current reaches this preset threshold Note When there is no control of breakers the type of protection is Sd not BOC Short Circuit BOC 6 back to List of setpoints Setpoint group Generator settings Related FW 1 9 0 Range units 0 00 10 00 s Default value 0 04 s Alternative config YES Step 0 01 s Comm object 9991 Related applications AMF MRS Config level Advanced Setpoint visibility...

Страница 229: ...inverse over current protection Reaction time is not constant but depends on over current level according to the following formula Note Reaction time is limited to 3600 s 60 minutes IDMT protection is not active for Reaction time values longer than 60 minutes Igen is maximal value of all measured phases of generator current Table 8 1 EXAMPLE of Reaction time for different over current levels Overc...

Страница 230: ...Alternative config NO Step 0 1 s Comm object 8285 Related applications AMF MRS Config level Advanced Setpoint visibility Conditioned by the setpoint Connection type page 177 Description Delay for Current Unbalance BOC page 230 protection Current Unbalance BOC Delay 6 back to List of setpoints Subgroup Voltage Protection Setpoint group Generator settings Related FW 1 9 0 Range units Generator Overv...

Страница 231: ...oltages are used for this protection Generator Overvoltage Wrn 6 back to List of setpoints Setpoint group Generator settings Related FW 1 9 0 Range units 0 Generator Undervoltage Wrn page 232 Default value 70 Alternative config NO Step 1 of Nominal Voltage Ph N page 179 or Nominal Voltage Ph Ph page 179 Comm object 8293 Related applications AMF MRS Config level Standard Setpoint visibility Always ...

Страница 232: ...0 s Default value 3 0 s Alternative config NO Step 0 1 s Comm object 9103 Related applications AMF MRS Config level Standard Setpoint visibility Always Description Delay for Generator Overvoltage Sd page 230 Generator Overvoltage Wrn page 231 Generator Undervoltage BOC page 231 and Generator Undervoltage Wrn page 232 protection Generator Voltage Delay 6 back to List of setpoints Setpoint group Gen...

Страница 233: ...ternative config NO Step 0 1 of Nominal Frequency page 180 Comm object 8296 Related applications AMF MRS Config level Standard Setpoint visibility Always Description Threshold for generator phase L1 overfrequency Note When there is no control of breakers the type of protection is Sd not BOC Generator Overfrequency BOC 6 back to List of setpoints Setpoint group Generator settings Related FW 1 9 0 R...

Страница 234: ...ge 234 Generator Overfrequency Wrn page 233 Default value 85 0 Alternative config NO Step 0 1 of Nominal Frequency page 180 Comm object 9689 Related applications AMF MRS Config level Standard Setpoint visibility Always Description Threshold for generator phase L1 underfrequency Generator Underfrequency Wrn 6 back to List of setpoints Setpoint group Generator settings Related FW 1 9 0 Range units 0...

Страница 235: ...ction is enabled or disabled by the state of LBI PROTECTION ENABLE PAGE 534 Overload Protection 6 back to List of setpoints Subgroup Current Protection Setpoint group Protections Related FW 1 9 0 Range units Enabled Disabled By LBI Default value Enabled Alternative config NO Step Comm object 15665 Related applications AMF MRS Config level Advanced Setpoint visibility Always Description This setpoi...

Страница 236: ...ate of LBI PROTECTION ENABLE PAGE 534 IDMT Overcurrent Protection 6 back to List of setpoints Setpoint group Protections Related FW 1 9 0 Range units Enabled Disabled By LBI Default value Enabled Alternative config NO Step Comm object 15667 Related applications AMF MRS Config level Advanced Setpoint visibility Always Description This setpoint adjusts the behavior of generator Current Unbalance pro...

Страница 237: ...enerator Voltage Delay page 232 Disabled Protection is disabled By LBI Protection is enabled or disabled by the state of LBI PROTECTION ENABLE PAGE 534 Generator Voltage Protection 6 back to List of setpoints Setpoint group Protections Related FW 1 9 0 Range units Enabled Disabled By LBI Default value Enabled Alternative config NO Step Comm object 15669 Related applications AMF MRS Config level Ad...

Страница 238: ...ency Wrn page 234 and Generator Frequency Delay page 234 Disabled Protection is disabled By LBI Protection is enabled or disabled by the state of LBI PROTECTION ENABLE PAGE 534 Generator Frequency Protection 6 back to List of setpoints Subgroup Speed Protection Setpoint group Protections Related FW 1 9 0 Range units Enabled Disabled By LBI Default value Enabled Alternative config NO Step Comm obje...

Страница 239: ... the state of LBI PROTECTION ENABLE PAGE 534 Overspeed Protection 6 back to List of setpoints Group Dual Operation Subgroup Dual Operation Setpoint group Dual Operation Related FW 1 9 0 Range units 0 1 1000 0 h Default value 10 h Alternative config NO Step 0 1 h Comm object 16039 Related applications AMF MRS Config level Advanced Setpoint visibility Only if relevant module is installed conditioned...

Страница 240: ...ontroller to 900 h to have both controllers on 0 running hours in dual operation Running Hours Base 6 back to List of setpoints Setpoint group Dual Operation Related FW 1 9 0 Range units Enabled Disabled Default value Enabled h Alternative config NO Step Comm object 16041 Related applications AMF MRS Config level Advanced Setpoint visibility Only if relevant module is installed conditioned by the ...

Страница 241: ...Advanced Setpoint visibility Only if relevant module is installed conditioned by the setpoint COM1 Mode page 343 and COM2 Mode page 345 Description This setpoint adjust the type of protection for Dual Operation Slave Fail page 665 alarm Slave Error Protection 6 back to List of setpoints Setpoint group Dual Operation Related FW 1 9 0 Range units 0 0 600 0 s Default value 1 0 s Alternative config NO...

Страница 242: ...T01 PAGE 604 is adjusted to required protection type Otherwise these setpoints are useless Analog Protection 1 Wrn 6 back to List of setpoints Setpoint group General Analog Inputs Related FW 1 9 0 Range units the range is defined by analog sensor curve Default value the value is defined by analog sensor curve Alternative config NO Step the step is defined by analog sensor curve Comm object 9260 Re...

Страница 243: ...s Analog Protection 1 Delay 6 back to List of setpoints Setpoint group General Analog Inputs Related FW 1 9 0 Range units the range is defined by analog sensor curve Default value the value is defined by analog sensor curve Alternative config NO Step the step is defined by analog sensor curve Comm object 11407 Related applications AMF MRS Config level Standard Setpoint visibility Visible only if t...

Страница 244: ...put Image 8 21 General analog input 1 switch Analog Switch 1 Off 6 back to List of setpoints General Analog Input 2 Setpoint group General Analog Inputs Related FW 1 9 0 Range units the range is defined by analog sensor curve Default value the value is defined by analog sensor curve Alternative config NO Step the step is defined by analog sensor curve Comm object 9262 Related applications AMF MRS ...

Страница 245: ...ese setpoints are used only if LAI AIN PROT02 PAGE 605 is adjusted to required protection type Otherwise these setpoints are useless Analog Protection 2 Sd 6 back to List of setpoints Setpoint group General Analog Inputs Related FW 1 9 0 Range units 0 900 s Default value 0 s Alternative config NO Step 1 s Comm object 9264 Related applications AMF MRS Config level Standard Setpoint visibility Visib...

Страница 246: ... defined by analog sensor curve Comm object 11408 Related applications AMF MRS Config level Standard Setpoint visibility Visible only if the logical binary output AIN SWITCH02 PAGE 553 is configured Description Threshold level for switching the binary output AIN SWITCH 02 PAGE 624 on The value is measured from AIN SWITCH 02 PAGE 624 analog input Image 8 22 General analog input 2 switch Analog Swit...

Страница 247: ...nput Image 8 23 General analog input 2 switch Analog Switch 2 Off 6 back to List of setpoints General Analog Input 3 Setpoint group General Analog Inputs Related FW 1 9 0 Range units the range is defined by analog sensor curve Default value the value is defined by analog sensor curve Alternative config NO Step the step is defined by analog sensor curve Comm object 9265 Related applications AMF MRS...

Страница 248: ...ese setpoints are used only if LAI AIN PROT03 PAGE 606 is adjusted to required protection type Otherwise these setpoints are useless Analog Protection 3 Sd 6 back to List of setpoints Setpoint group General Analog Inputs Related FW 1 9 0 Range units 0 900 s Default value 0 s Alternative config NO Step 1 s Comm object 9267 Related applications AMF MRS Config level Standard Setpoint visibility Visib...

Страница 249: ... defined by analog sensor curve Comm object 11409 Related applications AMF MRS Config level Standard Setpoint visibility Visible only if the logical binary output AIN SWITCH03 PAGE 554 is configured Description Threshold level for switching the binary output AIN SWITCH 03 PAGE 624 on The value is measured from AIN SWITCH 03 PAGE 624 analog input Image 8 24 General analog input 3 switch Analog Swit...

Страница 250: ...nput Image 8 25 General analog input 3 switch Analog Switch 3 Off 6 back to List of setpoints General Analog Input 4 Setpoint group General Analog Inputs Related FW 1 9 0 Range units the range is defined by analog sensor curve Default value the value is defined by analog sensor curve Alternative config NO Step the step is defined by analog sensor curve Comm object 9268 Related applications AMF MRS...

Страница 251: ...ese setpoints are used only if LAI AIN PROT04 PAGE 607 is adjusted to required protection type Otherwise these setpoints are useless Analog Protection 4 Sd 6 back to List of setpoints Setpoint group General Analog Inputs Related FW 1 9 0 Range units 0 900 s Default value 0 s Alternative config NO Step 1 s Comm object 9270 Related applications AMF MRS Config level Standard Setpoint visibility Visib...

Страница 252: ... defined by analog sensor curve Comm object 14385 Related applications AMF MRS Config level Standard Setpoint visibility Visible only if the logical binary output AIN SWITCH04 PAGE 554 is configured Description Threshold level for switching the binary output AIN SWITCH 04 PAGE 625 on The value is measured from AIN SWITCH 04 PAGE 625 analog input Image 8 26 General analog input 4 switch Analog Swit...

Страница 253: ...nput Image 8 27 General analog input 4 switch Analog Switch 4 Off 6 back to List of setpoints General Analog Input 5 Setpoint group General Analog Inputs Related FW 1 9 0 Range units the range is defined by analog sensor curve Default value the value is defined by analog sensor curve Alternative config NO Step the step is defined by analog sensor curve Comm object 9271 Related applications AMF MRS...

Страница 254: ...ese setpoints are used only if LAI AIN PROT05 PAGE 608 is adjusted to required protection type Otherwise these setpoints are useless Analog Protection 5 Sd 6 back to List of setpoints Setpoint group General Analog Inputs Related FW 1 9 0 Range units 0 900 s Default value 0 s Alternative config NO Step 1 s Comm object 9273 Related applications AMF MRS Config level Standard Setpoint visibility Visib...

Страница 255: ... defined by analog sensor curve Comm object 14963 Related applications AMF MRS Config level Standard Setpoint visibility Visible only if the logical binary output AIN SWITCH04 PAGE 554 is configured Description Threshold level for switching the binary output AIN SWITCH 05 PAGE 625 on The value is measured from AIN SWITCH 05 PAGE 625 analog input Image 8 28 General analog input 4 switch Analog Swit...

Страница 256: ...nput Image 8 29 General analog input 4 switch Analog Switch 5 Off 6 back to List of setpoints General Analog Input 6 Setpoint group General Analog Inputs Related FW 1 9 0 Range units the range is defined by analog sensor curve Default value the value is defined by analog sensor curve Alternative config NO Step the step is defined by analog sensor curve Comm object 9274 Related applications AMF MRS...

Страница 257: ...ese setpoints are used only if LAI AIN PROT06 PAGE 609 is adjusted to required protection type Otherwise these setpoints are useless Analog Protection 6 Sd 6 back to List of setpoints Setpoint group General Analog Inputs Related FW 1 9 0 Range units 0 900 s Default value 0 s Alternative config NO Step 1 s Comm object 9276 Related applications AMF MRS Config level Standard Setpoint visibility Visib...

Страница 258: ... defined by analog sensor curve Comm object 14964 Related applications AMF MRS Config level Standard Setpoint visibility Visible only if the logical binary output AIN SWITCH04 PAGE 554 is configured Description Threshold level for switching the binary output AIN SWITCH 06 PAGE 625 on The value is measured from AIN SWITCH 04 PAGE 625 analog input Image 8 30 General analog input 4 switch Analog Swit...

Страница 259: ...nput Image 8 31 General analog input 4 switch Analog Switch 6 Off 6 back to List of setpoints General Analog Input 7 Setpoint group General Analog Inputs Related FW 1 9 0 Range units the range is defined by analog sensor curve Default value the value is defined by analog sensor curve Alternative config NO Step the step is defined by analog sensor curve Comm object 9277 Related applications AMF MRS...

Страница 260: ...ese setpoints are used only if LAI AIN PROT07 PAGE 610 is adjusted to required protection type Otherwise these setpoints are useless Analog Protection 7 Sd 6 back to List of setpoints Setpoint group General Analog Inputs Related FW 1 9 0 Range units 0 900 s Default value 0 s Alternative config NO Step 1 s Comm object 9279 Related applications AMF MRS Config level Standard Setpoint visibility Visib...

Страница 261: ... defined by analog sensor curve Comm object 14965 Related applications AMF MRS Config level Standard Setpoint visibility Visible only if the logical binary output AIN SWITCH04 PAGE 554 is configured Description Threshold level for switching the binary output AIN SWITCH 07 PAGE 626 on The value is measured from AIN SWITCH 04 PAGE 625 analog input Image 8 32 General analog input 4 switch Analog Swit...

Страница 262: ...nput Image 8 33 General analog input 4 switch Analog Switch 7 Off 6 back to List of setpoints General Analog Input 8 Setpoint group General Analog Inputs Related FW 1 9 0 Range units the range is defined by analog sensor curve Default value the value is defined by analog sensor curve Alternative config NO Step the step is defined by analog sensor curve Comm object 9280 Related applications AMF MRS...

Страница 263: ...ese setpoints are used only if LAI AIN PROT08 PAGE 611 is adjusted to required protection type Otherwise these setpoints are useless Analog Protection 8 Sd 6 back to List of setpoints Setpoint group General Analog Inputs Related FW 1 9 0 Range units 0 900 s Default value 0 s Alternative config NO Step 1 s Comm object 9282 Related applications AMF MRS Config level Standard Setpoint visibility Visib...

Страница 264: ... defined by analog sensor curve Comm object 14966 Related applications AMF MRS Config level Standard Setpoint visibility Visible only if the logical binary output AIN SWITCH04 PAGE 554 is configured Description Threshold level for switching the binary output AIN SWITCH 08 PAGE 626 on The value is measured from AIN SWITCH 04 PAGE 625 analog input Image 8 34 General analog input 4 switch Analog Swit...

Страница 265: ...nput Image 8 35 General analog input 4 switch Analog Switch 8 Off 6 back to List of setpoints General Analog Input 9 Setpoint group General Analog Inputs Related FW 1 9 0 Range units the range is defined by analog sensor curve Default value the value is defined by analog sensor curve Alternative config NO Step the step is defined by analog sensor curve Comm object 9283 Related applications AMF MRS...

Страница 266: ...ese setpoints are used only if LAI AIN PROT09 PAGE 612 is adjusted to required protection type Otherwise these setpoints are useless Analog Protection 9 Sd 6 back to List of setpoints Setpoint group General Analog Inputs Related FW 1 9 0 Range units 0 900 s Default value 0 s Alternative config NO Step 1 s Comm object 9285 Related applications AMF MRS Config level Standard Setpoint visibility Visib...

Страница 267: ... defined by analog sensor curve Comm object 14967 Related applications AMF MRS Config level Standard Setpoint visibility Visible only if the logical binary output AIN SWITCH04 PAGE 554 is configured Description Threshold level for switching the binary output AIN SWITCH 09 PAGE 626 on The value is measured from AIN SWITCH 04 PAGE 625 analog input Image 8 36 General analog input 4 switch Analog Swit...

Страница 268: ...put Image 8 37 General analog input 4 switch Analog Switch 9 Off 6 back to List of setpoints General Analog Input 10 Setpoint group General Analog Inputs Related FW 1 9 0 Range units the range is defined by analog sensor curve Default value the value is defined by analog sensor curve Alternative config NO Step the step is defined by analog sensor curve Comm object 9286 Related applications AMF MRS...

Страница 269: ...se setpoints are used only if LAI AIN PROT10 PAGE 613 is adjusted to required protection type Otherwise these setpoints are useless Analog Protection 10 Sd 6 back to List of setpoints Setpoint group General Analog Inputs Related FW 1 9 0 Range units 0 900 s Default value 0 s Alternative config NO Step 1 s Comm object 9288 Related applications AMF MRS Config level Standard Setpoint visibility Visib...

Страница 270: ... defined by analog sensor curve Comm object 14968 Related applications AMF MRS Config level Standard Setpoint visibility Visible only if the logical binary output AIN SWITCH04 PAGE 554 is configured Description Threshold level for switching the binary output AIN SWITCH 10 PAGE 627 on The value is measured from AIN SWITCH 04 PAGE 625 analog input Image 8 38 General analog input 4 switch Analog Swit...

Страница 271: ...ut Image 8 39 General analog input 4 switch Analog Switch 10 Off 6 back to List of setpoints General Analog Input 11 Setpoint group General Analog Inputs Related FW 1 9 0 Range units the range is defined by analog sensor curve Default value the value is defined by analog sensor curve Alternative config NO Step the step is defined by analog sensor curve Comm object 9289 Related applications AMF MRS...

Страница 272: ...se setpoints are used only if LAI AIN PROT11 PAGE 614 is adjusted to required protection type Otherwise these setpoints are useless Analog Protection 11 Sd 6 back to List of setpoints Setpoint group General Analog Inputs Related FW 1 9 0 Range units 0 900 s Default value 0 s Alternative config NO Step 1 s Comm object 9291 Related applications AMF MRS Config level Standard Setpoint visibility Visib...

Страница 273: ... defined by analog sensor curve Comm object 14969 Related applications AMF MRS Config level Standard Setpoint visibility Visible only if the logical binary output AIN SWITCH04 PAGE 554 is configured Description Threshold level for switching the binary output AIN SWITCH 11 PAGE 627 on The value is measured from AIN SWITCH 04 PAGE 625 analog input Image 8 40 General analog input 4 switch Analog Swit...

Страница 274: ...ut Image 8 41 General analog input 4 switch Analog Switch 11 Off 6 back to List of setpoints General Analog Input 12 Setpoint group General Analog Inputs Related FW 1 9 0 Range units the range is defined by analog sensor curve Default value the value is defined by analog sensor curve Alternative config NO Step the step is defined by analog sensor curve Comm object 9292 Related applications AMF MRS...

Страница 275: ...se setpoints are used only if LAI AIN PROT12 PAGE 615 is adjusted to required protection type Otherwise these setpoints are useless Analog Protection 12 Sd 6 back to List of setpoints Setpoint group General Analog Inputs Related FW 1 9 0 Range units 0 900 s Default value 0 s Alternative config NO Step 1 s Comm object 9294 Related applications AMF MRS Config level Standard Setpoint visibility Visib...

Страница 276: ... defined by analog sensor curve Comm object 14970 Related applications AMF MRS Config level Standard Setpoint visibility Visible only if the logical binary output AIN SWITCH04 PAGE 554 is configured Description Threshold level for switching the binary output AIN SWITCH 12 PAGE 627 on The value is measured from AIN SWITCH 04 PAGE 625 analog input Image 8 42 General analog input 4 switch Analog Swit...

Страница 277: ...ut Image 8 43 General analog input 4 switch Analog Switch 12 Off 6 back to List of setpoints General Analog Input 13 Setpoint group General Analog Inputs Related FW 1 9 0 Range units the range is defined by analog sensor curve Default value the value is defined by analog sensor curve Alternative config NO Step the step is defined by analog sensor curve Comm object 9295 Related applications AMF MRS...

Страница 278: ...se setpoints are used only if LAI AIN PROT13 PAGE 616 is adjusted to required protection type Otherwise these setpoints are useless Analog Protection 13 Sd 6 back to List of setpoints Setpoint group General Analog Inputs Related FW 1 9 0 Range units 0 900 s Default value 0 s Alternative config NO Step 1 s Comm object 9297 Related applications AMF MRS Config level Standard Setpoint visibility Visib...

Страница 279: ... defined by analog sensor curve Comm object 14971 Related applications AMF MRS Config level Standard Setpoint visibility Visible only if the logical binary output AIN SWITCH04 PAGE 554 is configured Description Threshold level for switching the binary output AIN SWITCH 13 PAGE 628 on The value is measured from AIN SWITCH 04 PAGE 625 analog input Image 8 44 General analog input 4 switch Analog Swit...

Страница 280: ...ut Image 8 45 General analog input 4 switch Analog Switch 13 Off 6 back to List of setpoints General Analog Input 14 Setpoint group General Analog Inputs Related FW 1 9 0 Range units the range is defined by analog sensor curve Default value the value is defined by analog sensor curve Alternative config NO Step the step is defined by analog sensor curve Comm object 9298 Related applications AMF MRS...

Страница 281: ...se setpoints are used only if LAI AIN PROT14 PAGE 617 is adjusted to required protection type Otherwise these setpoints are useless Analog Protection 14 Sd 6 back to List of setpoints Setpoint group General Analog Inputs Related FW 1 9 0 Range units 0 900 s Default value 0 s Alternative config NO Step 1 s Comm object 9300 Related applications AMF MRS Config level Standard Setpoint visibility Visib...

Страница 282: ... defined by analog sensor curve Comm object 14972 Related applications AMF MRS Config level Standard Setpoint visibility Visible only if the logical binary output AIN SWITCH04 PAGE 554 is configured Description Threshold level for switching the binary output AIN SWITCH 14 PAGE 628 on The value is measured from AIN SWITCH 04 PAGE 625 analog input Image 8 46 General analog input 4 switch Analog Swit...

Страница 283: ...ut Image 8 47 General analog input 4 switch Analog Switch 14 Off 6 back to List of setpoints General Analog Input 15 Setpoint group General Analog Inputs Related FW 1 9 0 Range units the range is defined by analog sensor curve Default value the value is defined by analog sensor curve Alternative config NO Step the step is defined by analog sensor curve Comm object 9301 Related applications AMF MRS...

Страница 284: ...se setpoints are used only if LAI AIN PROT15 PAGE 618 is adjusted to required protection type Otherwise these setpoints are useless Analog Protection 15 Sd 6 back to List of setpoints Setpoint group General Analog Inputs Related FW 1 9 0 Range units 0 900 s Default value 0 s Alternative config NO Step 1 s Comm object 9303 Related applications AMF MRS Config level Standard Setpoint visibility Visib...

Страница 285: ... defined by analog sensor curve Comm object 14973 Related applications AMF MRS Config level Standard Setpoint visibility Visible only if the logical binary output AIN SWITCH04 PAGE 554 is configured Description Threshold level for switching the binary output AIN SWITCH 15 PAGE 628 on The value is measured from AIN SWITCH 04 PAGE 625 analog input Image 8 48 General analog input 4 switch Analog Swit...

Страница 286: ...ut Image 8 49 General analog input 4 switch Analog Switch 15 Off 6 back to List of setpoints General Analog Input 16 Setpoint group General Analog Inputs Related FW 1 9 0 Range units the range is defined by analog sensor curve Default value the value is defined by analog sensor curve Alternative config NO Step the step is defined by analog sensor curve Comm object 9304 Related applications AMF MRS...

Страница 287: ...se setpoints are used only if LAI AIN PROT16 PAGE 619 is adjusted to required protection type Otherwise these setpoints are useless Analog Protection 16 Sd 6 back to List of setpoints Setpoint group General Analog Inputs Related FW 1 9 0 Range units 0 900 s Default value 0 s Alternative config NO Step 1 s Comm object 9306 Related applications AMF MRS Config level Standard Setpoint visibility Visib...

