InteliLite Global Guide
101
Terminal
Event
SMS
Warning
SMS
BOC
SMS
Shutdown
SMS
Event
Warning
BOC
Shutdown
CM-RS232-485
no
no
no
no
no
no
no
no
CM-Ethernet
no
no
no
no
yes
yes
yes
yes
CM-GPRS
yes
yes
yes
yes
yes*
yes*
yes*
yes*
CM-4G-GPS
yes
yes
yes
yes
yes*
yes*
yes*
yes*
Note:
* Only with enabled
Internet Connection (page 359)
.
Alarmlist
Alarmlist is a container of active and inactive alarms. It will appear automatically on the controller display, if a
new alarm occurs, or can be displayed manually from the display menu.
Active alarms are shown as inverted, not yet confirmed alarms are marked with asterisk before them.
Alarmlist contains three types of alarms:
Controller built-in alarms
User configured alarms on binary or analog inputs
ECU alarms
Controller built-in alarms
An alarm message in the alarmlist begins with a prefix, which represents the alarm type (e.g. Wrn, Sd, BOC,
MP, MPR). Then the alarm name follows. In some cases the prefix can be omitted.
User configured alarms
An alarm message in the alarmlist begins with a prefix, which represents the alarm type (e.g. Wrn, Sd, BOC).
Alarm type is selected by user during the configuration of binary or analog input as alarm. Then the alarm name
follows. Name is adjusted by user during the configuration