Страница 288: ... defined by analog sensor curve Comm object 14974 Related applications AMF MRS Config level Standard Setpoint visibility Visible only if the logical binary output AIN SWITCH04 PAGE 554 is configured Description Threshold level for switching the binary output AIN SWITCH 16 PAGE 629 on The value is measured from AIN SWITCH 04 PAGE 625 analog input Image 8 50 General analog input 4 switch Analog Swit...

Страница 289: ...ut Image 8 51 General analog input 4 switch Analog Switch 16 Off 6 back to List of setpoints General Analog Input 17 Setpoint group General Analog Inputs Related FW 1 9 0 Range units the range is defined by analog sensor curve Default value the value is defined by analog sensor curve Alternative config NO Step the step is defined by analog sensor curve Comm object 9307 Related applications AMF MRS...

Страница 290: ...se setpoints are used only if LAI AIN PROT17 PAGE 620 is adjusted to required protection type Otherwise these setpoints are useless Analog Protection 17 Sd 6 back to List of setpoints Setpoint group General Analog Inputs Related FW 1 9 0 Range units 0 900 s Default value 0 s Alternative config NO Step 1 s Comm object 9309 Related applications AMF MRS Config level Standard Setpoint visibility Visib...

Страница 291: ... defined by analog sensor curve Comm object 14975 Related applications AMF MRS Config level Standard Setpoint visibility Visible only if the logical binary output AIN SWITCH04 PAGE 554 is configured Description Threshold level for switching the binary output AIN SWITCH 17 PAGE 629 on The value is measured from AIN SWITCH 04 PAGE 625 analog input Image 8 52 General analog input 4 switch Analog Swit...

Страница 292: ...ut Image 8 53 General analog input 4 switch Analog Switch 17 Off 6 back to List of setpoints General Analog Input 18 Setpoint group General Analog Inputs Related FW 1 9 0 Range units the range is defined by analog sensor curve Default value the value is defined by analog sensor curve Alternative config NO Step the step is defined by analog sensor curve Comm object 9310 Related applications AMF MRS...

Страница 293: ...se setpoints are used only if LAI AIN PROT18 PAGE 621 is adjusted to required protection type Otherwise these setpoints are useless Analog Protection 18 Sd 6 back to List of setpoints Setpoint group General Analog Inputs Related FW 1 9 0 Range units 0 900 s Default value 0 s Alternative config NO Step 1 s Comm object 9312 Related applications AMF MRS Config level Standard Setpoint visibility Visib...

Страница 294: ... defined by analog sensor curve Comm object 14976 Related applications AMF MRS Config level Standard Setpoint visibility Visible only if the logical binary output AIN SWITCH04 PAGE 554 is configured Description Threshold level for switching the binary output AIN SWITCH 18 PAGE 629 on The value is measured from AIN SWITCH 04 PAGE 625 analog input Image 8 54 General analog input 4 switch Analog Swit...

Страница 295: ...ut Image 8 55 General analog input 4 switch Analog Switch 18 Off 6 back to List of setpoints General Analog Input 19 Setpoint group General Analog Inputs Related FW 1 9 0 Range units the range is defined by analog sensor curve Default value the value is defined by analog sensor curve Alternative config NO Step the step is defined by analog sensor curve Comm object 9313 Related applications AMF MRS...

Страница 296: ...se setpoints are used only if LAI AIN PROT19 PAGE 622 is adjusted to required protection type Otherwise these setpoints are useless Analog Protection 19 Sd 6 back to List of setpoints Setpoint group General Analog Inputs Related FW 1 9 0 Range units 0 900 s Default value 0 s Alternative config NO Step 1 s Comm object 9315 Related applications AMF MRS Config level Standard Setpoint visibility Visib...

Страница 297: ... defined by analog sensor curve Comm object 14977 Related applications AMF MRS Config level Standard Setpoint visibility Visible only if the logical binary output AIN SWITCH04 PAGE 554 is configured Description Threshold level for switching the binary output AIN SWITCH 19 PAGE 630 on The value is measured from AIN SWITCH 04 PAGE 625 analog input Image 8 56 General analog input 4 switch Analog Swit...

Страница 298: ...ut Image 8 57 General analog input 4 switch Analog Switch 19 Off 6 back to List of setpoints General Analog Input 20 Setpoint group General Analog Inputs Related FW 1 9 0 Range units the range is defined by analog sensor curve Default value the value is defined by analog sensor curve Alternative config NO Step the step is defined by analog sensor curve Comm object 9316 Related applications AMF MRS...

Страница 299: ...se setpoints are used only if LAI AIN PROT20 PAGE 623 is adjusted to required protection type Otherwise these setpoints are useless Analog Protection 20 Sd 6 back to List of setpoints Setpoint group General Analog Inputs Related FW 1 9 0 Range units 0 900 s Default value 0 s Alternative config NO Step 1 s Comm object 9318 Related applications AMF MRS Config level Standard Setpoint visibility Visib...

Страница 300: ... defined by analog sensor curve Comm object 14978 Related applications AMF MRS Config level Standard Setpoint visibility Visible only if the logical binary output AIN SWITCH04 PAGE 554 is configured Description Threshold level for switching the binary output AIN SWITCH 20 PAGE 630 on The value is measured from AIN SWITCH 04 PAGE 625 analog input Image 8 58 General analog input 4 switch Analog Swit...

Страница 301: ...tput AIN SWITCH04 PAGE 554 is configured Description Threshold level for switching the binary output AIN SWITCH 20 PAGE 630 off The value is measured from AIN SWITCH 04 PAGE 625 analog input Image 8 59 General analog input 4 switch Analog Switch 20 Off 6 back to List of setpoints Group Scheduler Subgroup Time Date Setpoint group Scheduler Related FW 1 9 0 Range units HH MM SS Default value 0 0 0 A...

Страница 302: ... Time interval for periodic history records Note History record is made only when engine is running Time Stamp Period 6 back to List of setpoints Setpoint group Scheduler Related FW 1 9 0 Range units Disabled Winter Summer Winter S Summer S Default value Disabled Alternative config NO Step Comm object 8727 Related applications AMF MRS Config level Advanced Setpoint visibility Always Description Be...

Страница 303: ...1 has higher priority over Timer 2 So if Timer 1 Function page 303 is configured for OFF mode and Timer 2 Function page 310 is over the same time configured for AUTO mode controller will work in OFF mode Controller activates timer whenever it is powered up even in period where timer should be already running Disable The Timer is disabled No Func There is no any other function only binary output of...

Страница 304: ...e 309 Timer 1 Repeat Day In Month page 309 Timer 1 Repeat Week In Month page 310 Timer 1 Refresh Period page 307 Timer 1 Weekends page 308 Timer 1 Setup 6 back to List of setpoints Setpoint group Scheduler Related FW 1 9 0 Range units Off Once Repeated Default value Off Alternative config NO Step Comm object 0 Related applications AMF MRS Config level Standard Setpoint visibility Conditioned by th...

Страница 305: ...ts HH MM Default value 00 00 Alternative config NO Step Comm object 0 Related applications AMF MRS Config level Standard Setpoint visibility Conditioned by the setpoint Timer 1 Function page 303 Description Time of first occurrence of Timer 1 Function page 303 Timer 1 First Occur Time 6 back to List of setpoints Setpoint group Scheduler Related FW 1 9 0 Range units HH MM Default value 00 00 Altern...

Страница 306: ...ned by the setpoint Timer 1 Function page 303 Description Repeated interval of Timer 1 Function page 303 Daily Timer 1 Function page 303 is repeated every day Weekly Timer 1 Function page 303 is repeated every week in chosen days Monthly Timer 1 Function page 303 is repeated in chosen day every month or in chosen days of chosen week of month Short Period Timer 1 Function page 303 is repeated in ad...

Страница 307: ... you set this setpoint to 2 then every second week from first occurrence of Timer 1 Function page 303 the Timer 1 Function page 303 will be activated in selected days adjusted by Timer 1 Day page 308 Monthly Range units 1 12 month This setpoint adjust that every X month the timer will be activated Example If you have monthly repetition and you set this setpoint to 2 then every second month from fi...

Страница 308: ...ge 303 counter isn t running on the weekends and Timer 1 Function page 303 isn t active If the activation of timer is counted on the weekend than timer will be activated after weekend Another activation of timer is counted from original date of first occurrence date Timer 1 Weekends 6 back to List of setpoints Setpoint group Scheduler Related FW 1 9 0 Range units Monday Tuesday Wednesday Thursday ...

Страница 309: ... Monday Tuesday Wednesday Thursday Friday Saturday Sunday Default value All OFF Alternative config NO Step Comm object 0 Related applications AMF MRS Config level Standard Setpoint visibility Conditioned by the setpoint Timer 1 Function page 303 Description Use this setpoint to select the day of week when timer will be activated Note More day can be selected Timer will be activated on the day whic...

Страница 310: ... from following Timer functions Binary output EXERCISE TIMER 2 PAGE 571 is always activated when Timer is active regardless of chosen timer function Timer functions require controller running in AUTO mode Timer 1 has higher priority over Timer 2 So if Timer 1 Function page 303 is configured for OFF mode and Timer 2 Function page 310 is over the same time configured for AUTO mode controller will wo...

Страница 311: ... 316 Timer 2 Repeat Day In Month page 316 Timer 2 Repeat Week In Month page 317 Timer 2 Refresh Period page 314 Timer 2 Weekends page 315 Timer 2 Setup 6 back to List of setpoints Setpoint group Scheduler Related FW 1 9 0 Range units Off Once Repeated Default value Off Alternative config NO Step Comm object 0 Related applications AMF MRS Config level Standard Setpoint visibility Conditioned by the...

Страница 312: ...s HH MM Default value 00 00 Alternative config NO Step Comm object 0 Related applications AMF MRS Config level Standard Setpoint visibility Conditioned by the setpoint Timer 2 Function page 310 Description Time of first occurrence of Timer 2 Function page 310 Timer 2 First Occur Time 6 back to List of setpoints Setpoint group Scheduler Related FW 1 9 0 Range units HH MM Default value 00 00 Alterna...

Страница 313: ...ed by the setpoint Timer 2 Function page 310 Description Repeated interval of Timer 2 Function page 310 Daily Timer 2 Function page 310 is repeated every day Weekly Timer 2 Function page 310 is repeated every week in chosen days Monthly Timer 2 Function page 310 is repeated in chosen day every month or in chosen days of chosen week of month Short Period Timer 2 Function page 310 is repeated in adj...

Страница 314: ... you set this setpoint to 2 then every second week from first occurrence of Timer 2 Function page 310 the Timer 2 Function page 310 will be activated in selected days adjusted by Timer 2 Day page 315 Monthly Range units 1 12 month This setpoint adjust that every X month the timer will be activated Example If you have monthly repetition and you set this setpoint to 2 then every second month from fi...

Страница 315: ...ge 310 counter isn t running on the weekends and Timer 2 Function page 310 isn t active If the activation of timer is counted on the weekend than timer will be activated after weekend Another activation of timer is counted from original date of first occurrence date Timer 2 Weekends 6 back to List of setpoints Setpoint group Scheduler Related FW 1 9 0 Range units Monday Tuesday Wednesday Thursday ...

Страница 316: ... Monday Tuesday Wednesday Thursday Friday Saturday Sunday Default value All OFF Alternative config NO Step Comm object 0 Related applications AMF MRS Config level Standard Setpoint visibility Conditioned by the setpoint Timer 2 Function page 310 Description Use this setpoint to select the day of week when timer will be activated Note More day can be selected Timer will be activated on the day whic...

Страница 317: ...AMF MRS Config level Advanced Setpoint visibility Always Description Another engine start is not allowed when this timer elapsed This timer is based on engine running hours The alarm Rental Timer 1 Elapsed page 654 will be recorded in alarm list and the binary output AL RENTAL TIMER 1 PAGE 551 will close IMPORTANT To reset Rental Timer 1 page 317 we have to set up Rental Timer 1 page 317 again It ...

Страница 318: ...un counter will start increment when the engine is continue running after the Rental Timer 1 page 317 elapsed Note There is no priority between Rental Timer 1 and Rental Timer 2 The sooner timer will activated the Rental Timer BOC page 321 protection 6 back to List of setpoints ...

Страница 319: ...0 Range units DD MM YYYY Default value 01 01 2015 Alternative config NO Step 1 day Comm object 14367 Related applications AMF MRS Config level Advanced Setpoint visibility Always Description Another engine start is not allowed when this timer elapsed This timer is based on date At the midnight of the last day the alarm Rental Timer 2 Elapsed page 654 will be recorded in alarm list and the binary o...

Страница 320: ...ine will be cooled and stopped when the Rental Timer BOC page 321 time elapsed Image 8 62 Rental Timer 2 The Running Hours Overrun counter will start increment when the engine is continue running after the Rental Timer 2 page 319 elapsed Note There is no priority between Rental Timer 1 and Rental Timer 2 The sooner timer will activated the Rental Timer BOC page 321 protection 6 back to List of set...

Страница 321: ... are adjusted by this setpoint Image 8 63 Rental Timer 2 Wrn Rental Timer 2 Wrn 6 back to List of setpoints Setpoint group Scheduler Related FW 1 9 0 Range units Disabled 1 210 h Default value 24 h Alternative config NO Step 1 h Comm object 14334 Related applications AMF MRS Config level Advanced Setpoint visibility Conditioned by the setpoints Rental Timer 1 page 317 and Rental Timer 2 page 319 D...

Страница 322: ...s setpoint will be adjusted automatically from actual coordinates from GPS signal Home Latitude 6 back to List of setpoints Setpoint group Geo Fencing Related FW 1 9 0 Range units 180 0000 180 0000 Default value 0 0000 Alternative config NO Step 0 0001 Comm object 14607 Related applications AMF MRS Config level Standard Setpoint visibility Only if relevant module is installed Description This setp...

Страница 323: ...nits 0 0 99 9 km Default value 0 0 km Alternative config NO Step 0 1 km Comm object 14608 Related applications AMF MRS Config level Standard Setpoint visibility Only if relevant module is installed Description Radius for circle area 2 When the gen set leaves this area Fence 2 Protection page 326 is activated after Fence 2 Delay page 324 Note The center of this circle area is defined by Home positi...

Страница 324: ...bled Enabled LBI Enable Default value Disabled Alternative config NO Step Comm object 11681 Related applications AMF MRS Config level Standard Setpoint visibility Only if relevant module is installed Description This setpoint enables or disables geo fencing function Disabled Fence 1 Protection page 325 and Fence 2 Protection page 326 are disabled Enabled Fence 1 Protection page 325 and Fence 2 Pro...

Страница 325: ...nd displayed on the LCD screen but not used for protection History record is made if position is out of Fence Radius 1 page 323 Wrn Position of gen set is used for warning protection only Protection is activated when position of the gen set is out of Fence Radius 1 page 323 Sd Position of gen set is used for shutdown protection Protection is activated when position of the gen set is out of Fence R...

Страница 326: ...g protection only Protection is activated when position of the gen set is out of Fence Radius 2 page 323 Sd Position of gen set is used for shutdown protection Protection is activated when position of the gen set is out of Fence Radius 2 page 323 BOC Position of gen set is used for BOC Breaker Open and Cooling protection Protection is activated when position of the gen set is out of Fence Radius 2...

Страница 327: ...oup CU AIN Calibration Related FW 1 9 0 Range units the range is defined by analog sensor curve Default value 0 number of decimal is given by sensor curve Alternative config NO Step the step is defined by analog sensor curve Comm object 8431 Related applications AMF MRS Config level Standard Setpoint visibility Always Description Calibrating constant to adjust the measured value of controller anal...

Страница 328: ...it is adjusted via InteliConfig in configuration of analog input 2 CU AIN2 Calibration 6 back to List of setpoints Subgroup Analog Input 3 Setpoint group CU AIN Calibration Related FW 1 9 0 Range units the range is defined by analog sensor curve Default value 0 number of decimal is given by sensor curve Alternative config NO Step the step is defined by analog sensor curve Comm object 8467 Related ...

Страница 329: ...a InteliConfig in configuration of analog input 4 CU AIN4 Calibration 6 back to List of setpoints Group Alternate Config Subgroup Basic settings Setpoint group Basic settings Related FW 1 9 0 Range units Mono Phase SplPhL1L2 SplPhL1L3 3Ph3Wire 3Ph4Wire High Leg D Autodetect Default value 3Ph4Wire Alternative config YES Step Comm object 12058 Related applications AMF MRS Config level Standard Setpo...

Страница 330: ... Delta Split Phase Delta Three phase voltage measurement L1 L2 L3 with 120 phase shift No neutral is available 3x CT Current Transformer High Leg D High Leg Delta connection Three phase voltage measurement L1 L2 L3 3x CT Current Transformer Autodetect High Leg Delta or L1 100V L1 140V L2 140V L3 100V L3 140V 3PH3Wire or 3Ph4Wire or L1 100V L2 100V L3 100V SplPhL1L2 or L1 100V L2 100V L3 20V SplPhL...

Страница 331: ...ings Related FW 1 9 0 Range units 45 65 Hz Default value 50 Hz Alternative config YES Step 1 Hz Comm object 9913 Related applications AMF MRS Config level Standard Setpoint visibility Always Description Nominal system frequency usually 50 or 60 Hz Note This value is used when any other alternate configuration is not active Nominal Frequency 1 6 back to List of setpoints Setpoint group Basic settin...

Страница 332: ...lue is used when any other alternate configuration is not active Nominal Voltage Ph N 1 6 back to List of setpoints Setpoint group Basic settings Related FW 1 9 0 Range units 80 40000 V Default value 400 V Alternative config YES Step 1 V Comm object 12055 Related applications AMF MRS Config level Standard Setpoint visibility Conditioned by the setpoint Connection Type 1 page 329 Description Nomina...

Страница 333: ... 1 9 0 Range units 1 5 000 kW Default value 200 kW Alternative config Yes Step 1 kW Comm object 15771 Related applications AMF MRS Config level Standard Setpoint visibility Conditioned by the setpoint Connection type page 177 Description Nominal power of the gen set for detected split phase or mono phase connection Generator Overload BOC page 227 protection is based on this setpoint Note This setp...

Страница 334: ...hase voltage measurement L1 L3 with 180 phase shift 2x CT Current Transformer 3Ph4Wire Grounded Star Grounded Wye connection 3PY Three phase voltage measurement L1 L2 L3 with 120 phase shift 3x CT Current Transformer 3Ph3Wire Ungrounded Delta connection Open Delta Ungrounded Wye Corner Grounded Delta Split Phase Delta Three phase voltage measurement L1 L2 L3 with 120 phase shift No neutral is avai...

Страница 335: ... current limit for generator current protections and means maximal continuous generator current Nominal Current can be different from generator rated current value Note This value is used when binary input ALTERNATE CONFIG 2 PAGE 499 is active Nominal Current 2 6 back to List of setpoints Setpoint group Basic settings Related FW 1 9 0 Range units 45 65 Hz Default value 50 Hz Alternative config YES...

Страница 336: ...ect 12053 Related applications AMF MRS Config level Standard Setpoint visibility Conditioned by the setpoint Connection type 2 page 333 Description Nominal system voltage phase to neutral Note This value is used when binary input ALTERNATE CONFIG 2 PAGE 499 is active Nominal Voltage Ph N 2 6 back to List of setpoints Setpoint group Basic settings Related FW 1 9 0 Range units 80 40000 V Default val...

Страница 337: ... 1 9 0 Range units 1 5 000 kW Default value 200 kW Alternative config Yes Step 1 kW Comm object 15772 Related applications AMF MRS Config level Standard Setpoint visibility Conditioned by the setpoint Connection type page 177 Description Nominal power of the gen set for detected split phase or mono phase connection Generator Overload BOC page 227 protection is based on this setpoint Note This setp...

Страница 338: ...hase voltage measurement L1 L3 with 180 phase shift 2x CT Current Transformer 3Ph4Wire Grounded Star Grounded Wye connection 3PY Three phase voltage measurement L1 L2 L3 with 120 phase shift 3x CT Current Transformer 3Ph3Wire Ungrounded Delta connection Open Delta Ungrounded Wye Corner Grounded Delta Split Phase Delta Three phase voltage measurement L1 L2 L3 with 120 phase shift No neutral is avai...

Страница 339: ... current limit for generator current protections and means maximal continuous generator current Nominal Current can be different from generator rated current value Note This value is used when binary input ALTERNATE CONFIG 3 PAGE 499 is active Nominal Current 3 6 back to List of setpoints Setpoint group Basic settings Related FW 1 9 0 Range units 45 65 Hz Default value 50 Hz Alternative config YES...

Страница 340: ...ject 12054 Related applications AMF MRS Config level Standard Setpoint visibility Conditioned by the setpoint Connection type 3 page 337 Description Nominal system voltage phase to neutral Note This value is used when binary input ALTERNATE CONFIG 3 PAGE 499 is active Nominal Voltage Ph N 3 6 back to List of setpoints Setpoint group Basic settings Related FW 1 9 0 Range units 80 40 000 V Default v...

Страница 341: ...inary input ALTERNATE CONFIG 3 PAGE 499 is active Nominal Power 3 6 back to List of setpoints Setpoint group Basic settings Related FW 1 9 0 Range units 1 5 000 kW Default value 200 kW Alternative config Yes Step 1 kW Comm object 15773 Related applications AMF MRS Config level Standard Setpoint visibility Conditioned by the setpoint Connection type page 177 Description Nominal power of the gen set...

Страница 342: ...te This value is used when any other alternate configuration is not active ECU Speed Adjustment 1 6 back to List of setpoints Setpoint group Engine settings Related FW 1 9 0 Range units 0 100 Default value 50 Alternative config NO Step 1 Comm object 14338 Related applications AMF MRS Config level Advanced Setpoint visibility Visible only if ECU is configured Description Enables to adjust engine sp...

Страница 343: ...is used when binary input ALTERNATE CONFIG 3 PAGE 499 is active ECU Speed Adjustment 3 6 back to List of setpoints Group CM RS232 485 Setpoint group CM RS232 485 Related FW 1 9 0 Range units Direct MODBUS DualSlave Dual Master Default value Direct Alternative config NO Step Comm object 24522 Related applications AMF MRS Config level Standard Setpoint visibility Only if relevant module is installed...

Страница 344: ...justed here Speed of second part of line has to be adjusted to the same value Note Winscope supports only 19200 38400 57600 speeds COM1 Communication Speed 6 List of setpoints page 170 Setpoint group CM RS232 485 Related FW 1 9 0 Range units 9600 19200 38400 57600 115200 bps Default value 9600 bps Alternative config NO Step Comm object 24477 Related applications AMF MRS Config level Standard Setpo...

Страница 345: ...Dual operation protocol master function COM2 Mode 6 back to List of setpoints Setpoint group CM RS232 485 Related FW 1 9 0 Range units 9600 19200 38400 57600 115200 bps Default value 57600 bps Alternative config NO Step Comm object 24340 Related applications AMF MRS Config level Standard Setpoint visibility Only if relevant module is installed conditioned by the setpoint COM2 Mode page 345 Descrip...

Страница 346: ...up CM GPRS CM 4G GPS Related FW 1 9 0 Range units Email SMS SMS Only Default value Email SMS Alternative config NO Step Comm object 24315 Related applications AMF MRS Config level Standard Setpoint visibility Only if relevant module is installed Description This setpoint adjust the communication mode of module Email SMS Controller is connected to the Internet and is able to send e mails as well as...

Страница 347: ... of the GPRS 4G network provided by GSM operator APN Name 6 back to List of setpoints Setpoint group CM GPRS CM 4G GPS Related FW 1 9 0 Range units 0 15 characters Default value Alternative config NO Step Comm object 24361 Related applications AMF MRS Config level Standard Setpoint visibility Only if relevant module is installed conditioned by the setpoint Internet Connection page 359 Description ...

Страница 348: ...er Password 6 back to List of setpoints Setpoint group CM GPRS CM 4G GPS CM Ethernet Related FW 1 9 0 Range units 0 63 characters Default value Alternative config NO Step Comm object 24298 Related applications AMF MRS Config level Standard Setpoint visibility Only if relevant module is installed conditioned by the setpoint Internet Connection page 359 CM GPRS and CM 4G GPS modules Description Ente...

Страница 349: ... This setpoint is common for CM Ethernet CM GPRS and CM 4G GPS modules Email Address 2 6 back to List of setpoints Setpoint group CM GPRS CM 4G GPS CM Ethernet Related FW 1 9 0 Range units 0 63 characters Default value Alternative config NO Step Comm object 24145 Related applications AMF MRS Config level Standard Setpoint visibility Only if relevant module is installed conditioned by the setpoint ...

Страница 350: ...larm and event email should not be send Note This setpoint is common for CM Ethernet CM GPRS and CM 4G GPS modules Email Address 4 6 back to List of setpoints Setpoint group CM GPRS CM 4G GPS CM Ethernet Related FW 1 9 0 Range units Default value English Alternative config NO Step Comm object 24299 Related applications AMF MRS Config level Standard Setpoint visibility Only if relevant module is in...

Страница 351: ...the setpoint blank if the SMTP server does not require authentication SMTP User Name 6 back to List of setpoints Setpoint group CM GPRS CM 4G GPS Related FW 1 9 0 Range units 0 15 characters Default value Alternative config NO Step Comm object 24312 Related applications AMF MRS Config level Standard Setpoint visibility Only if relevant module is installed conditioned by the setpoint Internet Conne...

Страница 352: ...erver at airgate comap cz may be used Ports 25 and 9925 are supported After controller connects to AirGate for the first time or with new public IP address it may not be able to send emails for first 5 10 minutes SMTP Server Address 6 back to List of setpoints Setpoint group CM GPRS CM 4G GPS Related FW 1 9 0 Range units 0 31 characters Default value Alternative config NO Step Comm object 24310 Re...

Страница 353: ... your time zone Note If the time zone is not selected properly the active e mails may contain incorrect information about sending time which may result in confusion when the respective problem actually occurred Note This setpoint is common for CM Ethernet CM GPRS and CM 4G GPS modules Time Zone 6 back to List of setpoints Setpoint group CM GPRS CM 4G GPS CM Ethernet Related FW 1 9 0 Range units ON...

Страница 354: ... ON Alternative config NO Step Comm object 10566 Related applications AMF MRS Config level Standard Setpoint visibility Only if relevant module is installed Description This setpoint enables or disables BOC Messages This setpoint is common for CM Ethernet CM GPRS and CM 4G GPS modules BOC Message 6 back to List of setpoints Setpoint group CM GPRS CM 4G GPS CM Ethernet Related FW 1 9 0 Range units ...

Страница 355: ... prefix IMPORTANT Telephone number has to be entered without spaces Telephone Number 1 6 back to List of setpoints Setpoint group CM GPRS CM 4G GPS Related FW 1 9 0 Range units 0 31 characters Default value Alternative config NO Step Comm object 24295 Related applications AMF MRS Config level Standard Setpoint visibility Only if relevant module is installed Description Enter in this setpoint eithe...

Страница 356: ... prefix IMPORTANT Telephone number has to be entered without spaces Telephone Number 3 6 back to List of setpoints Setpoint group CM GPRS CM 4G GPS Related FW 1 9 0 Range units 0 31 characters Default value Alternative config NO Step Comm object 24142 Related applications AMF MRS Config level Standard Setpoint visibility Only if relevant module is installed Description Enter in this setpoint eithe...

Страница 357: ...S CM 4G GPS Related FW 1 9 0 Range units DISABLED ENABLED Default value ENABLED Alternative config NO Step Comm object 24273 Related applications AMF MRS Config level Standard Setpoint visibility Only if relevant module is installed conditioned by the setpoint Internet Connection page 359 Description This setpoint enable or disable AirGate connection via CM GPRS or via CM 4G GPS DISABLED Only SMS ...

Страница 358: ...Ethernet Related FW 1 9 0 Range units 0 65 535 Default value 23 Alternative config NO Step Comm object 24374 Related applications AMF MRS Config level Standard Setpoint visibility Only if relevant module is installed conditioned by the setpoint Internet Connection page 359 CM GPRS module Description This setpoint is used to adjust the port number which is used for Ethernet connection to a PC with ...

Страница 359: ...sible via AirGate Internet enabled SIM card must be used Also APN Name page 360 has to be adjusted SMS Only Only SMS are sent Internet enabled SIM card is not required IMPORTANT When this setpoint is changed the controller has to be restarted to apply changes Internet Connection 6 List of setpoints page 170 Setpoint group CM 4G GPS Related FW 1 9 0 Range units 2G 3G 4G Automatic Default value Auto...

Страница 360: ... of the GPRS 4G network provided by GSM operator APN Name 6 back to List of setpoints Setpoint group CM GPRS CM 4G GPS Related FW 1 9 0 Range units 0 15 characters Default value Alternative config NO Step Comm object 24361 Related applications AMF MRS Config level Standard Setpoint visibility Only if relevant module is installed conditioned by the setpoint Internet Connection page 359 Description ...

Страница 361: ...er Password 6 back to List of setpoints Setpoint group CM GPRS CM 4G GPS CM Ethernet Related FW 1 9 0 Range units 0 63 characters Default value Alternative config NO Step Comm object 24298 Related applications AMF MRS Config level Standard Setpoint visibility Only if relevant module is installed conditioned by the setpoint Internet Connection page 359 CM GPRS and CM 4G GPS modules Description Ente...

Страница 362: ... This setpoint is common for CM Ethernet CM GPRS and CM 4G GPS modules Email Address 2 6 back to List of setpoints Setpoint group CM GPRS CM 4G GPS CM Ethernet Related FW 1 9 0 Range units 0 63 characters Default value Alternative config NO Step Comm object 24145 Related applications AMF MRS Config level Standard Setpoint visibility Only if relevant module is installed conditioned by the setpoint ...

Страница 363: ...larm and event email should not be send Note This setpoint is common for CM Ethernet CM GPRS and CM 4G GPS modules Email Address 4 6 back to List of setpoints Setpoint group CM GPRS CM 4G GPS CM Ethernet Related FW 1 9 0 Range units Default value English Alternative config NO Step Comm object 24299 Related applications AMF MRS Config level Standard Setpoint visibility Only if relevant module is in...

Страница 364: ...the setpoint blank if the SMTP server does not require authentication SMTP User Name 6 back to List of setpoints Setpoint group CM GPRS CM 4G GPS Related FW 1 9 0 Range units 0 15 characters Default value Alternative config NO Step Comm object 24312 Related applications AMF MRS Config level Standard Setpoint visibility Only if relevant module is installed conditioned by the setpoint Internet Conne...

Страница 365: ...erver at airgate comap cz may be used Ports 25 and 9925 are supported After controller connects to AirGate for the first time or with new public IP address it may not be able to send emails for first 5 10 minutes SMTP Server Address 6 back to List of setpoints Setpoint group CM GPRS CM 4G GPS Related FW 1 9 0 Range units 0 31 characters Default value Alternative config NO Step Comm object 24310 Re...

Страница 366: ... your time zone Note If the time zone is not selected properly the active e mails may contain incorrect information about sending time which may result in confusion when the respective problem actually occurred Note This setpoint is common for CM Ethernet CM GPRS and CM 4G GPS modules Time Zone 6 back to List of setpoints Setpoint group CM GPRS CM 4G GPS CM Ethernet Related FW 1 9 0 Range units ON...

Страница 367: ... ON Alternative config NO Step Comm object 10566 Related applications AMF MRS Config level Standard Setpoint visibility Only if relevant module is installed Description This setpoint enables or disables BOC Messages This setpoint is common for CM Ethernet CM GPRS and CM 4G GPS modules BOC Message 6 back to List of setpoints Setpoint group CM GPRS CM 4G GPS CM Ethernet Related FW 1 9 0 Range units ...

Страница 368: ... prefix IMPORTANT Telephone number has to be entered without spaces Telephone Number 1 6 back to List of setpoints Setpoint group CM GPRS CM 4G GPS Related FW 1 9 0 Range units 0 31 characters Default value Alternative config NO Step Comm object 24295 Related applications AMF MRS Config level Standard Setpoint visibility Only if relevant module is installed Description Enter in this setpoint eithe...

Страница 369: ... prefix IMPORTANT Telephone number has to be entered without spaces Telephone Number 3 6 back to List of setpoints Setpoint group CM GPRS CM 4G GPS Related FW 1 9 0 Range units 0 31 characters Default value Alternative config NO Step Comm object 24142 Related applications AMF MRS Config level Standard Setpoint visibility Only if relevant module is installed Description Enter in this setpoint eithe...

Страница 370: ...rver address is adjusted by the setpoint AirGate Address page 384 IMPORTANT When this setpoint is changed the controller has to be restarted to apply changes AirGate Connection 6 back to List of setpoints Setpoint group CM GPRS CM 4G GPS CM Ethernet Related FW 1 9 0 Range units Default value airgate comap cz Alternative config NO Step Comm object 24364 Related applications AMF MRS Config level Sta...

Страница 371: ...ng many controllers or to overcome a firewall restrictions IMPORTANT If AirGate is used this setpoint has to be adjusted to 23 Note This setpoint is common for CM Ethernet CM GPRS and CM 4G GPS modules ComAp TCP Port 6 back to List of setpoints Group CM Ethernet Setpoint group CM GPRS CM 4G GPS CM Ethernet Related FW 1 9 0 Range units 0 63 characters Default value Alternative config NO Step Comm o...

Страница 372: ... This setpoint is common for CM Ethernet CM GPRS and CM 4G GPS modules Email Address 2 6 back to List of setpoints Setpoint group CM GPRS CM 4G GPS CM Ethernet Related FW 1 9 0 Range units 0 63 characters Default value Alternative config NO Step Comm object 24145 Related applications AMF MRS Config level Standard Setpoint visibility Only if relevant module is installed conditioned by the setpoint ...

Страница 373: ...larm and event email should not be send Note This setpoint is common for CM Ethernet CM GPRS and CM 4G GPS modules Email Address 4 6 back to List of setpoints Setpoint group CM GPRS CM 4G GPS CM Ethernet Related FW 1 9 0 Range units Default value English Alternative config NO Step Comm object 24299 Related applications AMF MRS Config level Standard Setpoint visibility Only if relevant module is in...

Страница 374: ... your time zone Note If the time zone is not selected properly the active e mails may contain incorrect information about sending time which may result in confusion when the respective problem actually occurred Note This setpoint is common for CM Ethernet CM GPRS and CM 4G GPS modules Time Zone 6 back to List of setpoints Setpoint group CM GPRS CM 4G GPS CM Ethernet Related FW 1 9 0 Range units ON...

Страница 375: ... ON Alternative config NO Step Comm object 10566 Related applications AMF MRS Config level Standard Setpoint visibility Only if relevant module is installed Description This setpoint enables or disables BOC Messages This setpoint is common for CM Ethernet CM GPRS and CM 4G GPS modules BOC Message 6 back to List of setpoints Setpoint group CM GPRS CM 4G GPS CM Ethernet Related FW 1 9 0 Range units ...

Страница 376: ... the setpoint blank if the SMTP server does not require authentication SMTP UserName 6 back to List of setpoints Setpoint group CM Ethernet Related FW 1 9 0 Range units 0 15 characters Default value Alternative config NO Step Comm object 24369 Related applications AMF MRS Config level Standard Setpoint visibility Only if relevant module is installed Description Use this setpoint to enter the passw...

Страница 377: ...e SMTP server at airgate comap cz may be used Ports 25 and 9925 are supported After controller connects to AirGate for the first time or with new public IP address it may not be able to send emails for first 5 10 minutes SMTP Server Address 6 back to List of setpoints Setpoint group CM Ethernet Related FW 1 9 0 Range units 0 31 characters Default value Alternative config NO Step Comm object 24367 ...

Страница 378: ...ed settings are then copied to the related setpoints If the process of obtaining the settings from the DHCP server is not successful the value 000 000 000 000 is copied to the setpoint IP address and the module continues to try to obtain the settings IP Address Mode 6 back to List of setpoints Setpoint group CM Ethernet Related FW 1 9 0 Range units Valid IP address Default value 192 168 1 254 Alte...

Страница 379: ...ver Subnet Mask 6 back to List of setpoints Setpoint group CM Ethernet Related FW 1 9 0 Range units Valid IP address Default value 192 168 1 1 Alternative config NO Step Comm object 24373 Related applications AMF MRS Config level Standard Setpoint visibility Only if relevant module is installed conditioned by the setpoint IP Address Mode page 378 Description The setpoint is used to select the meth...

Страница 380: ... is inactive The DNS server IP address is assigned by the DHCP server DNS IP Address 1 6 back to List of setpoints Setpoint group CM Ethernet Related FW 1 9 0 Range units Valid IP address Default value 8 8 8 8 Alternative config NO Step Comm object 24331 Related applications AMF MRS Config level Standard Setpoint visibility Only if relevant module is installed Description The setpoint is used to s...

Страница 381: ...ABLED Default value DISABLED Alternative config NO Step Comm object 24336 Related applications AMF MRS Config level Standard Setpoint visibility Only if relevant module is installed Description Enable or disable SNMP v1 Agent SNMP Agent 6 back to List of setpoints Setpoint group CM Ethernet Related FW 1 9 0 Range units 0 31 characters Default value public Alternative config NO Step Comm object 243...

Страница 382: ...Pv2 Not SNMPv2 Inf Default value SNMP v1 Trap Alternative config NO Step Comm object 24136 Related applications AMF MRS Config level Standard Setpoint visibility Only if relevant module is installed Description This setpoint adjusts type of SNMP traps SNMP Trap Format 6 back to List of setpoints Setpoint group CM Ethernet Related FW 1 9 0 Range units Valid IP address Default value DISABLED Alterna...

Страница 383: ...native config NO Step Comm object 24365 Related applications AMF MRS Config level Standard Setpoint visibility Only if relevant module is installed Description This setpoint selects the Ethernet connection mode DISABLED This is a standard mode in which the controller listens to the incoming traffic and answers the TCP IP queries addressed to it This mode requires the controller to be accessible fr...

Страница 384: ...Ethernet Related FW 1 9 0 Range units 0 65 535 Default value 23 Alternative config NO Step Comm object 24374 Related applications AMF MRS Config level Standard Setpoint visibility Only if relevant module is installed conditioned by the setpoint Internet Connection page 359 CM GPRS module Description This setpoint is used to adjust the port number which is used for Ethernet connection to a PC with ...

Страница 385: ...nt group EM BIO8 EFCP Related FW 1 9 0 Range units DISABLED ENABLED Default value ENABLED Alternative config NO Step Comm object 11631 Related applications AMF MRS Config level Standard Setpoint visibility Only if relevant module is installed Description This setpoint can block or allow Earth fault Current protection DISABLED Earth fault current protection is blocked ENABLED Earth fault current pr...

Страница 386: ...oint visibility Only if relevant module is installed Description There are 2 physical inputs for Earth Fault Current Protection page 385 Value of this setpoint has to be set on value of physical input which is presently in use Earth Fault CT Input Range 6 back to List of setpoints Setpoint group EM BIO8 EFCP Related FW 1 9 0 Range units 1 2000 1 1or5 A Default value 500 1 1or5 A Alternative config...

Страница 387: ...ed applications AMF MRS Config level Standard Setpoint visibility Only if relevant setpoint is used in PLC Description Adjustable value for input in PLC logic Configuration of setpoint Configuration is made via configuration PC tool InteliConfig Image 8 64 Screen of configuration from InteliConfig PLC Setpoint name Name of the setpoint 0 32 characters Dimension Dimension of value of the setpoint R...

Страница 388: ...int Configuration is made via configuration PC tool InteliConfig Image 8 65 Screen of configuration from InteliConfig PLC Setpoint name Name of the setpoint 0 32 characters Dimension Dimension of value of the setpoint Resolution Resolution of the value of the setpoint Resolution adjust number of decimal places in low and high limit Low limit The lowest value of setpoint Digit place of this value c...

Страница 389: ...int Configuration is made via configuration PC tool InteliConfig Image 8 66 Screen of configuration from InteliConfig PLC Setpoint name Name of the setpoint 0 32 characters Dimension Dimension of value of the setpoint Resolution Resolution of the value of the setpoint Resolution adjust number of decimal places in low and high limit Low limit The lowest value of setpoint Digit place of this value c...

Страница 390: ...int Configuration is made via configuration PC tool InteliConfig Image 8 67 Screen of configuration from InteliConfig PLC Setpoint name Name of the setpoint 0 32 characters Dimension Dimension of value of the setpoint Resolution Resolution of the value of the setpoint Resolution adjust number of decimal places in low and high limit Low limit The lowest value of setpoint Digit place of this value c...

Страница 391: ...int Configuration is made via configuration PC tool InteliConfig Image 8 68 Screen of configuration from InteliConfig PLC Setpoint name Name of the setpoint 0 32 characters Dimension Dimension of value of the setpoint Resolution Resolution of the value of the setpoint Resolution adjust number of decimal places in low and high limit Low limit The lowest value of setpoint Digit place of this value c...

Страница 392: ...int Configuration is made via configuration PC tool InteliConfig Image 8 69 Screen of configuration from InteliConfig PLC Setpoint name Name of the setpoint 0 32 characters Dimension Dimension of value of the setpoint Resolution Resolution of the value of the setpoint Resolution adjust number of decimal places in low and high limit Low limit The lowest value of setpoint Digit place of this value c...

Страница 393: ...int Configuration is made via configuration PC tool InteliConfig Image 8 70 Screen of configuration from InteliConfig PLC Setpoint name Name of the setpoint 0 32 characters Dimension Dimension of value of the setpoint Resolution Resolution of the value of the setpoint Resolution adjust number of decimal places in low and high limit Low limit The lowest value of setpoint Digit place of this value c...

Страница 394: ...int Configuration is made via configuration PC tool InteliConfig Image 8 71 Screen of configuration from InteliConfig PLC Setpoint name Name of the setpoint 0 32 characters Dimension Dimension of value of the setpoint Resolution Resolution of the value of the setpoint Resolution adjust number of decimal places in low and high limit Low limit The lowest value of setpoint Digit place of this value c...

Страница 395: ...int Configuration is made via configuration PC tool InteliConfig Image 8 72 Screen of configuration from InteliConfig PLC Setpoint name Name of the setpoint 0 32 characters Dimension Dimension of value of the setpoint Resolution Resolution of the value of the setpoint Resolution adjust number of decimal places in low and high limit Low limit The lowest value of setpoint Digit place of this value c...

Страница 396: ...nt Configuration is made via configuration PC tool InteliConfig Image 8 73 Screen of configuration from InteliConfig PLC Setpoint name Name of the setpoint 0 32 characters Dimension Dimension of value of the setpoint Resolution Resolution of the value of the setpoint Resolution adjust number of decimal places in low and high limit Low limit The lowest value of setpoint Digit place of this value ca...

Страница 397: ...nt Configuration is made via configuration PC tool InteliConfig Image 8 74 Screen of configuration from InteliConfig PLC Setpoint name Name of the setpoint 0 32 characters Dimension Dimension of value of the setpoint Resolution Resolution of the value of the setpoint Resolution adjust number of decimal places in low and high limit Low limit The lowest value of setpoint Digit place of this value ca...

Страница 398: ...nt Configuration is made via configuration PC tool InteliConfig Image 8 75 Screen of configuration from InteliConfig PLC Setpoint name Name of the setpoint 0 32 characters Dimension Dimension of value of the setpoint Resolution Resolution of the value of the setpoint Resolution adjust number of decimal places in low and high limit Low limit The lowest value of setpoint Digit place of this value ca...

Страница 399: ...nt Configuration is made via configuration PC tool InteliConfig Image 8 76 Screen of configuration from InteliConfig PLC Setpoint name Name of the setpoint 0 32 characters Dimension Dimension of value of the setpoint Resolution Resolution of the value of the setpoint Resolution adjust number of decimal places in low and high limit Low limit The lowest value of setpoint Digit place of this value ca...

Страница 400: ...nt Configuration is made via configuration PC tool InteliConfig Image 8 77 Screen of configuration from InteliConfig PLC Setpoint name Name of the setpoint 0 32 characters Dimension Dimension of value of the setpoint Resolution Resolution of the value of the setpoint Resolution adjust number of decimal places in low and high limit Low limit The lowest value of setpoint Digit place of this value ca...

Страница 401: ...nt Configuration is made via configuration PC tool InteliConfig Image 8 78 Screen of configuration from InteliConfig PLC Setpoint name Name of the setpoint 0 32 characters Dimension Dimension of value of the setpoint Resolution Resolution of the value of the setpoint Resolution adjust number of decimal places in low and high limit Low limit The lowest value of setpoint Digit place of this value ca...

Страница 402: ...nt Configuration is made via configuration PC tool InteliConfig Image 8 79 Screen of configuration from InteliConfig PLC Setpoint name Name of the setpoint 0 32 characters Dimension Dimension of value of the setpoint Resolution Resolution of the value of the setpoint Resolution adjust number of decimal places in low and high limit Low limit The lowest value of setpoint Digit place of this value ca...

Страница 403: ...nt Configuration is made via configuration PC tool InteliConfig Image 8 80 Screen of configuration from InteliConfig PLC Setpoint name Name of the setpoint 0 32 characters Dimension Dimension of value of the setpoint Resolution Resolution of the value of the setpoint Resolution adjust number of decimal places in low and high limit Low limit The lowest value of setpoint Digit place of this value ca...

Страница 404: ...nt Configuration is made via configuration PC tool InteliConfig Image 8 81 Screen of configuration from InteliConfig PLC Setpoint name Name of the setpoint 0 32 characters Dimension Dimension of value of the setpoint Resolution Resolution of the value of the setpoint Resolution adjust number of decimal places in low and high limit Low limit The lowest value of setpoint Digit place of this value ca...

Страница 405: ...nt Configuration is made via configuration PC tool InteliConfig Image 8 82 Screen of configuration from InteliConfig PLC Setpoint name Name of the setpoint 0 32 characters Dimension Dimension of value of the setpoint Resolution Resolution of the value of the setpoint Resolution adjust number of decimal places in low and high limit Low limit The lowest value of setpoint Digit place of this value ca...

Страница 406: ...nt Configuration is made via configuration PC tool InteliConfig Image 8 83 Screen of configuration from InteliConfig PLC Setpoint name Name of the setpoint 0 32 characters Dimension Dimension of value of the setpoint Resolution Resolution of the value of the setpoint Resolution adjust number of decimal places in low and high limit Low limit The lowest value of setpoint Digit place of this value ca...

Страница 407: ...nt Configuration is made via configuration PC tool InteliConfig Image 8 84 Screen of configuration from InteliConfig PLC Setpoint name Name of the setpoint 0 32 characters Dimension Dimension of value of the setpoint Resolution Resolution of the value of the setpoint Resolution adjust number of decimal places in low and high limit Low limit The lowest value of setpoint Digit place of this value ca...

Страница 408: ...nt Configuration is made via configuration PC tool InteliConfig Image 8 85 Screen of configuration from InteliConfig PLC Setpoint name Name of the setpoint 0 32 characters Dimension Dimension of value of the setpoint Resolution Resolution of the value of the setpoint Resolution adjust number of decimal places in low and high limit Low limit The lowest value of setpoint Digit place of this value ca...

Страница 409: ...nt Configuration is made via configuration PC tool InteliConfig Image 8 86 Screen of configuration from InteliConfig PLC Setpoint name Name of the setpoint 0 32 characters Dimension Dimension of value of the setpoint Resolution Resolution of the value of the setpoint Resolution adjust number of decimal places in low and high limit Low limit The lowest value of setpoint Digit place of this value ca...

Страница 410: ...nt Configuration is made via configuration PC tool InteliConfig Image 8 87 Screen of configuration from InteliConfig PLC Setpoint name Name of the setpoint 0 32 characters Dimension Dimension of value of the setpoint Resolution Resolution of the value of the setpoint Resolution adjust number of decimal places in low and high limit Low limit The lowest value of setpoint Digit place of this value ca...

Страница 411: ...nt Configuration is made via configuration PC tool InteliConfig Image 8 88 Screen of configuration from InteliConfig PLC Setpoint name Name of the setpoint 0 32 characters Dimension Dimension of value of the setpoint Resolution Resolution of the value of the setpoint Resolution adjust number of decimal places in low and high limit Low limit The lowest value of setpoint Digit place of this value ca...

Страница 412: ...nt Configuration is made via configuration PC tool InteliConfig Image 8 89 Screen of configuration from InteliConfig PLC Setpoint name Name of the setpoint 0 32 characters Dimension Dimension of value of the setpoint Resolution Resolution of the value of the setpoint Resolution adjust number of decimal places in low and high limit Low limit The lowest value of setpoint Digit place of this value ca...

Страница 413: ...nt Configuration is made via configuration PC tool InteliConfig Image 8 90 Screen of configuration from InteliConfig PLC Setpoint name Name of the setpoint 0 32 characters Dimension Dimension of value of the setpoint Resolution Resolution of the value of the setpoint Resolution adjust number of decimal places in low and high limit Low limit The lowest value of setpoint Digit place of this value ca...

Страница 414: ...nt Configuration is made via configuration PC tool InteliConfig Image 8 91 Screen of configuration from InteliConfig PLC Setpoint name Name of the setpoint 0 32 characters Dimension Dimension of value of the setpoint Resolution Resolution of the value of the setpoint Resolution adjust number of decimal places in low and high limit Low limit The lowest value of setpoint Digit place of this value ca...

Страница 415: ...nt Configuration is made via configuration PC tool InteliConfig Image 8 92 Screen of configuration from InteliConfig PLC Setpoint name Name of the setpoint 0 32 characters Dimension Dimension of value of the setpoint Resolution Resolution of the value of the setpoint Resolution adjust number of decimal places in low and high limit Low limit The lowest value of setpoint Digit place of this value ca...

Страница 416: ...nt Configuration is made via configuration PC tool InteliConfig Image 8 93 Screen of configuration from InteliConfig PLC Setpoint name Name of the setpoint 0 32 characters Dimension Dimension of value of the setpoint Resolution Resolution of the value of the setpoint Resolution adjust number of decimal places in low and high limit Low limit The lowest value of setpoint Digit place of this value ca...

Страница 417: ...nt Configuration is made via configuration PC tool InteliConfig Image 8 94 Screen of configuration from InteliConfig PLC Setpoint name Name of the setpoint 0 32 characters Dimension Dimension of value of the setpoint Resolution Resolution of the value of the setpoint Resolution adjust number of decimal places in low and high limit Low limit The lowest value of setpoint Digit place of this value ca...

Страница 418: ...nt Configuration is made via configuration PC tool InteliConfig Image 8 95 Screen of configuration from InteliConfig PLC Setpoint name Name of the setpoint 0 32 characters Dimension Dimension of value of the setpoint Resolution Resolution of the value of the setpoint Resolution adjust number of decimal places in low and high limit Low limit The lowest value of setpoint Digit place of this value ca...

Страница 419: ...nt Configuration is made via configuration PC tool InteliConfig Image 8 96 Screen of configuration from InteliConfig PLC Setpoint name Name of the setpoint 0 32 characters Dimension Dimension of value of the setpoint Resolution Resolution of the value of the setpoint Resolution adjust number of decimal places in low and high limit Low limit The lowest value of setpoint Digit place of this value ca...

Страница 420: ...nt Configuration is made via configuration PC tool InteliConfig Image 8 97 Screen of configuration from InteliConfig PLC Setpoint name Name of the setpoint 0 32 characters Dimension Dimension of value of the setpoint Resolution Resolution of the value of the setpoint Resolution adjust number of decimal places in low and high limit Low limit The lowest value of setpoint Digit place of this value ca...

Страница 421: ...nt Configuration is made via configuration PC tool InteliConfig Image 8 98 Screen of configuration from InteliConfig PLC Setpoint name Name of the setpoint 0 32 characters Dimension Dimension of value of the setpoint Resolution Resolution of the value of the setpoint Resolution adjust number of decimal places in low and high limit Low limit The lowest value of setpoint Digit place of this value ca...

Страница 422: ...nt Configuration is made via configuration PC tool InteliConfig Image 8 99 Screen of configuration from InteliConfig PLC Setpoint name Name of the setpoint 0 32 characters Dimension Dimension of value of the setpoint Resolution Resolution of the value of the setpoint Resolution adjust number of decimal places in low and high limit Low limit The lowest value of setpoint Digit place of this value ca...

Страница 423: ...nt Configuration is made via configuration PC tool InteliConfig Image 8 100 Screen of configuration from InteliConfig PLC Setpoint name Name of the setpoint 0 32 characters Dimension Dimension of value of the setpoint Resolution Resolution of the value of the setpoint Resolution adjust number of decimal places in low and high limit Low limit The lowest value of setpoint Digit place of this value c...

Страница 424: ...nt Configuration is made via configuration PC tool InteliConfig Image 8 101 Screen of configuration from InteliConfig PLC Setpoint name Name of the setpoint 0 32 characters Dimension Dimension of value of the setpoint Resolution Resolution of the value of the setpoint Resolution adjust number of decimal places in low and high limit Low limit The lowest value of setpoint Digit place of this value c...

Страница 425: ...nt Configuration is made via configuration PC tool InteliConfig Image 8 102 Screen of configuration from InteliConfig PLC Setpoint name Name of the setpoint 0 32 characters Dimension Dimension of value of the setpoint Resolution Resolution of the value of the setpoint Resolution adjust number of decimal places in low and high limit Low limit The lowest value of setpoint Digit place of this value c...

Страница 426: ...nt Configuration is made via configuration PC tool InteliConfig Image 8 103 Screen of configuration from InteliConfig PLC Setpoint name Name of the setpoint 0 32 characters Dimension Dimension of value of the setpoint Resolution Resolution of the value of the setpoint Resolution adjust number of decimal places in low and high limit Low limit The lowest value of setpoint Digit place of this value c...

Страница 427: ...nt Configuration is made via configuration PC tool InteliConfig Image 8 104 Screen of configuration from InteliConfig PLC Setpoint name Name of the setpoint 0 32 characters Dimension Dimension of value of the setpoint Resolution Resolution of the value of the setpoint Resolution adjust number of decimal places in low and high limit Low limit The lowest value of setpoint Digit place of this value c...

Страница 428: ...nt Configuration is made via configuration PC tool InteliConfig Image 8 105 Screen of configuration from InteliConfig PLC Setpoint name Name of the setpoint 0 32 characters Dimension Dimension of value of the setpoint Resolution Resolution of the value of the setpoint Resolution adjust number of decimal places in low and high limit Low limit The lowest value of setpoint Digit place of this value c...

Страница 429: ...nt Configuration is made via configuration PC tool InteliConfig Image 8 106 Screen of configuration from InteliConfig PLC Setpoint name Name of the setpoint 0 32 characters Dimension Dimension of value of the setpoint Resolution Resolution of the value of the setpoint Resolution adjust number of decimal places in low and high limit Low limit The lowest value of setpoint Digit place of this value c...

Страница 430: ...nt Configuration is made via configuration PC tool InteliConfig Image 8 107 Screen of configuration from InteliConfig PLC Setpoint name Name of the setpoint 0 32 characters Dimension Dimension of value of the setpoint Resolution Resolution of the value of the setpoint Resolution adjust number of decimal places in low and high limit Low limit The lowest value of setpoint Digit place of this value c...

Страница 431: ...nt Configuration is made via configuration PC tool InteliConfig Image 8 108 Screen of configuration from InteliConfig PLC Setpoint name Name of the setpoint 0 32 characters Dimension Dimension of value of the setpoint Resolution Resolution of the value of the setpoint Resolution adjust number of decimal places in low and high limit Low limit The lowest value of setpoint Digit place of this value c...

Страница 432: ...nt Configuration is made via configuration PC tool InteliConfig Image 8 109 Screen of configuration from InteliConfig PLC Setpoint name Name of the setpoint 0 32 characters Dimension Dimension of value of the setpoint Resolution Resolution of the value of the setpoint Resolution adjust number of decimal places in low and high limit Low limit The lowest value of setpoint Digit place of this value c...

Страница 433: ...nt Configuration is made via configuration PC tool InteliConfig Image 8 110 Screen of configuration from InteliConfig PLC Setpoint name Name of the setpoint 0 32 characters Dimension Dimension of value of the setpoint Resolution Resolution of the value of the setpoint Resolution adjust number of decimal places in low and high limit Low limit The lowest value of setpoint Digit place of this value c...

Страница 434: ...nt Configuration is made via configuration PC tool InteliConfig Image 8 111 Screen of configuration from InteliConfig PLC Setpoint name Name of the setpoint 0 32 characters Dimension Dimension of value of the setpoint Resolution Resolution of the value of the setpoint Resolution adjust number of decimal places in low and high limit Low limit The lowest value of setpoint Digit place of this value c...

Страница 435: ...nt Configuration is made via configuration PC tool InteliConfig Image 8 112 Screen of configuration from InteliConfig PLC Setpoint name Name of the setpoint 0 32 characters Dimension Dimension of value of the setpoint Resolution Resolution of the value of the setpoint Resolution adjust number of decimal places in low and high limit Low limit The lowest value of setpoint Digit place of this value c...

Страница 436: ...nt Configuration is made via configuration PC tool InteliConfig Image 8 113 Screen of configuration from InteliConfig PLC Setpoint name Name of the setpoint 0 32 characters Dimension Dimension of value of the setpoint Resolution Resolution of the value of the setpoint Resolution adjust number of decimal places in low and high limit Low limit The lowest value of setpoint Digit place of this value c...

Страница 437: ...nt Configuration is made via configuration PC tool InteliConfig Image 8 114 Screen of configuration from InteliConfig PLC Setpoint name Name of the setpoint 0 32 characters Dimension Dimension of value of the setpoint Resolution Resolution of the value of the setpoint Resolution adjust number of decimal places in low and high limit Low limit The lowest value of setpoint Digit place of this value c...

Страница 438: ...nt Configuration is made via configuration PC tool InteliConfig Image 8 115 Screen of configuration from InteliConfig PLC Setpoint name Name of the setpoint 0 32 characters Dimension Dimension of value of the setpoint Resolution Resolution of the value of the setpoint Resolution adjust number of decimal places in low and high limit Low limit The lowest value of setpoint Digit place of this value c...

Страница 439: ...nt Configuration is made via configuration PC tool InteliConfig Image 8 116 Screen of configuration from InteliConfig PLC Setpoint name Name of the setpoint 0 32 characters Dimension Dimension of value of the setpoint Resolution Resolution of the value of the setpoint Resolution adjust number of decimal places in low and high limit Low limit The lowest value of setpoint Digit place of this value c...

Страница 440: ...nt Configuration is made via configuration PC tool InteliConfig Image 8 117 Screen of configuration from InteliConfig PLC Setpoint name Name of the setpoint 0 32 characters Dimension Dimension of value of the setpoint Resolution Resolution of the value of the setpoint Resolution adjust number of decimal places in low and high limit Low limit The lowest value of setpoint Digit place of this value c...

Страница 441: ...nt Configuration is made via configuration PC tool InteliConfig Image 8 118 Screen of configuration from InteliConfig PLC Setpoint name Name of the setpoint 0 32 characters Dimension Dimension of value of the setpoint Resolution Resolution of the value of the setpoint Resolution adjust number of decimal places in low and high limit Low limit The lowest value of setpoint Digit place of this value c...

Страница 442: ...nt Configuration is made via configuration PC tool InteliConfig Image 8 119 Screen of configuration from InteliConfig PLC Setpoint name Name of the setpoint 0 32 characters Dimension Dimension of value of the setpoint Resolution Resolution of the value of the setpoint Resolution adjust number of decimal places in low and high limit Low limit The lowest value of setpoint Digit place of this value c...

Страница 443: ...nt Configuration is made via configuration PC tool InteliConfig Image 8 120 Screen of configuration from InteliConfig PLC Setpoint name Name of the setpoint 0 32 characters Dimension Dimension of value of the setpoint Resolution Resolution of the value of the setpoint Resolution adjust number of decimal places in low and high limit Low limit The lowest value of setpoint Digit place of this value c...

Страница 444: ...nt Configuration is made via configuration PC tool InteliConfig Image 8 121 Screen of configuration from InteliConfig PLC Setpoint name Name of the setpoint 0 32 characters Dimension Dimension of value of the setpoint Resolution Resolution of the value of the setpoint Resolution adjust number of decimal places in low and high limit Low limit The lowest value of setpoint Digit place of this value c...

Страница 445: ...nt Configuration is made via configuration PC tool InteliConfig Image 8 122 Screen of configuration from InteliConfig PLC Setpoint name Name of the setpoint 0 32 characters Dimension Dimension of value of the setpoint Resolution Resolution of the value of the setpoint Resolution adjust number of decimal places in low and high limit Low limit The lowest value of setpoint Digit place of this value c...

Страница 446: ...nt Configuration is made via configuration PC tool InteliConfig Image 8 123 Screen of configuration from InteliConfig PLC Setpoint name Name of the setpoint 0 32 characters Dimension Dimension of value of the setpoint Resolution Resolution of the value of the setpoint Resolution adjust number of decimal places in low and high limit Low limit The lowest value of setpoint Digit place of this value c...

Страница 447: ...nt Configuration is made via configuration PC tool InteliConfig Image 8 124 Screen of configuration from InteliConfig PLC Setpoint name Name of the setpoint 0 32 characters Dimension Dimension of value of the setpoint Resolution Resolution of the value of the setpoint Resolution adjust number of decimal places in low and high limit Low limit The lowest value of setpoint Digit place of this value c...

Страница 448: ...nt Configuration is made via configuration PC tool InteliConfig Image 8 125 Screen of configuration from InteliConfig PLC Setpoint name Name of the setpoint 0 32 characters Dimension Dimension of value of the setpoint Resolution Resolution of the value of the setpoint Resolution adjust number of decimal places in low and high limit Low limit The lowest value of setpoint Digit place of this value c...

Страница 449: ...nt Configuration is made via configuration PC tool InteliConfig Image 8 126 Screen of configuration from InteliConfig PLC Setpoint name Name of the setpoint 0 32 characters Dimension Dimension of value of the setpoint Resolution Resolution of the value of the setpoint Resolution adjust number of decimal places in low and high limit Low limit The lowest value of setpoint Digit place of this value c...

Страница 450: ...nt Configuration is made via configuration PC tool InteliConfig Image 8 127 Screen of configuration from InteliConfig PLC Setpoint name Name of the setpoint 0 32 characters Dimension Dimension of value of the setpoint Resolution Resolution of the value of the setpoint Resolution adjust number of decimal places in low and high limit Low limit The lowest value of setpoint Digit place of this value c...

Страница 451: ...ed on an analog input The configured ECU or extension module does not provide the particular value The communication with the ECU or extension module is interrupted A value containing the invalid flag is displayed as in InteliConfig and on the controller screen If such a value is read out via MODBUS it will contain the data 32768 in the case of signed values and 65535 in the case of unsigned value...

Страница 452: ...ad kVAr L2 464 Load kVAr L3 464 Load kW 464 Load kW L1 465 Load kW L2 465 Load kW L3 465 Load Power Factor 465 Load Power Factor L1 466 Load Power Factor L2 466 Load Power Factor L3 466 Dual Operation Running Hours To Swap 466 Master Running Hours 466 Slave Running Hours 467 Controler I O Analog Input 1 467 Analog Input 2 467 Analog Input 3 467 Analog Input 4 467 Battery Volts 468 Binary Inputs 46...

Страница 453: ...ail Result 488 Operator 489 CM 4G GPS GPS part Altitude 483 HomePosDist 483 Latitude 483 Longitude 484 Satellites 484 CM Ethernet AirGate Status 489 AirGate ID 489 Current DNS 490 ETH Interface Status 490 Current Gateway 490 Current IP Address 490 Last Email Result 491 MAC Address 491 Current Subnet Mask 492 Date Time Time 492 Date 492 Plug In I O EM BIO A 492 EM BIO B 493 PLC PLC Resource 1 493 P...

Страница 454: ...lues Value group Engine Related FW 1 9 0 Units Comm object 12484 Related applications AMF MRS Description The rate of soot in DPF Diesel particulate filter DPFSootLoad 6 back to List of values Value group Engine Related FW 1 9 0 Units Depends on ECU value Comm object 10153 Related applications AMF MRS Description This is one of the inputs which are defined by ECU Order of values depends on type of...

Страница 455: ...ke temperature C oil pressure bar boost pressure bar load oil temperature C etc ECU BIN 3 6 back to List of values Value group Engine Related FW 1 9 0 Units Depends on ECU value Comm object 10156 Related applications AMF MRS Description This is one of the inputs which are defined by ECU Order of values depends on type of ECU Note Usually there are engine speed RPM fuel rate L h coolant temperature...

Страница 456: ...ke temperature C oil pressure bar boost pressure bar load oil temperature C etc ECU BIN 7 6 back to List of values Value group Engine Related FW 1 9 0 Units Depends on ECU value Comm object 10160 Related applications AMF MRS Description This is one of the inputs which are defined by ECU Order of values depends on type of ECU Note Usually there are engine speed RPM fuel rate L h coolant temperature...

Страница 457: ...FW 1 9 0 Units Comm object 12926 Related applications AMF MRS Description Shows selected frequency of ECU The value is calculated from setpoint Nominal Frequency page 180 If is Nominal Frequency page 180 in range from 45 Hz to 54 Hz is considered as 50 Hz application The value is set to 0 If is Nominal Frequency page 180 in range from 55 Hz to 65 Hz is considered as 60 Hz application The value is ...

Страница 458: ...0137 Related applications AMF MRS Description Engine speed control via CAN bus Speed request Requested speed Accelerator pedal position 0 1350 RPM 0 50 1500 RPM 50 100 1650 RPM 100 Speed Request 6 back to List of values Value group Engine Related FW 1 9 0 Units RPM Comm object 10006 Related applications AMF MRS Description Requested engine speed Speed Required RPM 6 back to List of values Group Ge...

Страница 459: ...f values Value group Generator Related FW 1 9 0 Units V Comm object 9629 Related applications AMF MRS Description Generator phase to phase voltage between L2 and L3 phases Generator Voltage L2 L3 6 back to List of values Value group Generator Related FW 1 9 0 Units V Comm object 8193 Related applications AMF MRS Description Generator voltage on phase 2 Generator Voltage L2 N 6 back to List of valu...

Страница 460: ...ist of values Value group Generator Related FW 1 9 0 Units V Comm object 9018 Related applications AMF MRS Description Generator nominal power Nominal Power 6 back to List of values Value group Generator Related FW 1 9 0 Units V Comm object 9917 Related applications AMF MRS Description Generator nominal voltage Nominal Voltage 6 back to List of values Value group Generator Related FW 1 9 0 Units A...

Страница 461: ...witch into one decimal power format via InteliConfig PC tool In this case the range of value is decrease 10 times Load A L2 6 back to List of values Value group Load Related FW 1 9 0 Units A Comm object 8200 Related applications AMF MRS Description Load current phase L3 Note This value can be also switch into one decimal power format via InteliConfig PC tool In this case the range of value is decr...

Страница 462: ... is capacitive and R is resistive load power factor 1 Load Characteristic L2 6 back to List of values Value group Load Related FW 1 9 0 Units Comm object 8628 Related applications AMF MRS Description Character of the generator load in the L3 phase L means inductive load C is capacitive and R is resistive load power factor 1 Load Characteristic L3 6 back to List of values Value group Load Related F...

Страница 463: ...t via InteliConfig PC tool In this case the range of value is decrease 10 times Load kVA L2 6 back to List of values Value group Load Related FW 1 9 0 Units kVA Comm object 8532 Related applications AMF MRS Description Load apparent power L3 Note This value can be also switch into one decimal power format via InteliConfig PC tool In this case the range of value is decrease 10 times Load kVA L3 6 b...

Страница 464: ...er format via InteliConfig PC tool In this case the range of value is decrease 10 times Load kVAr L2 6 back to List of values Value group Load Related FW 1 9 0 Units kVAr Comm object 8529 Related applications AMF MRS Description Load reactive power in phase L3 Note This value can be also switch into one decimal power format via InteliConfig PC tool In this case the range of value is decrease 10 ti...

Страница 465: ... in phase L2 Note This value can be also switch into one decimal power format via InteliConfig PC tool In this case the range of value is decrease 10 times Load kW L2 6 back to List of values Value group Load Related FW 1 9 0 Units kW Comm object 8526 Related applications AMF MRS Description Load active power in phase L3 Note This value can be also switch into one decimal power format via InteliCo...

Страница 466: ... Description Generator power factor in phase L3 Load Power Factor L3 6 back to List of values Group Dual Operation Value group Dual Operation Related FW 1 9 0 Units Comm object 16046 Related applications AMF MRS Description This value shows how long it will take until the swap between gen sets will be made Running Hours To Swap 6 back to List of values Value group Dual Operation Related FW 1 9 0 U...

Страница 467: ...the controller Analog Input 1 6 back to List of values Value group Controler I O Related FW 1 9 0 Units Configurable Comm object 9152 Related applications AMF MRS Description This is the value of the analog input 2 of the controller Analog Input 2 6 back to List of values Value group Controler I O Related FW 1 9 0 Units Configurable Comm object 9153 Related applications AMF MRS Description This is...

Страница 468: ...lated applications AMF MRS Description State of the binary inputs of the controller Binary Inputs 6 back to List of values Value group Controler I O Related FW 1 9 0 Units Comm object 8239 Related applications AMF MRS Description State of the binary outputs of the controller Binary Outputs 6 back to List of values Value group Controler I O Related FW 1 9 0 Units V Comm object 10603 Related applica...

Страница 469: ... of gen set active power Note This value can be also switch into one decimal power format via InteliConfig PC tool In this case the range of value is decrease 10 times Genset kWh 6 back to List of values Value group Statistics Related FW 1 9 0 Units hours Comm object 11616 Related applications AMF MRS Description Countdown until next maintenance 1 Initial value can be set in Maintenance Timer 1 pa...

Страница 470: ...tatistics Related FW 1 9 0 Units Comm object 8207 Related applications AMF MRS Description Engine start commands counter The counter is increased by 1 even if the particular start command will take more than one attempt Num Starts 6 back to List of values Value group Statistics Related FW 1 9 0 Units Comm object 10986 Related applications AMF MRS Description This is the value of PULSE COUNTER 1 PA...

Страница 471: ...ues Value group Statistics Related FW 1 9 0 Units hours Comm object 8206 Related applications AMF MRS Description Engine operation hours counter The engine hours are incremented in the controller while the engine is running Running Hours 6 back to List of values Value group Statistics Related FW 1 9 0 Units Comm object 11196 Related applications AMF MRS Description Shutdown alarms counter This cou...

Страница 472: ...ion Assessment in hours when the fuel tank will be empty Note This value is based on setpoint Fuel Tank Volume page 216 and value from ECU Fuel Rate For correct calculation of this value is necessary to have configured ECU which send Fuel Rate value otherwise this value can t be calculated Time Till Empty 6 back to List of values Value group Statistics Related FW 1 9 0 Units minutes Comm object 13...

Страница 473: ...uel Tank Volume page 216 and fuel level sensor Total Fuel Consumption 6 back to List of values Group IL Info Value group IL Info Related FW 1 9 0 Units Comm object 8480 Related applications AMF MRS Description The value contains actual application in controller Application 6 back to List of values Value group IL Info Related FW 1 9 0 Units Comm object 9245 Related applications AMF MRS Description ...

Страница 474: ...ted FW 1 9 0 Units Comm object 24339 Related applications AMF MRS Description Major and minor firmware version number FW Version 6 back to List of values Value group IL Info Related FW 1 9 0 Units Comm object 24501 Related applications AMF MRS Description Name of controller which is used in InteliConfig in command bar ID String 6 back to List of values Value group IL Info Related FW 1 9 0 Units Co...

Страница 475: ...ications AMF MRS Description The value contains the numeric code of the Current process timer text which is shown on the main screen of the controller The assignment of texts to the codes can be obtained using InteliConfig Open any connection also offline with a previously saved archive and go to the Tools ribbon Generate CFG image all The resulting file will contain the assignment of texts to the...

Страница 476: ...tputs Log Bout 2 6 back to List of values Value group Log Bout Related FW 1 9 0 Units Comm object 9145 Related applications AMF MRS Description State of binary outputs Log Bout 3 6 back to List of values Value group Log Bout Related FW 1 9 0 Units Comm object 9146 Related applications AMF MRS Description State of binary outputs Log Bout 4 6 back to List of values Value group Log Bout Related FW 1 ...

Страница 477: ... Bout 7 6 back to List of values Value group Log Bout Related FW 1 9 0 Units Comm object 9150 Related applications AMF MRS Description State of binary outputs Log Bout 8 6 back to List of values Value group Log Bout Related FW 1 9 0 Units Comm object 11896 Related applications AMF MRS Description State of binary outputs Log Bout 9 6 back to List of values Value group Log Bout Related FW 1 9 0 Unit...

Страница 478: ...ck to List of values Group CM GPRS Value group CM GPRS CM 4G GPS 4G part Related FW 1 9 0 Units Comm object 24308 Related applications AMF MRS Description Diagnostic code for AirGate connection Helps in troubleshooting Code Description 0 SIM card is not inserted 1 Controller registered waiting for authorization 2 Not possible to register controller blacklisted 3 Not possible to register server has...

Страница 479: ...lues Value group CM GPRS CM 4G GPS 4G part Related FW 1 9 0 Units Comm object 24288 Related applications AMF MRS Description Diagnostic code for the CM GPRS or CM 4G GPS module Code Description 0 OK No error 1 Not possible to hang up 2 Modul is switched off 3 Module is switched on 4 Module error in initialization 5 Module not possible to set the APN 6 Module not possible to connect to GPRS network...

Страница 480: ... can t detect module speed 24 SIMCom HW reset issued 25 PUK is required 26 Error of SIM card detected 27 ME909s can t set module bps 28 ME909s can t set link configuration 29 ME909s can t do power off 30 ME909s can t do power on 31 ME909s can t do hardware reset 32 ME909s ME909s not started 33 ME909s switch off issued 34 ME909s switch on issued 35 ME909s HW reset issued 36 ME909s can t switch echo...

Страница 481: ... GPRS CM 4G GPS 4G part Related FW 1 9 0 Units Comm object 24302 Related applications AMF MRS Description This value contains information about relative strength of the cellular signal received by the CM GPRS module or by CM 4G GPS module It is a relative value helping to find the best signal and for troubleshooting cases Cell Signal Lev 6 back to List of values Value group CM GPRS CM 4G GPS 4G pa...

Страница 482: ...d 7 Command can t be send 8 HELO command was refused 11 AUTH LOGIN command was refused 12 Wrong user name 13 Wrong password 14 MAIL FROM command was refused 15 RCPT TO command was refused 16 DATA command was refused 17 Sending of email failed 18 SMTP server refused the data of email 19 SMTP server refused the data of email 20 QUIT command was refused 21 Lost of connection 23 Error during closing t...

Страница 483: ...on Actual GPS altitude Altitude 6 back to List of values Value group CM 4G GPS GPS part Related FW 1 9 0 Units km Comm object 11680 Related applications AMF MRS Description Actual distance from home position Home position is adjusted via setpoints Home Latitude page 322 and Home Longitude page 322 or by binary input GEO HOME POSITION PAGE 530 HomePosDist 6 back to List of values Value group CM 4G ...

Страница 484: ...Value group CM 4G GPS GPS part Related FW 1 9 0 Units Comm object 24265 Related applications AMF MRS Description Number of available satellites for GPS location Satellites 6 back to List of values Value group CM GPRS CM 4G GPS 4G part Related FW 1 9 0 Units Comm object 24309 Related applications AMF MRS Description Identification string generated by AirGate server for the purpose of establishing c...

Страница 485: ...other reason 5 Controller registered and authorized AirGate Status 6 back to List of values Value group CM GPRS CM 4G GPS 4G part Related FW 1 9 0 Units Comm object 24146 Related applications AMF MRS Description The type of data connection Connection Type 6 back to List of values Value group CM GPRS CM 4G GPS 4G part Related FW 1 9 0 Units Comm object 24288 Related applications AMF MRS Description...

Страница 486: ...er to complement initialization string 17 Not possible to read GSM signal strength 18 CDMA modem not detected 19 No CDMA network 20 Unsuccessful registration to CDMA network 21 SIMCom ME909s can t read FW version 22 SIMCom GSM signal not found 23 SIMCom can t detect module speed 24 SIMCom HW reset issued 25 PUK is required 26 Error of SIM card detected 27 ME909s can t set module bps 28 ME909s can ...

Страница 487: ...igher quality of signal Cell ErrorRate 6 back to List of values Value group CM GPRS CM 4G GPS 4G part Related FW 1 9 0 Units Comm object 24302 Related applications AMF MRS Description This value contains information about relative strength of the cellular signal received by the CM GPRS module or by CM 4G GPS module It is a relative value helping to find the best signal and for troubleshooting case...

Страница 488: ...d 7 Command can t be send 8 HELO command was refused 11 AUTH LOGIN command was refused 12 Wrong user name 13 Wrong password 14 MAIL FROM command was refused 15 RCPT TO command was refused 16 DATA command was refused 17 Sending of email failed 18 SMTP server refused the data of email 19 SMTP server refused the data of email 20 QUIT command was refused 21 Lost of connection 23 Error during closing t...

Страница 489: ...or AirGate connection Helps in troubleshooting Code Description 0 Ethernet cable is disconnected 1 Controller registered waiting for authorization 2 Not possible to register controller blacklisted 3 Not possible to register server has no more capacity 4 Not possible to register other reason 5 Controller registered and authorized AirGate Status 6 back to List of values Value group CM EthernetInfo R...

Страница 490: ...plications AMF MRS Description Current status of ethernet communication ETH Interface Status 6 back to List of values Value group CM Ethernet Related FW 1 9 0 Units Comm object 24182 Related applications AMF MRS Description Current gateway address Current Gateway 6 back to List of values Value group CM Ethernet Related FW 1 9 0 Units Comm object 24184 Related applications AMF MRS Description Curre...

Страница 491: ...ame 13 Wrong password 14 MAIL FROM command was refused 15 RCPT TO command was refused 16 DATA command was refused 17 Sending of email failed 20 QUIT command was refused 25 It is impossible to create data for command DATA 26 It is impossible to read data for command DATA 27 Email address can t be read 30 SMTP server address translation error from DNS server 31 Error reading email content data 24327...

Страница 492: ...Comm object 24554 Related applications AMF MRS Description Shows setup time Time 6 back to List of values Value group Date Time Related FW 1 9 0 Units DD MM YYYY Comm object 24553 Related applications AMF MRS Description Shows setup date Date 6 back to List of values Group Plug In I O Value group Plug In I O Related FW 1 9 0 Units Comm object 14291 Related applications AMF MRS Description Binary i...

Страница 493: ...st of values Value group PLC Related FW 1 9 0 Units Comm object 10505 Related applications AMF MRS Description Internal state of PLC countdowns e g state of block Timer etc PLC Resource 2 6 back to List of values Value group PLC Related FW 1 9 0 Units Comm object 10506 Related applications AMF MRS Description Internal state of PLC countdowns e g state of block Timer etc PLC Resource 3 6 back to Li...

Страница 494: ...ource 6 6 back to List of values Value group PLC Related FW 1 9 0 Units Comm object 10510 Related applications AMF MRS Description Internal state of PLC countdowns e g state of block Timer etc PLC Resource 7 6 back to List of values Value group PLC Related FW 1 9 0 Units Comm object 10511 Related applications AMF MRS Description Internal state of PLC countdowns e g state of block Timer etc PLC Res...

Страница 495: ... BOUT 3 6 back to List of values Value group PLC Related FW 1 9 0 Units Comm object 10427 Related applications AMF MRS Description State of binary outputs of PLC PLC BOUT 4 6 back to List of values Value group PLC Related FW 1 9 0 Units Comm object 10428 Related applications AMF MRS Description State of binary outputs of PLC PLC BOUT 5 6 back to List of values Value group PLC Related FW 1 9 0 Unit...

Страница 496: ...InteliLite Global Guide 496 Value group PLC Related FW 1 9 0 Units Comm object 10430 Related applications AMF MRS Description State of binary outputs of PLC PLC BOUT 7 6 back to List of values ...

Страница 497: ...binary values and functions Alphabetical groups of Logical binary inputs LBI A 499 LBI B 500 LBI C 524 LBI D 526 LBI E 527 LBI F 528 LBI G 529 LBI H 531 LBI I 531 LBI L 532 LBI N 533 LBI O 534 LBI P 534 LBI R 535 LBI S 537 For full list of Logical binary inputs go to the chapter Logical binary inputs alphabetically page 498 ...

Страница 498: ... BIN Protection 33 516 BIN Protection 34 517 BIN Protection 35 517 BIN Protection 36 518 BIN Protection 37 518 BIN Protection 38 519 BIN Protection 39 519 BIN Protection 40 520 BIN Protection 41 520 BIN Protection 42 521 BIN Protection 43 521 BIN Protection 44 522 BIN Protection 45 522 BIN Protection 46 523 BIN Protection 47 523 BIN Protection 48 524 Choke Inhibit 524 Coolant Temp 525 Dark Mode 52...

Страница 499: ...can switch between configuration sets When this binary input is active setpoints in Alternate Config group are switched to the second set setpoints with number 2 IMPORTANT If LBO ECU POWER RELAY PAGE 570 is used change of alternate configuration can be made only in prestart phase So prestart has to be set up for enough long time Alternate Config 2 6 back to Logical binary inputs alphabetically Rel...

Страница 500: ...MRS Comm object 9999 Description This binary input is for general input function used as alarm Monitoring Binary input is not used for protection or any other function Signal is only monitored HistRecOnl Binary input is not used for protection Only history record is made if binary input is active AL Indic Binary input is not used for protection Only alarmlist record is made if binary input is acti...

Страница 501: ... is used for shutdown protection Protection types BIN Protection 02 6 back to Logical binary inputs alphabetically Related FW 1 9 0 Related applications AMF MRS Comm object 9997 Description This binary input is for general input function used as alarm Monitoring Binary input is not used for protection or any other function Signal is only monitored HistRecOnl Binary input is not used for protection...

Страница 502: ... is used for shutdown protection Protection types BIN Protection 04 6 back to Logical binary inputs alphabetically Related FW 1 9 0 Related applications AMF MRS Comm object 9995 Description This binary input is for general input function used as alarm Monitoring Binary input is not used for protection or any other function Signal is only monitored HistRecOnl Binary input is not used for protection...

Страница 503: ... is used for shutdown protection Protection types BIN Protection 06 6 back to Logical binary inputs alphabetically Related FW 1 9 0 Related applications AMF MRS Comm object 9993 Description This binary input is for general input function used as alarm Monitoring Binary input is not used for protection or any other function Signal is only monitored HistRecOnl Binary input is not used for protection...

Страница 504: ... is used for shutdown protection Protection types BIN Protection 08 6 back to Logical binary inputs alphabetically Related FW 1 9 0 Related applications AMF MRS Comm object 9991 Description This binary input is for general input function used as alarm Monitoring Binary input is not used for protection or any other function Signal is only monitored HistRecOnl Binary input is not used for protection...

Страница 505: ... is used for shutdown protection Protection types BIN Protection 10 6 back to Logical binary inputs alphabetically Related FW 1 9 0 Related applications AMF MRS Comm object 9989 Description This binary input is for general input function used as alarm Monitoring Binary input is not used for protection or any other function Signal is only monitored HistRecOnl Binary input is not used for protection...

Страница 506: ... is used for shutdown protection Protection types BIN Protection 12 6 back to Logical binary inputs alphabetically Related FW 1 9 0 Related applications AMF MRS Comm object 9987 Description This binary input is for general input function used as alarm Monitoring Binary input is not used for protection or any other function Signal is only monitored HistRecOnl Binary input is not used for protection...

Страница 507: ... is used for shutdown protection Protection types BIN Protection 14 6 back to Logical binary inputs alphabetically Related FW 1 9 0 Related applications AMF MRS Comm object 9985 Description This binary input is for general input function used as alarm Monitoring Binary input is not used for protection or any other function Signal is only monitored HistRecOnl Binary input is not used for protection...

Страница 508: ... is used for shutdown protection Protection types BIN Protection 16 6 back to Logical binary inputs alphabetically Related FW 1 9 0 Related applications AMF MRS Comm object 9983 Description This binary input is for general input function used as alarm Monitoring Binary input is not used for protection or any other function Signal is only monitored HistRecOnl Binary input is not used for protection...

Страница 509: ... is used for shutdown protection Protection types BIN Protection 18 6 back to Logical binary inputs alphabetically Related FW 1 9 0 Related applications AMF MRS Comm object 9981 Description This binary input is for general input function used as alarm Monitoring Binary input is not used for protection or any other function Signal is only monitored HistRecOnl Binary input is not used for protection...

Страница 510: ... is used for shutdown protection Protection types BIN Protection 20 6 back to Logical binary inputs alphabetically Related FW 1 9 0 Related applications AMF MRS Comm object 9979 Description This binary input is for general input function used as alarm Monitoring Binary input is not used for protection or any other function Signal is only monitored HistRecOnl Binary input is not used for protection...

Страница 511: ... is used for shutdown protection Protection types BIN Protection 22 6 back to Logical binary inputs alphabetically Related FW 1 9 0 Related applications AMF MRS Comm object 9977 Description This binary input is for general input function used as alarm Monitoring Binary input is not used for protection or any other function Signal is only monitored HistRecOnl Binary input is not used for protection...

Страница 512: ... is used for shutdown protection Protection types BIN Protection 24 6 back to Logical binary inputs alphabetically Related FW 1 9 0 Related applications AMF MRS Comm object 9975 Description This binary input is for general input function used as alarm Monitoring Binary input is not used for protection or any other function Signal is only monitored HistRecOnl Binary input is not used for protection...

Страница 513: ... is used for shutdown protection Protection types BIN Protection 26 6 back to Logical binary inputs alphabetically Related FW 1 9 0 Related applications AMF MRS Comm object 9973 Description This binary input is for general input function used as alarm Monitoring Binary input is not used for protection or any other function Signal is only monitored HistRecOnl Binary input is not used for protection...

Страница 514: ... is used for shutdown protection Protection types BIN Protection 28 6 back to Logical binary inputs alphabetically Related FW 1 9 0 Related applications AMF MRS Comm object 9971 Description This binary input is for general input function used as alarm Monitoring Binary input is not used for protection or any other function Signal is only monitored HistRecOnl Binary input is not used for protection...

Страница 515: ... is used for shutdown protection Protection types BIN Protection 30 6 back to Logical binary inputs alphabetically Related FW 1 9 0 Related applications AMF MRS Comm object 9969 Description This binary input is for general input function used as alarm Monitoring Binary input is not used for protection or any other function Signal is only monitored HistRecOnl Binary input is not used for protection...

Страница 516: ... is used for shutdown protection Protection types BIN Protection 32 6 back to Logical binary inputs alphabetically Related FW 1 9 0 Related applications AMF MRS Comm object 9967 Description This binary input is for general input function used as alarm Monitoring Binary input is not used for protection or any other function Signal is only monitored HistRecOnl Binary input is not used for protection...

Страница 517: ... is used for shutdown protection Protection types BIN Protection 34 6 back to Logical binary inputs alphabetically Related FW 1 9 0 Related applications AMF MRS Comm object 9965 Description This binary input is for general input function used as alarm Monitoring Binary input is not used for protection or any other function Signal is only monitored HistRecOnl Binary input is not used for protection...

Страница 518: ... is used for shutdown protection Protection types BIN Protection 36 6 back to Logical binary inputs alphabetically Related FW 1 9 0 Related applications AMF MRS Comm object 9963 Description This binary input is for general input function used as alarm Monitoring Binary input is not used for protection or any other function Signal is only monitored HistRecOnl Binary input is not used for protection...

Страница 519: ... is used for shutdown protection Protection types BIN Protection 38 6 back to Logical binary inputs alphabetically Related FW 1 9 0 Related applications AMF MRS Comm object 9961 Description This binary input is for general input function used as alarm Monitoring Binary input is not used for protection or any other function Signal is only monitored HistRecOnl Binary input is not used for protection...

Страница 520: ... is used for shutdown protection Protection types BIN Protection 40 6 back to Logical binary inputs alphabetically Related FW 1 9 0 Related applications AMF MRS Comm object 9959 Description This binary input is for general input function used as alarm Monitoring Binary input is not used for protection or any other function Signal is only monitored HistRecOnl Binary input is not used for protection...

Страница 521: ... is used for shutdown protection Protection types BIN Protection 42 6 back to Logical binary inputs alphabetically Related FW 1 9 0 Related applications AMF MRS Comm object 9957 Description This binary input is for general input function used as alarm Monitoring Binary input is not used for protection or any other function Signal is only monitored HistRecOnl Binary input is not used for protection...

Страница 522: ... is used for shutdown protection Protection types BIN Protection 44 6 back to Logical binary inputs alphabetically Related FW 1 9 0 Related applications AMF MRS Comm object 9955 Description This binary input is for general input function used as alarm Monitoring Binary input is not used for protection or any other function Signal is only monitored HistRecOnl Binary input is not used for protection...

Страница 523: ... is used for shutdown protection Protection types BIN Protection 46 6 back to Logical binary inputs alphabetically Related FW 1 9 0 Related applications AMF MRS Comm object 9953 Description This binary input is for general input function used as alarm Monitoring Binary input is not used for protection or any other function Signal is only monitored HistRecOnl Binary input is not used for protection...

Страница 524: ...is active Wrn Binary input is used for warning protection only BOC Binary input is used for BOC Breaker Open and Cooling protection Sd Binary input is used for shutdown protection Protection types BIN Protection 48 6 back to Logical binary inputs alphabetically LBI C Related FW 1 9 0 Related applications AMF MRS Comm object 946 Description Logical binary input CHOKE INHIBIT prevent Choke functiona...

Страница 525: ...is not used for protection or any other function Signal is only monitored HistRecOnl Binary input is not used for protection Only history record is made if binary input is active Wrn Binary input is used for warning protection only BOC Binary input is used for BOC Breaker Open and Cooling protection Sd Binary input is used for shutdown protection Protection types Coolant Temp 6 back to Logical bin...

Страница 526: ... in dual operation This LBI has higher priority then setpoint Swap Gen sets page 240 This LBI is accepted only in Master controller Dual Swap Gen sets 6 back to Logical binary inputs alphabetically Related FW 1 9 0 Related applications AMF MRS Comm object 954 Description This LBI defines which gen set has higher priority in dual operation mode If this LBI is active on one gen set this gen set is u...

Страница 527: ...tpoint ECU Speed Adjustment page 226 by binary inputs When the LBI is activated the setpoint is increase by 2 ECU Speed Up 6 back to Logical binary inputs alphabetically Related FW 1 9 0 Related applications AMF MRS Comm object 45 Description This input is designed to allow the gen set or breakers to be controlled externally not by the controller This feature can be useful in case of some failure ...

Страница 528: ...als For more detail see chapter recommended wiring Emergency Stop 6 back to Logical binary inputs alphabetically LBI F Related FW 1 9 0 Related applications AMF MRS Comm object 191 Description Binary input has the same function as Fault Reset button on the InteliLite front panel Fault Reset Button 6 back to Logical binary inputs alphabetically Related FW 1 9 0 Related applications AMF MRS Comm obj...

Страница 529: ... output FUEL PUMP PAGE 572 The output is deactivated automatically as soon as fuel level reaches 100 Note This binary input is basically designed for ON and OFF switch switch with arrestment in these positions because controller reacts to rising and falling edge of signal in this input IMPORTANT When binary input FUEL PUMP ON OFF PAGE 529 is configured then binary output FUEL PUMP PAGE 572 is cont...

Страница 530: ...not configure the feedback to binary inputs GCB Feedback 6 back to Logical binary inputs alphabetically Related FW 1 9 0 Related applications AMF MRS Comm object 219 Description This binary input can be used to adjust home position of gen set In case that binary input is active setpoints Home Latitude page 322 and Home Longitude page 322 are adjusted automatically from actual coordinates from GPS ...

Страница 531: ... 6 back to Logical binary inputs alphabetically LBI H Related FW 1 9 0 Related applications AMF MRS Comm object 192 Description Binary input has the same function as Horn reset button on the InteliLite front panel Horn Reset Button 6 back to Logical binary inputs alphabetically LBI I Related FW 1 9 0 Related applications AMF MRS Comm object 624 Description This binary input changes cooling speed f...

Страница 532: ...d LANG SELECTION 3 PAGE 533 are active 5 Fifth language Lang Selection 1 6 back to Logical binary inputs alphabetically Related FW 1 9 0 Related applications AMF MRS Comm object 108 Description Use this binary input with binary input LANG SELECTION 1 PAGE 532 and LANG SELECTION 3 PAGE 533 to choose required language of controller The system is based on binary numbers Binary input Binary number Act...

Страница 533: ...nguage English LANG SELECTION 2 PAGE 532 is active 2 Second language Language Selection 1 and LANG SELECTION 2 PAGE 532 are active 3 Third language Lang Selection 3 page 1 is active 4 Fourth language LANG SELECTION 1 PAGE 532 and Lang Selection 3 page 1 are active 5 Fifth language Lang Selection 3 6 back to Logical binary inputs alphabetically LBI N Related FW 1 9 0 Related applications AMF MRS Co...

Страница 534: ...o use binary input of oil pressure sensor just for protection please use one of the BIN PROTECTION 1 PAGE 500 Oil Pressure 6 back to Logical binary inputs alphabetically LBI P Related FW 1 9 0 Related applications AMF MRS Comm object 920 Description This logic binary input enables or disables protections adjusted as LBI Enable Protection Enable 6 back to Logical binary inputs alphabetically Relate...

Страница 535: ... to ECU Note ECU with Tier IV support is required for proper functionality Regeneration Inhib 6 back to Logical binary inputs alphabetically Related FW 1 9 0 Related applications AMF MRS Comm object 620 Description The controller is switched to the AUTO mode there are four modes OFF MAN AUTO TEST when this binary input is closed When opens controller is switched back to previous mode This binary i...

Страница 536: ...s alphabetically Related FW 1 9 0 Related applications AMF MRS Comm object 617 Description The controller is switched to the OFF mode there are four modes OFF MAN AUTO TEST when this binary input is closed When opens controller is switched back to previous mode Remote control priority Remote OFF Highest priority Remote TEST Remote MAN Remote AUTO Lowest Priority Remote OFF 6 back to Logical binary...

Страница 537: ...ne is not protected IMPORTANT MISUSE OF THIS INPUT CAN CAUSE DAMAGE TO THE GEN SET Sd Override 6 back to Logical binary inputs alphabetically Related FW 1 9 0 Related applications AMF MRS Comm object 189 Description Binary input has the same function as Start Button on the InteliLite front panel It is evaluated in MAN mode only Start Button 6 back to Logical binary inputs alphabetically Related FW...

Страница 538: ...ry values and functions Alphabetical groups of Logical binary outputs LBO A 541 LBO B 564 LBO C 567 LBO D 568 LBO E 569 LBO F 572 LBO G 574 LBO H 581 LBO I 582 LBO M 584 LBO N 584 LBO P 585 LBO R 587 LBO S 596 LBO T 600 LBO V 600 For full list of Logical binary outputs go to the chapter Logical binary outputs alphabetically page 539 ...

Страница 539: ... Wrn 550 AL Overspeed 550 AL Rental Timer 1 551 AL Rental Timer 2 551 AL Start Fail 552 AL Stop Fail 552 AL Underspeed 552 Alarm 552 AIN Switch01 553 AIN Switch02 553 AIN Switch03 554 AIN Switch04 554 AIN Switch05 555 AIN Switch06 555 AIN Switch07 556 AIN Switch08 556 AIN Switch09 557 AIN Switch10 557 AIN Switch11 558 AIN Switch12 558 AIN Switch13 559 AIN Switch14 559 AIN Switch15 560 AIN Switch16...

Страница 540: ... 04 589 Remote Control 05 590 Remote Control 06 590 Remote Control 07 591 Remote Control 08 591 Remote Control 09 592 Remote Control 10 592 Remote Control 11 593 Remote Control 12 593 Remote Control 13 594 Remote Control 14 594 Remote Control 15 595 Remote Control 16 595 Running 596 Sd Override 596 Starter 597 Still Log 0 597 Still Log 1 597 Stop Pulse 598 Stop Solenoid 598 Supplying Load 599 Swap...

Страница 541: ... 0 Related applications AMF MRS Comm object 1386 Description The output is closed when there is the shutdown or BOC alarm from the analog input 1 of the controller present in the alarmlist or isn t confirmed AL AIN 1 Sd BOC 6 back to Logical binary outputs alphabetically Related FW 1 9 0 Related applications AMF MRS Comm object 1382 Description The output is closed when there is the warning alarm ...

Страница 542: ...lications AMF MRS Comm object 1388 Description The output is closed when there is the shutdown or BOC alarm from the analog input 3 of the controller present in the alarmlist or isn t confirmed AL AIN 3 Sd BOC 6 back to Logical binary outputs alphabetically Related FW 1 9 0 Related applications AMF MRS Comm object 1384 Description The output is closed when there is the warning alarm from the analo...

Страница 543: ...cally Related FW 1 9 0 Related applications AMF MRS Comm object 1272 Description This output is active when the Battery Charger Fail page 652 alarm is present in the alarmlist or isn t confirmed AL Battery Charger 6 back to Logical binary outputs alphabetically Related FW 1 9 0 Related applications AMF MRS Comm object 1995 Description This output is active when the Wrn Battery Voltage page 655 ala...

Страница 544: ...No BOC alarm is active and Fault reset button is pressed AL Common BOC 6 back to Logical binary outputs alphabetically Related FW 1 9 0 Related applications AMF MRS Comm object 6 Description Output closes when any sensor fail alarm appears The output opens if No sensor fail alarm is active and Fault reset button is pressed AL Common Fls 6 back to Logical binary outputs alphabetically Related FW 1 ...

Страница 545: ...oolantTemp Low 6 Logical binary outputs alphabetically page 539 Related FW 1 9 0 Related applications AMF MRS Comm object 1421 Description The output is closed when there is the shutdown or BOC alarm from the COOLANT TEMP PAGE 631 in the alarmlist or isn t confirmed AL CoolantTemp Sd 6 Logical binary outputs alphabetically page 539 Related FW 1 9 0 Related applications AMF MRS Comm object 1420 Des...

Страница 546: ...is active when there is alarm of 2nd level on Slave controller AL Dual Slave Fail 6 back to Logical binary outputs alphabetically Related FW 1 9 0 Related applications AMF MRS Comm object 1294 Description This output is active when the Sd Earth Fault Current page 674 alarm is present in alarm list or isn t confirm Note It is strongly recommended to use this output only onetime AL Earth Fault 6 bac...

Страница 547: ...elated applications AMF MRS Comm object 1422 Description The output is closed when there is the warning alarm from the FUEL LEVEL PAGE 632 in the alarmlist or isn t confirmed Note Binary output is also active if protection type is set to HistRecOnl and threshold level for history record is reach AL Fuel Level Wrn 6 back to Logical binary outputs alphabetically Related FW 1 9 0 Related applications...

Страница 548: ... 0 Related applications AMF MRS Comm object 1265 Description This output is active when at least one generator underfrequency alarm is present in alarmlist or isn t confirm AL Gen Underfrequency 6 back to Logical binary outputs alphabetically Related FW 1 9 0 Related applications AMF MRS Comm object 1262 Description This output is active when at least one generator undervoltage alarm is present in...

Страница 549: ...MRS Comm object 1255 Description This output is active when the Alarm Maintenance 2 is present in the alarmlist It means that counter of maintenance is on zero or the Alarm Maintenance 2 isn t confirm AL Maintenance 2 6 back to Logical binary outputs alphabetically Related FW 1 9 0 Related applications AMF MRS Comm object 1256 Description This output is active when the Alarm Maintenance 3 is prese...

Страница 550: ...ist or isn t confirm AL Overcurrent 6 back to Logical binary outputs alphabetically Related FW 1 9 0 Related applications AMF MRS Comm object 1268 Description This output is active when the Sd Overload page 681 alarm is present in the alarmlist or isn t confirm AL Overload BOC 6 back to Logical binary outputs alphabetically Related FW 1 9 0 Related applications AMF MRS Comm object 1269 Description...

Страница 551: ...er 1 page 317 elapsed Image 8 131 Rental Timer 1 AL Rental Timer 1 6 back to Logical binary outputs alphabetically Related FW 1 9 0 Related applications AMF MRS Comm object 1371 Description The binary output closes when the Rental Timer 2 page 319 elapsed Image 8 132 Rental Timer 2 AL Rental Timer 2 6 back to Logical binary outputs alphabetically ...

Страница 552: ...Fail 6 back to Logical binary outputs alphabetically Related FW 1 9 0 Related applications AMF MRS Comm object 1296 Description This output is active when the Sd Underspeed page 682 alarm is present in the alarmlist or isn t confirm AL Underspeed 6 back to Logical binary outputs alphabetically Related FW 1 9 0 Related applications AMF MRS Comm object 2 Description The output is designed to be used...

Страница 553: ...nalog input Image 8 133 General analog input 1 switch AIN Switch01 6 back to Logical binary outputs alphabetically Related FW 1 9 0 Related applications AMF MRS Comm object 1401 Description This is an output from the General Analog Input 2 switch function The behavior of the switch depends on the adjustment of the setpoints Analog Switch 2 On page 246 and Analog Switch 2 Off page 247 The value is ...

Страница 554: ...nalog input Image 8 135 General analog input 3 switch AIN Switch03 6 back to Logical binary outputs alphabetically Related FW 1 9 0 Related applications AMF MRS Comm object 1403 Description This is an output from the General Analog Input 4 switch function The behavior of the switch depends on the adjustment of the setpoints Analog Switch 4 On page 252 and Analog Switch 4 Off page 253 The value is ...

Страница 555: ...alog input Image 8 137 General analog input 5 switch AIN Switch05 6 Logical binary outputs alphabetically page 539 Related FW 1 9 0 Related applications AMF MRS Comm object 1788 Description This is an output from the General Analog Input 6 switch function The behavior of the switch depends on the adjustment of the setpoints Analog Switch 6 On page 258 and Analog Switch 6 Off page 259 The value is ...

Страница 556: ...alog input Image 8 139 General analog input 7 switch AIN Switch07 6 Logical binary outputs alphabetically page 539 Related FW 1 9 0 Related applications AMF MRS Comm object 1790 Description This is an output from the General Analog Input 8 switch function The behavior of the switch depends on the adjustment of the setpoints Analog Switch 8 On page 264 and Analog Switch 8 Off page 265 The value is ...

Страница 557: ...og input Image 8 141 General analog input 9 switch AIN Switch09 6 Logical binary outputs alphabetically page 539 Related FW 1 9 0 Related applications AMF MRS Comm object 1792 Description This is an output from the General Analog Input 10 switch function The behavior of the switch depends on the adjustment of the setpoints Analog Switch 10 On page 270 and Analog Switch 10 Off page 271 The value is...

Страница 558: ...log input Image 8 143 General analog input 11 switch AIN Switch11 6 Logical binary outputs alphabetically page 539 Related FW 1 9 0 Related applications AMF MRS Comm object 1794 Description This is an output from the General Analog Input 12 switch function The behavior of the switch depends on the adjustment of the setpoints Analog Switch 12 On page 276 and Analog Switch 12 Off page 277 The value ...

Страница 559: ...log input Image 8 145 General analog input 13 switch AIN Switch13 6 Logical binary outputs alphabetically page 539 Related FW 1 9 0 Related applications AMF MRS Comm object 1796 Description This is an output from the General Analog Input 14 switch function The behavior of the switch depends on the adjustment of the setpoints Analog Switch 14 On page 282 and Analog Switch 14 Off page 283 The value ...

Страница 560: ...log input Image 8 147 General analog input 15 switch AIN Switch15 6 Logical binary outputs alphabetically page 539 Related FW 1 9 0 Related applications AMF MRS Comm object 1798 Description This is an output from the General Analog Input 16 switch function The behavior of the switch depends on the adjustment of the setpoints Analog Switch 16 On page 288 and Analog Switch 16 Off page 289 The value ...

Страница 561: ...log input Image 8 149 General analog input 17 switch AIN Switch17 6 Logical binary outputs alphabetically page 539 Related FW 1 9 0 Related applications AMF MRS Comm object 1800 Description This is an output from the General Analog Input 18 switch function The behavior of the switch depends on the adjustment of the setpoints Analog Switch 18 On page 294 and Analog Switch 18 Off page 295 The value ...

Страница 562: ...ically page 539 Related FW 1 9 0 Related applications AMF MRS Comm object 1802 Description This is an output from the General Analog Input 20 switch function The behavior of the switch depends on the adjustment of the setpoints Analog Switch 20 On page 300 and Analog Switch 20 Off page 301 The value is measured from AIN SWITCH 20 PAGE 630 analog input Image 8 152 General analog input 20 switch AIN...

Страница 563: ...HEST LAMP signal binary input will be opened without no matter if alarms in alarmlist are confirmed or not ATT HEST Lamp 6 back to Logical binary outputs alphabetically Related FW 1 9 0 Related applications AMF MRS Comm object 2155 Description This output is active when ATT Inhibited Lamp is active ATT Inhibited Lamp 6 back to Logical binary outputs alphabetically Related FW 1 9 0 Related applicat...

Страница 564: ...st LBO is still active Image 8 153 Binary Input 1 Status BIN 1 Status 6 back to Logical binary outputs alphabetically Related FW 1 9 0 Related applications AMF MRS Comm object 1375 Description This output is closed when Binary Input 2 is active and open when Binary Input 2 is inactive When Binary Input 2 is used for BIN protection function then this output is closed when BIN protection alarm is in...

Страница 565: ...LBO is still active Image 8 155 Binary Input 3 Status BIN 3 Status 6 back to Logical binary outputs alphabetically Related FW 1 9 0 Related applications AMF MRS Comm object 1377 Description This output is closed when Binary Input 4 is active and open when Binary Input 4 is inactive When Binary Input 4 is used for BIN protection function then this output is closed when BIN protection alarm is in Al...

Страница 566: ...LBO is still active Image 8 157 Binary Input 5 Status BIN 5 Status 6 back to Logical binary outputs alphabetically Related FW 1 9 0 Related applications AMF MRS Comm object 1379 Description This output is closed when Binary Input 6 is active and open when Binary Input 6 is inactive When Binary Input 6 is used for BIN protection function then this output is closed when BIN protection alarm is in Al...

Страница 567: ...ist LBO is still active Image 8 159 Binary Input 7 Status BIN 7 Status 6 back to Logical binary outputs alphabetically LBO C Related FW 1 9 0 Related applications AMF MRS Comm object 2091 Description Logical binary output for choke valve control Output CHOKE is activated every time when logical binary output STARTER PAGE 597 is activated Output is deactivated when one of these conditions is fulfil...

Страница 568: ...s alphabetically Related FW 1 9 0 Related applications AMF MRS Comm object 74 Description The output closes when gen set is in Cooling state Cooling 6 back to Logical binary outputs alphabetically LBO D Related FW 1 9 0 Related applications AMF MRS Comm object 2097 Description This LBO is active when there is Dual Operation Fail page 665 alarm in alarmlist Dual Operation Error 6 back to Logical bi...

Страница 569: ...when engine is not stop ECU POWER RELAY PAGE 570 is active ECU Communic Error 6 back to Logical binary outputs alphabetically Related FW 1 9 0 Related applications AMF MRS Comm object 347 Description This output is active when an ECU is configured connected and the communication with the ECU is established Note When ECU POWER RELAY PAGE 570 is not configured output is evaluated all the time If ECU...

Страница 570: ...ECU Communication Fail page 675 or Wrn ECU Communication Fail page 656 alarms With configured LBO ECU Power Relay these alarms are evaluated only when this LBO is active Without configured LBO ECU Power Relay these alarm are evaluated all the time ECU Power Relay 6 back to Logical binary outputs alphabetically Related FW 1 9 0 Related applications AMF MRS Comm object 350 Description This output is...

Страница 571: ...eir own proprietary frames and some do not provide the flag at all ECU Yellow Lamp 6 back to Logical binary outputs alphabetically Related FW 1 9 0 Related applications AMF MRS Comm object 1250 Description This is an output from the Exercise timer 1 This output makes it easy to make periodic tests of the gen set and its activation depends on the setpoints in the Subgroup Timer 1 page 303 subgroup ...

Страница 572: ...ly Related FW 1 9 0 Related applications AMF MRS Comm object 1253 Description Output closes when the value of Fuel Level lies under the value of Fuel Pump On page 217 setpoint and opens when value of Fuel Pump Off page 218 is reached This output also can be closed by binary input FUEL PUMP ON OFF PAGE 529 In this case the binary output FUEL PUMP ON PAGE 217 is closed until the binary input FUEL PU...

Страница 573: ...ore binary output STARTER PAGE 597 The lead time is adjusted by setpoint Fuel Solenoid Lead page 198 Image 8 162 Fuel Solenoid 1 Image 8 163 Fuel Solenoid 2 The output opens when Emergency Stop comes cooled gen set is stopped in pause between repeated starts ...

Страница 574: ... Logical binary outputs alphabetically LBO G Related FW 1 9 0 Related applications AMF MRS Comm object 41 Description The output controls the generator circuit breaker Its state represents the breaker position requested by the controller The breaker must react within 5 seconds to a close or open command otherwise an alarm is issued Note InteliLite controllers can work even without breaker feedback...

Страница 575: ...InteliLite Global Guide 575 Image 8 165 GCB Close command Image 8 166 Repeated GCB Close command Image 8 167 GCB Open command 6 back to Logical binary outputs alphabetically ...

Страница 576: ...d for control of open coil of generator circuit breaker The output gives a pulse in the moment the breaker has to be opened The pulse lasts until the feedback deactivates but at least for 5 seconds Image 8 168 GCB OFF Coil command Image 8 169 GCB OFF Coil command GCB OFF Coil 6 back to Logical binary outputs alphabetically ...

Страница 577: ...east 5 second pulse in the moment the breaker has to be closed Image 8 170 GCB ON Coil close command Image 8 171 Repeated GCB ON coil close command GCB ON Coil 6 back to Logical binary outputs alphabetically Related FW 1 9 0 Related applications AMF MRS Comm object 44 Description The output is intended for control of undervoltage coil of generator circuit breaker The output is active the GCB UV Co...

Страница 578: ...the generator is running The output is deactivated for at least 5 seconds in the moment the breaker has to be switched off Image 8 172 GCB UV Coil close command Image 8 173 GCB UV Coil open command 6 back to Logical binary outputs alphabetically ...

Страница 579: ...delay after the voltage frequency voltage unbalance has got out of limits when GCB is closed Generator Healthy 6 back to Logical binary outputs alphabetically Related FW 1 9 0 Related applications AMF MRS Comm object 1252 Description This output is dedicated for diesel engine only This output will close for exact time pre set by setpoint Glow Plugs Time page 192 before every starting attempt The o...

Страница 580: ... is long as Cranking Fail Pause page 190 Image 8 175 Glow Plugs in Cranking Fail Pause 1 When the Glow Plugs Time page 192 is shorter than Cranking Fail Pause page 190 then the Glow Plugs Time page 192 in Cranking Fail Pause page 190 is long as normal Glow Plugs Time page 192 Image 8 176 Glow Plugs in Cranking Fail Pause 2 6 back to Logical binary outputs alphabetically ...

Страница 581: ...al binary outputs alphabetically Related FW 1 9 0 Related applications AMF MRS Comm object 1 Description The output designed to be used for acoustic indication of a newly appeared alarm The output is activated each time a new alarm has appeared and remains active until one of the following events occurs Fault reset is pressed Horn reset is pressed Horn Timeout page 185 has elapsed Horn 6 back to L...

Страница 582: ...nect binary output Idle Nominal to speed governor to switch the speed opened Idle closed Nominal for normally open contact type Idle Nominal 6 back to Logical binary outputs alphabetically Related FW 1 9 0 Related applications AMF MRS Comm object 37 Description This output is dedicated to controlling the ignition at a gas engine The output is closed together with binary output FUEL SOLENOID PAGE 5...

Страница 583: ...cations AMF MRS Comm object 1257 Description This input is on since start button is pressed till the unit is completely stopped or the engine doesn t start or Sd or E Stop becomes active Note This function is the same as ECU POWER RELAY PAGE 570 Ignition ON stays there from historical reasons Ignition On 6 back to Logical binary outputs alphabetically ...

Страница 584: ...enever the controller is in AUTO mode Mode AUTO 6 back to Logical binary outputs alphabetically Related FW 1 9 0 Related applications AMF MRS Comm object 18 Description This output is active whenever the controller is in MAN mode Mode MAN 6 back to Logical binary outputs alphabetically Related FW 1 9 0 Related applications AMF MRS Comm object 17 Description This output is active whenever the contr...

Страница 585: ...h depends on the adjustment of the setpoints Power Switch On page 223 and Power Switch Off page 224 When the dummy load function is used the switching ON of Power switch is block when the engine isn t running and is allowed 30 s after start of the engine Image 8 180 Power Switch Note Setpoints Power Switch On page 223 and Power Switch Off page 224 are invisible until configuration of this LBO Powe...

Страница 586: ...od of Prestart Time page 191 The output opens 100 ms before the STARTER PAGE 597 output closes Image 8 181 Engine start When the Prestart Time page 191 is longer than Cranking Fail Pause page 190 then the Prestart Time page 191 in Cranking Fail Pause page 190 is long as Cranking Fail Pause page 190 minus 100ms Image 8 182 Prestart in Cranking Fail Pause 1 ...

Страница 587: ...in limits If GCB is open then gen set voltage and frequency must be in limits If GCB is close then gen set voltage and frequency can be out of limits but protection delay can t be count down If gen set voltage and frequency will return into limits until delay is count down then output is still closed Ready To Load 6 back to Logical binary outputs alphabetically Related FW 1 9 0 Related application...

Страница 588: ...ue 0000 all switches are 0 value FFFF all switches are 1 Single register 5210 supported function 5 value 0000 switch is 0 value FF00 switch is 1 Remote Control 01 6 back to Logical binary outputs alphabetically Related FW 1 9 0 Related applications AMF MRS Comm object 2286 Description Logical binary outputs which can be controlled remotely via MODBUS There are fixed registers for MODBUS control Ho...

Страница 589: ... 5 value 0000 switch is 0 value FF00 switch is 1 Remote Control 03 6 back to Logical binary outputs alphabetically Related FW 1 9 0 Related applications AMF MRS Comm object 2288 Description Logical binary outputs which can be controlled remotely via MODBUS There are fixed registers for MODBUS control Holding register 5200 this register can adjust all switches supported function 6 value 0000 all sw...

Страница 590: ... 5 value 0000 switch is 0 value FF00 switch is 1 Remote Control 05 6 back to Logical binary outputs alphabetically Related FW 1 9 0 Related applications AMF MRS Comm object 2290 Description Logical binary outputs which can be controlled remotely via MODBUS There are fixed registers for MODBUS control Holding register 5200 this register can adjust all switches supported function 6 value 0000 all sw...

Страница 591: ... 5 value 0000 switch is 0 value FF00 switch is 1 Remote Control 07 6 back to Logical binary outputs alphabetically Related FW 1 9 0 Related applications AMF MRS Comm object 2292 Description Logical binary outputs which can be controlled remotely via MODBUS There are fixed registers for MODBUS control Holding register 5200 this register can adjust all switches supported function 6 value 0000 all sw...

Страница 592: ... 5 value 0000 switch is 0 value FF00 switch is 1 Remote Control 09 6 back to Logical binary outputs alphabetically Related FW 1 9 0 Related applications AMF MRS Comm object 2294 Description Logical binary outputs which can be controlled remotely via MODBUS There are fixed registers for MODBUS control Holding register 5200 this register can adjust all switches supported function 6 value 0000 all sw...

Страница 593: ... 5 value 0000 switch is 0 value FF00 switch is 1 Remote Control 11 6 back to Logical binary outputs alphabetically Related FW 1 9 0 Related applications AMF MRS Comm object 2296 Description Logical binary outputs which can be controlled remotely via MODBUS There are fixed registers for MODBUS control Holding register 5200 this register can adjust all switches supported function 6 value 0000 all sw...

Страница 594: ... 5 value 0000 switch is 0 value FF00 switch is 1 Remote Control 13 6 back to Logical binary outputs alphabetically Related FW 1 9 0 Related applications AMF MRS Comm object 2298 Description Logical binary outputs which can be controlled remotely via MODBUS There are fixed registers for MODBUS control Holding register 5200 this register can adjust all switches supported function 6 value 0000 all sw...

Страница 595: ... 5 value 0000 switch is 0 value FF00 switch is 1 Remote Control 15 6 back to Logical binary outputs alphabetically Related FW 1 9 0 Related applications AMF MRS Comm object 2300 Description Logical binary outputs which can be controlled remotely via MODBUS There are fixed registers for MODBUS control Holding register 5200 this register can adjust all switches supported function 6 value 0000 all sw...

Страница 596: ...n The out remains close until engine stop and cooling period elapses Image 8 184 Running Running 6 back to Logical binary outputs alphabetically LBO S Related FW 1 9 0 Related applications AMF MRS Comm object 962 Description The output is closed if SD OVERRIDE PAGE 537 input is active and open if SD OVERRIDE PAGE 537 input is inactive This output is usually used to send information about SD OVERRI...

Страница 597: ...equest to stop comes up D value is higher than D Treshold page 206 Oil pressure value is higher than Starting Oil Pressure page 192 Generator voltage 25 of Nominal Voltage Ph N page 179 or Nominal Voltage Ph Ph page 179 any phase Starter 6 back to Logical binary outputs alphabetically Related FW 1 9 0 Related applications AMF MRS Comm object 26 Description Logical binary output which is still in l...

Страница 598: ...ne stop request Image 8 186 Stop Pulse Stop Pulse 6 back to Logical binary outputs alphabetically Related FW 1 9 0 Related applications AMF MRS Comm object 23 Description This output is dedicated to control the stop solenoid valve The output closes when an engine stop command is received and is deactivated 12 s after last running engine indication went off i e engine is stopped Image 8 187 Stop So...

Страница 599: ...tch 1 s When the measured active power is equal to or bigger than 5 of Nominal Power page 176 for 1 s then the binary output is closed When the measured active power is equal to or lower than 3 of Nominal Power page 176 for 1 s then the binary output is opened Supplying Load 6 back to Logical binary outputs alphabetically Related FW 1 9 0 Related applications AMF MRS Comm object 1997 Description T...

Страница 600: ...s logical binary output is activated at the beginning of start procedure together with PRESTART PAGE 585 LBO Ventilation output is deactivated when engine stops revolving Ventilation LBO is also deactivated immediately when EMERGENCY STOP PAGE 528 or E Stop is activated or when controller is switched to OFF mode Note The output is intended for control of an engine room ventilation fan engine conta...

Страница 601: ...ications AMF MRS Comm object 2089 Description This logical binary output is activated on rising edge of VENTILATION PAGE 600 LBO at the begining of prestart period The pulse duration is adjusted by Ventilation Pulse Time page 226 setpoint Note The output is intended for control of an engine room ventilation fan engine container ventilation fan container louvres or similar running gen set technolog...

Страница 602: ...l analog inputs are Logical analog inputs are inputs for analog values Alphabetical groups of Logical analog inputs LAI A 604 LAI C 631 LAI F 632 LAI N 633 LAI O 634 For full list of Logical analog inputs go to the chapter Logical analog inputs alphabetically page 603 ...

Страница 603: ...AIN Prot18 621 AIN Prot19 622 AIN Prot20 623 AIN Switch 01 624 AIN Switch 02 624 AIN Switch 03 624 AIN Switch 04 625 AIN Switch 05 625 AIN Switch 06 625 AIN Switch 07 626 AIN Switch 08 626 AIN Switch 09 626 AIN Switch 10 627 AIN Switch 11 627 AIN Switch 12 627 AIN Switch 13 628 AIN Switch 14 628 AIN Switch 15 628 AIN Switch 16 629 AIN Switch 17 629 AIN Switch 18 629 AIN Switch 19 630 AIN Switch 20...

Страница 604: ...BOC Analog value is used for warning and BOC Breaker Open and Cooling protection BOC Analog value is used for BOC Breaker Open and Cooling protection Wrn Sd Analog value is used for warning and shutdown protection Sd Analog value is used for shutdown protection Protection types Note This parameter has to be adjusted via InteliConfig Under limit Alarm is activated when value of analog input is unde...

Страница 605: ... Analog value is used for warning and BOC Breaker Open and Cooling protection BOC Analog value is used for BOC Breaker Open and Cooling protection Wrn Sd Analog value is used for warning and shutdown protection Sd Analog value is used for shutdown protection Protection types Note This parameter has to be adjusted via InteliConfig Under limit Alarm is activated when value of analog input is under a...

Страница 606: ... Analog value is used for warning and BOC Breaker Open and Cooling protection BOC Analog value is used for BOC Breaker Open and Cooling protection Wrn Sd Analog value is used for warning and shutdown protection Sd Analog value is used for shutdown protection Protection types Note This parameter has to be adjusted via InteliConfig Under limit Alarm is activated when value of analog input is under a...

Страница 607: ... Analog value is used for warning and BOC Breaker Open and Cooling protection BOC Analog value is used for BOC Breaker Open and Cooling protection Wrn Sd Analog value is used for warning and shutdown protection Sd Analog value is used for shutdown protection Protection types Note This parameter has to be adjusted via InteliConfig Under limit Alarm is activated when value of analog input is under a...

Страница 608: ... Analog value is used for warning and BOC Breaker Open and Cooling protection BOC Analog value is used for BOC Breaker Open and Cooling protection Wrn Sd Analog value is used for warning and shutdown protection Sd Analog value is used for shutdown protection Protection types Note This parameter has to be adjusted via InteliConfig Under limit Alarm is activated when value of analog input is under a...

Страница 609: ... Analog value is used for warning and BOC Breaker Open and Cooling protection BOC Analog value is used for BOC Breaker Open and Cooling protection Wrn Sd Analog value is used for warning and shutdown protection Sd Analog value is used for shutdown protection Protection types Note This parameter has to be adjusted via InteliConfig Under limit Alarm is activated when value of analog input is under a...

Страница 610: ... Analog value is used for warning and BOC Breaker Open and Cooling protection BOC Analog value is used for BOC Breaker Open and Cooling protection Wrn Sd Analog value is used for warning and shutdown protection Sd Analog value is used for shutdown protection Protection types Note This parameter has to be adjusted via InteliConfig Under limit Alarm is activated when value of analog input is under a...

Страница 611: ... Analog value is used for warning and BOC Breaker Open and Cooling protection BOC Analog value is used for BOC Breaker Open and Cooling protection Wrn Sd Analog value is used for warning and shutdown protection Sd Analog value is used for shutdown protection Protection types Note This parameter has to be adjusted via InteliConfig Under limit Alarm is activated when value of analog input is under a...

Страница 612: ... Analog value is used for warning and BOC Breaker Open and Cooling protection BOC Analog value is used for BOC Breaker Open and Cooling protection Wrn Sd Analog value is used for warning and shutdown protection Sd Analog value is used for shutdown protection Protection types Note This parameter has to be adjusted via InteliConfig Under limit Alarm is activated when value of analog input is under a...

Страница 613: ...OC Analog value is used for warning and BOC Breaker Open and Cooling protection BOC Analog value is used for BOC Breaker Open and Cooling protection Wrn Sd Analog value is used for warning and shutdown protection Sd Analog value is used for shutdown protection Protection types Note This parameter has to be adjusted via InteliConfig Under limit Alarm is activated when value of analog input is under...

Страница 614: ...OC Analog value is used for warning and BOC Breaker Open and Cooling protection BOC Analog value is used for BOC Breaker Open and Cooling protection Wrn Sd Analog value is used for warning and shutdown protection Sd Analog value is used for shutdown protection Protection types Note This parameter has to be adjusted via InteliConfig Under limit Alarm is activated when value of analog input is under...

Страница 615: ...OC Analog value is used for warning and BOC Breaker Open and Cooling protection BOC Analog value is used for BOC Breaker Open and Cooling protection Wrn Sd Analog value is used for warning and shutdown protection Sd Analog value is used for shutdown protection Protection types Note This parameter has to be adjusted via InteliConfig Under limit Alarm is activated when value of analog input is under...

Страница 616: ...OC Analog value is used for warning and BOC Breaker Open and Cooling protection BOC Analog value is used for BOC Breaker Open and Cooling protection Wrn Sd Analog value is used for warning and shutdown protection Sd Analog value is used for shutdown protection Protection types Note This parameter has to be adjusted via InteliConfig Under limit Alarm is activated when value of analog input is under...

Страница 617: ...OC Analog value is used for warning and BOC Breaker Open and Cooling protection BOC Analog value is used for BOC Breaker Open and Cooling protection Wrn Sd Analog value is used for warning and shutdown protection Sd Analog value is used for shutdown protection Protection types Note This parameter has to be adjusted via InteliConfig Under limit Alarm is activated when value of analog input is under...

Страница 618: ...OC Analog value is used for warning and BOC Breaker Open and Cooling protection BOC Analog value is used for BOC Breaker Open and Cooling protection Wrn Sd Analog value is used for warning and shutdown protection Sd Analog value is used for shutdown protection Protection types Note This parameter has to be adjusted via InteliConfig Under limit Alarm is activated when value of analog input is under...

Страница 619: ...OC Analog value is used for warning and BOC Breaker Open and Cooling protection BOC Analog value is used for BOC Breaker Open and Cooling protection Wrn Sd Analog value is used for warning and shutdown protection Sd Analog value is used for shutdown protection Protection types Note This parameter has to be adjusted via InteliConfig Under limit Alarm is activated when value of analog input is under...

Страница 620: ...OC Analog value is used for warning and BOC Breaker Open and Cooling protection BOC Analog value is used for BOC Breaker Open and Cooling protection Wrn Sd Analog value is used for warning and shutdown protection Sd Analog value is used for shutdown protection Protection types Note This parameter has to be adjusted via InteliConfig Under limit Alarm is activated when value of analog input is under...

Страница 621: ...OC Analog value is used for warning and BOC Breaker Open and Cooling protection BOC Analog value is used for BOC Breaker Open and Cooling protection Wrn Sd Analog value is used for warning and shutdown protection Sd Analog value is used for shutdown protection Protection types Note This parameter has to be adjusted via InteliConfig Under limit Alarm is activated when value of analog input is under...

Страница 622: ...OC Analog value is used for warning and BOC Breaker Open and Cooling protection BOC Analog value is used for BOC Breaker Open and Cooling protection Wrn Sd Analog value is used for warning and shutdown protection Sd Analog value is used for shutdown protection Protection types Note This parameter has to be adjusted via InteliConfig Under limit Alarm is activated when value of analog input is under...

Страница 623: ...OC Analog value is used for warning and BOC Breaker Open and Cooling protection BOC Analog value is used for BOC Breaker Open and Cooling protection Wrn Sd Analog value is used for warning and shutdown protection Sd Analog value is used for shutdown protection Protection types Note This parameter has to be adjusted via InteliConfig Under limit Alarm is activated when value of analog input is under...

Страница 624: ...e 40 This analog input controls logical binary output AIN SWITCH02 PAGE 553 The behavior of the switch depends on the adjustment of the setpoints Analog Switch 2 On page 246 and Analog Switch 2 Off page 247 Note This function is not suitable for tristate or binary analog sensors IMPORTANT This analog input has no protection Input is designed only to control appropriate logical binary output AIN Sw...

Страница 625: ...e 40 This analog input controls logical binary output AIN SWITCH05 PAGE 555 The behavior of the switch depends on the adjustment of the setpoints Analog Switch 5 On page 255 and Analog Switch 5 Off page 256 Note This function is not suitable for tristate or binary analog sensors IMPORTANT This analog input has no protection Input is designed only to control appropriate logical binary output AIN Sw...

Страница 626: ...e 40 This analog input controls logical binary output AIN SWITCH08 PAGE 556 The behavior of the switch depends on the adjustment of the setpoints Analog Switch 8 On page 264 and Analog Switch 8 Off page 265 Note This function is not suitable for tristate or binary analog sensors IMPORTANT This analog input has no protection Input is designed only to control appropriate logical binary output AIN Sw...

Страница 627: ... 40 This analog input controls logical binary output AIN SWITCH11 PAGE 558 The behavior of the switch depends on the adjustment of the setpoints Analog Switch 11 On page 273 and Analog Switch 11 Off page 274 Note This function is not suitable for tristate or binary analog sensors IMPORTANT This analog input has no protection Input is designed only to control appropriate logical binary output AIN S...

Страница 628: ... 40 This analog input controls logical binary output AIN SWITCH14 PAGE 559 The behavior of the switch depends on the adjustment of the setpoints Analog Switch 14 On page 282 and Analog Switch 14 Off page 283 Note This function is not suitable for tristate or binary analog sensors IMPORTANT This analog input has no protection Input is designed only to control appropriate logical binary output AIN S...

Страница 629: ... 40 This analog input controls logical binary output AIN SWITCH17 PAGE 561 The behavior of the switch depends on the adjustment of the setpoints Analog Switch 17 On page 291 and Analog Switch 17 Off page 292 Note This function is not suitable for tristate or binary analog sensors IMPORTANT This analog input has no protection Input is designed only to control appropriate logical binary output AIN S...

Страница 630: ...ned only to control appropriate logical binary output AIN Switch 19 6 back to Logical analog inputs alphabetically Related FW 1 9 0 Related applications AMF MRS Comm object 293 Description Logical analog input designed for general value received from analog sensor For more information about wiring of analog inputs see Analog inputs on page 40 This analog input controls logical binary output AIN SW...

Страница 631: ...Analog value is used for shutdown protection Protection types Note This parameter has to be adjusted via InteliConfig Under limit Alarm is activated when value of analog input is under adjusted limits Over limit Alarm is activated when value of analog input is over adjusted limits Under limit fls Alarm is activated when value of analog input is under adjusted limits If sensor fail is detected then...

Страница 632: ...ted via InteliConfig Under limit Alarm is activated when value of analog input is under adjusted limits Over limit Alarm is activated when value of analog input is over adjusted limits Under limit fls Alarm is activated when value of analog input is under adjusted limits If sensor fail is detected then the alarm with higher level is activate as well Over limit fls Alarm is activated when value of ...

Страница 633: ...InteliLite Global Guide 633 LAI N Related FW 1 9 0 Related applications AMF MRS Comm object 230 Description Input has no function Not Used 6 back to Logical analog inputs alphabetically ...

Страница 634: ... Alarm is activated when value of analog input is under adjusted limits Over limit Alarm is activated when value of analog input is over adjusted limits Under limit fls Alarm is activated when value of analog input is under adjusted limits If sensor fail is detected then the alarm with higher level is activate as well Over limit fls Alarm is activated when value of analog input is over adjusted li...

Страница 635: ...InteliLite Global Guide 635 Group Comparison of analog inputs 640 Group Time functions 642 Group Other functions 646 For full list of PLC blocks go to the chapter List of PLC blocks page 636 ...

Страница 636: ...roup Basic logical functions OR AND 637 XOR RS 639 Group Comparison of analog inputs Comparator With Hysteresis 640 Comparator With Delay 641 Group Time functions Timer 642 Delay 644 Group Other functions Force History Record 646 Force Protection 646 ...

Страница 637: ...tputs Output Type Negation Range Function Output Binary Yes 0 1 Result of the logical operation Description The block performs logical operation OR AND of 2 8 binary operands The inputs as well as the output can be inverted Input 1 Input 2 Output 0 0 0 0 1 1 1 0 1 1 1 1 Function OR Input 1 Input 2 Output 0 0 0 0 1 0 1 0 0 1 1 1 Function AND There have to be at least 2 inputs every time There may b...

Страница 638: ...InteliLite Global Guide 638 Image 9 1 Configuration of OR AND block 6 back to List of PLC blocks ...

Страница 639: ... Outputs Output Type Negation Range Function Output Binary Yes 0 1 Result of the logical operation Description The block provides logical function of two values XOR or RS flip flop Both inputs and output can be inverted Input 1 Input 2 Output 0 0 0 0 1 1 1 0 1 1 1 0 Function XOR R S Qn 1 0 0 Qn 0 1 1 1 0 0 1 1 0 Function RS Image 9 2 Configuration of XOR RS block XOR RS 6 back to List of PLC block...

Страница 640: ...ut ON Analog No Same as Input Comparative level for switching on Input OFF Analog No Same as Input Comparative level for switching off Outputs Output Type Negation Range Function Output Binary No 0 1 Comparator output Description The block compares the input value with the comparative levels The behavior depends on whether the ON level is higher than OFF level or vice versa Image 9 3 Different On ...

Страница 641: ...parison of analog inputs Related FW 1 9 0 Related applications AMF MRS Comm object 4 Inputs Input Type Negation Range Function Input 1 Analog No Any Compared value Input 2 Analog No Same as Input 1 Comparative level Delay Analog No 0 0 3000 0 s Comparative delay Outputs Output Type Negation Range Function Output Binary No 0 1 Comparator output Description The block works as an analog switch It com...

Страница 642: ...PLC blocks Group Time functions PLC group Time functions Related FW 1 9 0 Related applications AMF MRS Comm object 14 Inputs Input Type Negation Range Function Run Binary No 0 1 The timer runs only if this input is active or not connected Reload Binary No 0 1 This input reloads the timer to the initial value Reload value Analog No 0 0 3276 7 s Initial value of the timer Outputs Timer ...

Страница 643: ...any other moment using the reload input The timer is held at reload value until the reload input is deactivated The timer output is inverted always when the timer is reloaded Image 9 7 Principle of timer Image 9 8 Configuration of Timer block Note Input reload value can be constant or value from controller Note If you want the output to start at logical 0 tick First down option Otherwise the outpu...

Страница 644: ...appears on Input when Input reset is deactivated already Outputs Output Type Negation Range Function Output Binary No 0 1 Output signal Description This block can work in two modes of operation Delay mode the rising edge at the output is generated with delay of input time up when a rising edge at the input is detected The falling edge at the output is generated with delay of input time down when a...

Страница 645: ...f Delay block Note If Input time up or Input time down value is 0 this input is internally set to zero Note Input time up and Input time down values can be constants or values from controller Note Use Pulse on edge option to choose between delay and pulse mode 6 back to List of PLC blocks ...

Страница 646: ...ivated Image 9 11 Configuration of Force Hist block Note Maximal number of characters for history message is 15 Force History Record 6 back to List of PLC blocks PLC group Other functions Related FW 1 9 0 Related applications AMF MRS Comm object 10 Inputs Input Type Negation Range Function Lvl 1 Binary No 0 1 The input activates yellow level of the configured protection if it is configured Lvl 2 B...

Страница 647: ...Wrn BOC BOC Wrn Sd Sd Note Maximal number of characters for alarmlist message is 15 Note Prefix of protection e g Wrn Sd BOC is added automatically into alarmlist message 6 back to List of PLC blocks 8 2 Alarms 8 2 1 Alarms level 1 647 8 2 2 Alarms level 2 671 8 2 3 Fail sensor and other types 689 What alarms are The controller evaluates two levels of alarms For more information see Alarm manageme...

Страница 648: ...arms level 1 go to List of alarms level 1 page 649 What alarms level 1 are The level 1 alarm indicates that a value or parameter is out of normal limits but has still not reached critical level For more information see Alarm types Level 1 on page 99 ...

Страница 649: ...e 659 Wrn Generator L2L3 Voltage 659 Wrn Generator L3 Voltage 659 Wrn Generator L3 Voltage 660 Wrn Generator L3L1 Voltage 660 Wrn Generator L3L1 Voltage 660 Wrn Generator Frequency 661 Wrn Generator Frequency 661 Wrn Check DPF Status 661 Wrn Maintenance 1 661 Wrn Maintenance 2 662 Wrn Maintenance 3 662 Wrn Oil Pressure 662 Wrn Overload 662 Wrn Override All Sd 663 Wrn Rental Timer 1 663 Wrn Rental ...

Страница 650: ...adjusted in setpoint Email Address 2 page 372 and email wasn t send Alarm Email 2 Fail 6 back to List of alarms level 1 Alarm Type Other Alarmlist message Alarm Email 3 Fail Alarm evaluated All the time Related applications AMF MRS Description The alarm indicates that there was a request to send an alarm email to email address which is adjusted in setpoint Email Address 3 page 372 and email wasn t...

Страница 651: ...sted in setpoint Telephone Number 2 page 368 and SMS wasn t send Alarm SMS 2 Fail 6 back to List of alarms level 1 Alarm Type Other Alarmlist message Alarm SMS 3 Fail Alarm evaluated All the time Related applications AMF MRS Description The alarm indicates that there was a request to send an alarm SMS to telephone number which is adjusted in setpoint Telephone Number 3 page 369 and SMS wasn t send...

Страница 652: ... 371 and email wasn t send Event Email 1 Fail 6 back to List of alarms level 1 Alarm Type Other Alarmlist message Event Email 2 Fail Alarm evaluated All the time Related applications AMF MRS Description The alarm indicates that there was a request to send an event email to email address which is adjusted in setpoint Email Address 2 page 372 and email wasn t send Event Email 2 Fail 6 back to List o...

Страница 653: ...usted in setpoint Telephone Number 1 page 368 and SMS wasn t send Event SMS 1 Fail 6 back to List of alarms level 1 Alarm Type Other Alarmlist message Event SMS 2 Fail Alarm evaluated All the time Related applications AMF MRS Description The alarm indicates that there was a request to send an event SMS to telephone number which is adjusted in setpoint Telephone Number 2 page 368 and SMS wasn t sen...

Страница 654: ...alarms level 1 Alarm Type Warning Alarmlist message Rental Timer 2 Elapsed Alarm evaluated All the time Related applications AMF MRS Description This alarm is activated when Rental Timer 2 page 319 elapses Rental Timer 2 Elapsed 6 back to List of alarms level 1 Alarm Type Other Alarmlist message Rental Timer Block Start Alarm evaluated All the time Related applications AMF MRS Description Alarm is...

Страница 655: ...ge Delay page 221 Wrn Battery Voltage 6 back to List of alarms level 1 Alarm Type Warning Alarmlist message Wrn Name of binary input Alarm evaluated All the time Related applications AMF MRS Description Binary input also can be adjusted like alarm In this case message in alarmlist contains prefix Wrn and binary input name This alarm occurs when appropriate binary input is active Wrn BIN Protection...

Страница 656: ...10 setpoint Wrn Coolant Temp 6 back to List of alarms level 1 Alarm Type Warning Alarmlist message Wrn ECU Communication Fail Alarm evaluated With configured LBO ECU POWER RELAY PAGE 570 only when this LBO is active Without configured LBO ECU POWER RELAY PAGE 570 all the time Related applications AMF MRS Description This alarm occurs when an ECU is configured but the communication with the ECU is ...

Страница 657: ...el Wrn page 214 setpoint Wrn Fuel Level 6 back to List of alarms level 1 Alarm Type Warning Alarmlist message Wrn Fuel Theft Alarm evaluated All the time Related applications AMF MRS Description This alarm occurs when the fuel level value measured at relevant AI Fuel Level drops faster than is the limit adjusted by setpoint Maximal Fuel Drop page 216 Wrn Fuel Theft 6 back to List of alarms level 1...

Страница 658: ... it Generator Overvoltage Wrn page 231 Generator Voltage Delay page 232 Wrn Generator L1L2 Voltage 6 back to List of alarms level 1 Alarm Type Warning Alarmlist message Wrn Generator L1L2 Voltage Alarm evaluated Generator excited only Related applications AMF MRS Description This alarm evaluates the generator phase to phase voltage between phases 1 and 2 The following setpoints are related to it G...

Страница 659: ...on This alarm evaluates the generator phase to phase voltage between phases 2 and 3 The following setpoints are related to it Generator Overvoltage Wrn page 231 Generator Voltage Delay page 232 Wrn Generator L2L3 Voltage 6 back to List of alarms level 1 Alarm Type Warning Alarmlist message Wrn Generator L2L3 Voltage Alarm evaluated Generator excited only Related applications AMF MRS Description Th...

Страница 660: ... to List of alarms level 1 Alarm Type Warning Alarmlist message Wrn Generator L3L1 Voltage Alarm evaluated Generator excited only Related applications AMF MRS Description This alarm evaluates the generator phase to phase voltage between phases 3 and 1 The following setpoints are related to it Generator Overvoltage Wrn page 231 Generator Voltage Delay page 232 Wrn Generator L3L1 Voltage 6 back to L...

Страница 661: ...234 Wrn Generator Frequency 6 back to List of alarms level 1 Alarm Type Warning Alarmlist message Wrn Check DPF Status Alarm evaluated When ECU is configured Related applications AMF MRS Description This alarm occurs when ECU send alarm message about Tier IV protection Note Tier IV protection have to be supported by ECU Wrn Check DPF Status 6 back to List of alarms level 1 Alarm Type Warning Alarm...

Страница 662: ... setpoint will count down while the engine is running and if reaches zero this alarm will be issued The alarm message will remain in the alarm list even if the controller is switched off and on again until the setpoint is re adjusted to a positive value Wrn Maintenance 3 6 back to List of alarms level 1 Alarm Type Warning Alarmlist message Wrn Oil Pressure Alarm evaluated Gen set is running Relate...

Страница 663: ...ion This alarm occurs xx hours before Rental Timer 1 page 317 elapsed Hours are adjusted by setpoint Rental Timer 1 Wrn page 319 Wrn Rental Timer 1 6 back to List of alarms level 1 Alarm Type Warning Alarmlist message Wrn Rental Timer 2 Alarm evaluated All the time Related applications AMF MRS Description This alarm occurs xx hours before Rental Timer 2 page 319 elapsed Hours are adjusted by setpo...

Страница 664: ...l this alarm is inactive and reset 6 back to List of alarms level 1 Other type Alarm Type Alarm indication Alarmlist message After Treatment Alarm evaluated All the time Related applications AMF MRS Description This alarm occurs when appropriate after treatment lamp is active After Treatment 6 back to List of alarms level 1 Alarm Type Alarm indication Alarmlist message Dual Operation Different FW ...

Страница 665: ... Alarm indication Alarmlist message Dual Operation Master Fail Alarm evaluated Only during dual operation Related applications AMF MRS Description This alarm is active when Master is not able to take the load e g there is alarm of 2nd level on Master Logical binary input AL DUAL MASTER FAIL PAGE 546 is activated Note This alarm is also written to history Dual Operation Master Fail 6 back to List o...

Страница 666: ...n ECU send information that ECU Yellow lamp is activated LBO ALARM PAGE 552 is not activated after deactivation of lamp alarm automatically disappear ECU Yellow Lamp 6 back to List of alarms level 1 Alarm Type Other Alarmlist message EM A a message lost Alarm evaluated All the time Related applications AMF MRS Description This alarm indicates that there is a problem with communication between cont...

Страница 667: ...larm Type Other Alarmlist message EM B a message lost Alarm evaluated All the time Related applications AMF MRS Description This alarm indicates that there is a problem with communication between controller and module in slot EM B a message lost 6 back to List of alarms level 1 Alarm Type Other Alarmlist message EM B configuration mistake Alarm evaluated All the time Related applications AMF MRS D...

Страница 668: ...void wrong voltage phase connection There is a fixed defined phase sequence in InteliLite controller T35 N T36 L1 T37 L2 and T38 L3 When the phases are connected in a different order alarms are detected This alarm prevent circuit breaker closing Generator CCW Rotation 6 back to List of alarms level 1 Alarm Type Other Alarmlist message Module slotA comm outage Alarm evaluated All the time Related a...

Страница 669: ...t module than which is configured or the module is unconfigured and has to be configured for proper function Module slotA unexpected 6 back to List of alarms level 1 Alarm Type Other Alarmlist message Module slotA unknown module Alarm evaluated All the time Related applications AMF MRS Description This alarm indicates that unknown module is inserted in slot Module slotA unknown module 6 back to Li...

Страница 670: ...xpected Alarm evaluated All the time Related applications AMF MRS Description This alarm indicates that in slot is inserted different module than which is configured or the module is unconfigured and has to be configured for proper function Module slotB unexpected 6 back to List of alarms level 1 Alarm Type Other Alarmlist message Module slotB unknown module Alarm evaluated All the time Related ap...

Страница 671: ...alarm will occur when FUEL PUMP PAGE 572 is active Wrn Transferring Fuel 6 back to List of alarms level 1 8 2 2 Alarms level 2 Shutdown 673 Other type 682 For full list of Alarms level 2 go to List of alarms level 2 page 672 What alarms level 2 are The level 2 level alarm indicates that a critical level of the respective value or parameter has been reached For more information see Alarm types Leve...

Страница 672: ...ency 679 Sd Generator Frequency 680 Sd Generator Voltage Unbalance Ph Ph 680 Sd Generator Voltage Unbalance Ph N 680 Sd Oil Pressure 680 Sd Overload 681 Sd Overspeed 681 Sd RPM Measurement Fail 681 Sd Short Circuit 682 Sd Start Fail 682 Sd Underspeed 682 BOC AIN Prot 682 BOC BIN Protection 683 BOC Coolant Temp 683 BOC Current Unbalance 683 BOC Fence 1 Alarm 683 BOC Fence 2 Alarm 684 BOC Fuel Level...

Страница 673: ...cy Stop 6 back to List of alarms level 2 Alarm Type Sd Alarmlist message Sd Name of analog input Alarm evaluated All the time Related applications AMF MRS Description This alarm indicates that value the general analog protection is out of shutdown protection limit Sd AIN Protec 6 back to List of alarms level 2 Alarm Type Shutdown Alarmlist message Sd Battery Flat Alarm evaluated During cranking Re...

Страница 674: ...ons AMF MRS Description This alarm evaluates the unbalance of the phase currents i e the difference between highest and lowest phase current at any given time The following setpoints are related to it Current Unbalance BOC page 230 adjusts the maximum allowed difference between the highest and lowest phase current at any given time Current Unbalance BOC Delay page 230 adjusts the alarm delay Sd Cu...

Страница 675: ...is alarm evaluates the GPS position of gen set The following setpoint are related to it Geo Fencing page 324 Fence 1 Protection page 325 Fence Radius 1 page 323 Sd Fence 1 Alarm 6 back to List of alarms level 2 Alarm Type Shutdown Alarmlist message Sd Fence 2 Alarm Alarm evaluated All the time Related applications AMF MRS Description This alarm evaluates the GPS position of gen set The following s...

Страница 676: ... or close command within 2 seconds Sd GCB Fail 6 back to List of alarms level 2 Alarm Type Shutdown Alarmlist message Sd Generator L1 Voltage Alarm evaluated Generator excited only Related applications AMF MRS Description This alarm evaluates the generator phase voltage in phase 1 The following setpoints are related to it Generator Overvoltage Sd page 230 Generator Voltage Delay page 232 Sd Genera...

Страница 677: ...setpoints are related to it Generator Undervoltage BOC page 231 Generator Voltage Delay page 232 Sd Generator L1L2 Voltage 6 back to List of alarms level 2 Alarm Type Shutdown Alarmlist message Sd Generator L2 Voltage Alarm evaluated Generator excited only Related applications AMF MRS Description This alarm evaluates the generator phase voltage in phase 2 The following setpoints are related to it ...

Страница 678: ...cations AMF MRS Description This alarm evaluates the generator phase to phase voltage between phases 2 and 3 The following setpoints are related to it Generator Undervoltage BOC page 231 Generator Voltage Delay page 232 Sd Generator L2L3 Voltage 6 back to List of alarms level 2 Alarm Type Shutdown Alarmlist message Sd Generator L3 Voltage Alarm evaluated Generator excited only Related applications...

Страница 679: ...ator L3L1 Voltage 6 back to List of alarms level 2 Alarm Type Shutdown Alarmlist message Sd Generator L3L1 Voltage Alarm evaluated Generator excited only Related applications AMF MRS Description This alarm evaluates the generator phase to phase voltage between phases 3 and 1 The following setpoints are related to it Generator Undervoltage BOC page 231 Generator Voltage Delay page 232 Sd Generator ...

Страница 680: ...ge Unbalance BOC page 232 adjusts the maximum allowed difference between the highest and lowest phase voltage at any given time Voltage Unbalance BOC Delay page 233 adjusts the alarm delay Sd Generator Voltage Unbalance Ph Ph 6 back to List of alarms level 2 Alarm Type Shutdown Alarmlist message Sd Generator Voltage Unbalance Ph N Alarm evaluated Generator excited only Related applications AMF MRS...

Страница 681: ...peed Alarm evaluated All the time Related applications AMF MRS Description This alarm occurs immediately when the engine speed has exceeded the limit The behavior of the overspeed alarm is adjusted by the following setpoints Overspeed Sd page 207 adjust the overspeed limit Overspeed Overshot page 207 adjust the additional overspeed limit Overspeed Overshot Period page 208 adjust the time period of...

Страница 682: ...oints are related to this alarm Cranking Attempts page 189 adjust the number of attempts Sd Start Fail 6 back to List of alarms level 2 Alarm Type Shutdown Alarmlist message Sd Underspeed Alarm evaluated Engine running only Related applications AMF MRS Description This alarm will be issued when the gen set is running and then stops by itself i e the RPM drops under the value of setpoint Underspeed...

Страница 683: ...st of alarms level 2 Alarm Type BOC Alarmlist message BOC Current Unbalance Alarm evaluated All the time Related applications AMF MRS Description This alarm evaluates the unbalance of the phase currents i e the difference between highest and lowest phase current at any given time The following setpoints are related to it Current Unbalance BOC page 230 adjusts the maximum allowed difference between...

Страница 684: ...pplications AMF MRS Description This alarm indicates that the fuel level is lower than the level set level in Fuel Level Sd page 214 setpoint BOC Fuel Level 6 back to List of alarms level 2 Alarm Type BOC Alarmlist message BOC Generator L1 Voltage Alarm evaluated Generator excited only Related applications AMF MRS Description This alarm evaluates the generator phase voltage in phases 1 The followi...

Страница 685: ...nerator L2 Voltage 6 back to List of alarms level 2 Alarm Type BOC Alarmlist message BOC Generator L2L3 Voltage Alarm evaluated Generator excited only Related applications AMF MRS Description This alarm evaluates the generator phase to phase voltage between phases 2 and 3 The following setpoints are related to it Generator Undervoltage BOC page 231 Generator Voltage Delay page 232 BOC Generator L2...

Страница 686: ...escription This alarm evaluates the generator frequency in the phase L1 The following setpoints are related to it Generator Overfrequency BOC page 233 Generator Frequency Delay page 234 BOC Generator Frequency 6 back to List of alarms level 2 Alarm Type BOC Alarmlist message BOC Generator Frequency Alarm evaluated Generator excited only Related applications AMF MRS Description This alarm evaluates...

Страница 687: ...llowed difference between the highest and lowest phase voltage at any given time Voltage Unbalance BOC Delay page 233 adjusts the alarm delay BOC Gen Voltage Unbalance Ph N 6 back to List of alarms level 2 Alarm Type Shutdown Alarmlist message Sd Name of binary input Alarm evaluated Generator excited only Related applications AMF MRS Description The overcurrent alarm is based on IDMT principle The...

Страница 688: ...BOC Rental Timer 6 back to List of alarms level 2 Alarm Type BOC Alarmlist message BOC Short Circuit Alarm evaluated All the time Related applications AMF MRS Description This is a fast overcurrent protection The following setpoints are related to this alarm Short Circuit BOC page 228 adjusts the short current limit Short Circuit BOC Delay page 228 adjusts the delay in fine steps BOC Short Circuit...

Страница 689: ...ist of Fails sensor and other types of alarms go to List of fail sensor alarms page 690 What Fail sensor and other types of alarms are If the measured resistance on an analog input exceeds the valid range a sensor fail will be detected and a sensor fail message will appear in the Alarmlist For more information see Sensor fail detection FLS on page 100 ...

Страница 690: ...List of fail sensor alarms Fls AIN Prot 1 691 Fls Coolant Temp 691 Fls Fuel Level 691 Fls Oil Pressure 691 InteliLite Global Guide 690 ...

Страница 691: ...e of coolant temperature is out of range or is missing Fls Coolant Temp 6 back to List of fail sensor alarms Alarm Type Fls Alarmlist message Fls Fuel Level Alarm evaluated All the time Related applications AMF MRS Description This alarm occurs when measurement value of fuel level is out of range or is missing Fls Fuel Level 6 List of fail sensor alarms page 690 Alarm Type Fls Alarmlist message Fl...

Страница 692: ...e available extension plug in modules are EM BIO8 EFCP extension module with 8 binary inputs outputs and with earth fault current protection Note Controller has 2 plug in module slots Module CM Ethernet CM 4G GPS CM GPRS CM RS232 485 EM BIO8 EFCP CM Ethernet CM 4G GPS CM GPRS CM RS232 485 EM BIO8 EFCP Supported combinations of plug in modules Communication modules CM RS232 485 692 CM Ethernet 694 ...

Страница 693: ...l Guide 693 Image 9 14 CM RS232 485 interface IMPORTANT Any manipulation with plug in module shall be done with disconnected power supply to controller Image 9 15 Pinout of RS 232 line Image 9 16 Pinout of RS 485 line ...

Страница 694: ...Tools Firmware upgrade select the Plug in modules tab and select the appropriate firmware you want to program into the module in InteliConfig Press the OK button to start upgrade of firmware The firmware update process may be performed via any kind of connection including connection via the same module in which the firmware is to be updated The connection is reestablished again automatically when ...

Страница 695: ... can also be connected directly to a PC using cross wired UTP cable Image 9 19 Cross wired cable Power consumption 120 mA 8 VDC 82 mA 12 VDC 35 mA 24 VDC 25 mA 36 VDC Technical data Module setup All settings related to the module are to be adjusted via the controller setpoints The respective setpoints are located in the setpoint Group CM Ethernet page 371 All actual operational values like actual ...

Страница 696: ...g in modules tab and select the appropriate firmware you want to program into the module in InteliConfig Press the OK button to start upgrade of firmware The firmware update process may be performed via any kind of connection including connection via the same module in which the firmware is to be updated The connection is reestablished again automatically when the update process is finished CM GPR...

Страница 697: ...erator that the particular SIM card does support 2 5G network Contact your mobile operator for getting packet data APN APN Access Point Name username and password Example APN Name internet UserName blank Password blank Make sure SIM card does not require PIN code Use any mobile phone to switch the SIM PIN security off Place the SIM card into slot on CM GPRS card Connect the antenna to Cellular mod...

Страница 698: ...on 5 Module not possible to set the APN 6 Module not possible to connect to GPRS network 7 Module not possible to retrieve IP address 8 Module not accepted DNS IP address 9 Error in modem detection 10 Error in initialization of analog modem 11 SIM card is locked Possibly PIN code required PIN needs to be deactivated or unknown status of SIM locking 12 No GSM signal 13 Not possible to read the SIM ...

Страница 699: ...9s can t do power on 31 ME909s can t do hardware reset 32 ME909s ME909s not started 33 ME909s switch off issued 34 ME909s switch on issued 35 ME909s HW reset issued 36 ME909s can t switch echo off 37 ME909s can t find out state of registration 38 ME909s GSM signal not found 39 ME909s no SIM memory for SMS 40 ME909s waiting for registration 41 Can t read operator name 42 ME909s can t set flow contr...

Страница 700: ... GSM WCDMA LTE modem which can works in two modes of operation based on the settings in the setpoint Internet Connection page 359 Image 9 23 CM 4G GPS module IMPORTANT Any manipulation with plug in module shall be done with disconnected power supply to controller IMPORTANT CM 4G GPS and CM GPRS modules cant be used in one controller in the same time IMPORTANT Operating temperature of module is fro...

Страница 701: ...net UserName blank Password blank Make sure SIM card does not require PIN code Use any mobile phone to switch the SIM PIN security off Place the SIM card into slot on CM 4G GPS card Connect the antenna to Cellular module antenna connector If you want to use the built in GPS receiver connect also an active GPS antenna to the GPS antenna connector Switch off the controller Insert CM 4G GPS module in...

Страница 702: ...nitialization 5 Module not possible to set the APN 6 Module not possible to connect to GPRS network 7 Module not possible to retrieve IP address 8 Module not accepted DNS IP address 9 Error in modem detection 10 Error in initialization of analog modem 11 SIM card is locked Possibly PIN code required PIN needs to be deactivated or unknown status of SIM locking 12 No GSM signal 13 Not possible to re...

Страница 703: ...9s can t do power on 31 ME909s can t do hardware reset 32 ME909s ME909s not started 33 ME909s switch off issued 34 ME909s switch on issued 35 ME909s HW reset issued 36 ME909s can t switch echo off 37 ME909s can t find out state of registration 38 ME909s GSM signal not found 39 ME909s no SIM memory for SMS 40 ME909s waiting for registration 41 Can t read operator name 42 ME909s can t set flow contr...

Страница 704: ... performed via any kind of connection including connection via the same module in which the firmware is to be updated The connection is reestablished again automatically when the update process is finished Extension modules EM BIO8 EFCP 704 EM BIO8 EFCP EM BIO8 EFCP is optional plug in card Through this card controller can accommodate one AC current CT measuring input 1A or 5A input and up to 8 bi...

Страница 705: ...e 9 28 EM BIO8 EFCP wiring EM BIO8 EFCP technical data Power supply range 8 36 VDC Power consumption 40 mA 8 VDC 27 mA 12 VDC 22 mA 24 VDC 19 mA 36 VDC Power supply Number Up to 8 non isolated Close Open indication 0 2 VDC close contact 6 VDC open contact Binary inputs ...

Страница 706: ...ay page 386 time elapses the Earth Fault Current Protection page 385 Sd Earth Fault Current page 674 alarm and AL EARTH FAULT PAGE 546 output are activated Earth Fault protection is not active when gen set does not run and when the Earth Fault Current Protection page 385 is disabled IMPORTANT Earth fault current measurement is not intended to protect human health but the machines Image 9 29 Earth ...

Страница 707: ...og outputs this CAN module can be switched to Inteli IO 16 0 extension CAN module with 16 binary inputs and 2 analog outputs Slot Inteli AIN8 Inteli AIN8TC Inteli IO8 8 Inteli IO 16 0 IGL RA15 IGS PTM Inteli AIO9 1 1 2 3 4 5 Supported combinations of modules IMPORTANT In slot 3 4 and 5 CAN modules Inteli IO8 8 and Inteli IO 16 0 are supported without analog outputs Analog outputs of these CAN modu...

Страница 708: ...InteliLite Global Guide 708 Image 9 30 Inteli AIN8 Image 9 31 Inteli AIN8 dimensions Note All dimensions are in mm ...

Страница 709: ... CAN resistor active in position ON switch both switches Note Impulse input is not supported Analog inputs 8 channels can be configured as resistor three wire input current input voltage input All inputs can be configured to any logical function or protection IMPORTANT Impulse input is not supported in controller Supported sensors Sensors User curves NI100 F fix 0 5V PT100 C fix NI1000 F fix 0 10V...

Страница 710: ... deactivated Programming firmware Firmware upgrade process 1 Disconnect all terminals from the unit 2 Separate the top cover of module 3 Put the TEST jumper on a pins 4 Connect the unit with PC via RS232 null modem cable and AT Link conv 5 Connect power supply of the module status LED lights continuously 6 Launch FlashPgr exe PC software version 4 2 or higher 7 In FlashPrg program choose card Inte...

Страница 711: ...r supply again status LED should blinking 12 Module FW is upgraded LED indication LED status Description Dark Fw in module does not work correctly Flashing Module does not communicate with controller in case non zero CAN address Lights Power supply is in the range and the communication between Inteli AIN8 and controller works properly Or power supply is in range and zero CAN address is set in case...

Страница 712: ...eliLite Global Guide 712 Resistance sensor 2 wires Note Ranges Pt100 Pt1000 Ni100 Ni1000 0 2400 Ω 0 10 kΩ Current sensor active Note Ranges 20 mA 4 20 mA Current sensor passive Note Ranges 0 20 mA 4 20 mA ...

Страница 713: ...istive Range 0 10 kΩ Accuracy 0 5 of actual value 2 Ω Analog inputs Inteli IO8 8 Inteli IO8 8 module is an extension module equipped with binary inputs binary outputs and analog outputs Inteli IO8 8 is the name of the module but it is possible to configure the module by internal switch to two configurations Inteli IO8 8 8 binary inputs 8 binary outputs and 2 analog outputs Inteli IO 16 0 16 binary...

Страница 714: ...InteliLite Global Guide 714 Image 9 32 Inteli IO8 8 Image 9 33 Inteli IO8 8 dimensions Note All dimensions are in mm ...

Страница 715: ...ary outputs LEDs 8 LEDs for binary output indication CAN LED Indication transmitted or received data Status LED indication of correct function CAN terminator Terminating CAN resistor active in position ON switch both switches Inputs and outputs Binary inputs 8 channels can be configured as pull up pull down All 8 inputs are configured to one type together All inputs can be configured to any logica...

Страница 716: ...istory record and alarm are issued type of the alarm is set by Protection upon module failure No protection Warning Shutdown This function is designed for short circuit or other failure which causes change of set state of binary output CAN address In Inteli IO8 8 mode CAN address for binary inputs is determined by DIP switch A CAN address for binary output and analog outputs is determined by DIP s...

Страница 717: ...orrect Module has power supply no CAN bus connection status LED lights continuously 10 After successful programming disconnect AT Link conv remove TEST jumper and disconnect power supply 11 Connect power supply again status LED should blinking 12 Module FW is upgraded LED indication Binary input Each binary input has LED which indicates input signal LED is shining when input signal is set and LED ...

Страница 718: ...ing The following diagrams show the correct connection of inputs and outputs Binary inputs pull up There are two options of wiring On upper picture you can see case when binary input is connected between BIN2 and COM COM is connected internally to the GND dashed line On lower picture is case of wiring between BIN2 and GND Both ways are correct Binary inputs pull down There are two options of wirin...

Страница 719: ...uts low side When low side setting of outputs is chosen binary output must be connected to the plus potential of power supply directly Minus potential is connected internally dashed line Analog outputs Note Limit of analog ground AGND is 100mA IMPORTANT Terminator for analog output has special analog ground AGND which must not be connected to the GND Technical data Power supply 8 to 36 V DC Curren...

Страница 720: ...utputs Number of channels 8 for Inteli IO8 8 16 for Inteli IO 16 0 Input resistance 4400 Ω Input range 0 to 36 V DC Switching voltage level for open contact indication 0 to 2 V DC Max voltage level for close contact indication 6 to 36 V DC Binary inputs Number of channels 8 for Inteli IO8 8 0 for Inteli IO 16 0 Max current 500 mA Max switching voltage 36 V DC Binary outputs IGS PTM IGS PTM module ...

Страница 721: ...InteliLite Global Guide 721 Image 9 34 IGS PTM Image 9 35 IGS PTM dimensions ...

Страница 722: ...ower supply Analog inputs Analog inputs can be configured for Resistance measurement Current measurement Voltage measurement The type of analog inputs is configured via jumpers RUI located on lower PCB RUI Analog input configuration 1 2 Resistance measuring 2 3 Current measuring no jumper Voltage measuring Supported sensors Sensors PT100 C fix User curves NI100 C fix 0 100 mV PT100 F fix 0 2400 oh...

Страница 723: ...sary to close jumper BOOT RESET jumper is used to reset the device Close jumper to reset the device For programming is used FlashProg PC tool LED indication Binary input Each binary input has LED which indicates input signal LED is shining when input signal is set and LED is dark while input signal has other state Binary output Each binary output has LED which indicates output signal Binary output...

Страница 724: ... outputs Resistance sensor Note Range 0 2400 Ω IMPORTANT Physical analog input range is 0 250 Ω In sensor configuration in PC tool it is necessary to chose 0 2400 Ω sensor HW type to ensure proper function of analog input Voltage sensor Note Range 0 100 mV ...

Страница 725: ...A 0 33 mA Technical data Power supply 8 to 36 V DC Current consumption 100 mA at 24V 500 mA Interface to controller CAN1 Protection IP20 Storage temperature 40 C to 80 C Operating temperature 30 C to 70 C Dimensions WxHxD 95 96 43 mm 3 7 3 8 1 7 General data Number of channels 8 Voltage Range 0 100 mV Accuracy 1 5 1 mV out of measured value Current Range 0 20 mA Accuracy 2 5 0 5 ohm out of measure...

Страница 726: ...r of channels 8 Voltage Range 0 100 mV Accuracy 1 5 1 mV out of measured value Current Range 0 20 mA Accuracy 2 5 0 5 ohm out of measured value Resistive Range 0 250 Ω Accuracy 1 2 ohm out of measured value Binary outputs Inteli AIN8TC Inteli AIN8TC module is extension module equipped with 8 analog inputs dedicated for thermocouple sensors only The detection of communication speed is indicated by ...

Страница 727: ...InteliLite Global Guide 727 Image 9 36 Inteli AIN8TC Image 9 37 Inteli AIN8TC dimensions ...

Страница 728: ...dication of correct function CAN terminator Terminating CAN resistor active in position ON TEST jumper Upgrade of sw AT LINK Connector for AT LINK Analog inputs 8 channels can be configured as thermocouple sensors only Supported sensors Sensors Thermocpl J C fix Thermocpl K C fix Thermocpl L C fix Thermocpl J F fix Thermocpl K F fix Thermocpl L F fix Thermocpl nc J C fix ...

Страница 729: ... link TTL For programming it is necessary to close jumper TEST For programming FlashProg PC tool version 4 2 or higher must be used LED indication LED status Description Dark Fw in module does not work correctly Flashing Module does not communicate with controller in case non zero CAN address Fast flashing Detection of CAN communication speed Lights Power supply is in the range and the communicati...

Страница 730: ...log inputs are not galvanic separated between channels Power supply 8 to 36 V DC Protection IP20 Current consumption 35 mA at 24 V 100 mA at 8 V Storage temperature 40 C to 80 C Operating temperature 30 C to 70 C Heat radiation 2 W Thermocouples galvanically separated and galvanically non separated are supported Inteli AIO9 1 Inteli AIO9 1 module is extension module equipped with analog inputs and...

Страница 731: ...InteliLite Global Guide 731 Image 9 38 Inteli AIO9 1 Image 9 39 Inteli AIO9 1 dimensions ...

Страница 732: ...minating CAN resistor active in position ON TEST jumper Upgrade of sw AT LINK Connector for AT LINK Upgrade of sw Analog inputs 4 channels AIN1 AIN4 can be configured as Sensor 65V it is determinated for measurement of battery voltage 4 channels AIN5 AIN8 can be configured as Thermocouples type J K or L in C or F Sensor 75mV DC for connecting current shunts 1 channel AIN9 can be configured as RTD ...

Страница 733: ...L C fix Thermocpl nc J C fix Thermocpl nc K C fix Thermocpl nc L C fix Thermocpl nc J F fix Thermocpl nc K F fix Thermocpl nc L F fix Address and DIP switch setting Address configuration DIP switch determinates CAN address for analog inputs and outputs Programming Firmware Firmware upgrade is via AT link TTL For programming it is necessary to close jumper TEST and switch OFF and switch ON the powe...

Страница 734: ...and controller works properly Or power supply is in range and zero CAN address is set in case zero CAN address module doesn t communicate with the controller Wiring The following diagrams show the correct connection of sensors Measuring resistance AIN9 2 wire measurement Ranges Pt1000 Ni1000 0 2400 Ω Analog input 9 is determined for measuring resistance only ...

Страница 735: ...f actual value 75 µV Galvanic separated from power supply AIN9 resistance input Range 0 2400 Ω Accuracy of measurement 0 5 of actual value 4 Ω Pt1000 Ni1000 2 5 C It is not galvanic separated from power supply Analog output I 0 20mA 500Rmax 1 of actual value 200 uA U 0 10V 0 5 of actual value 50 mV PWM 5 V 200 Hz 2 4kHz 15 mA max Galvanic separated from power supply Galvanic separation CAN bus is ...

Отзывы: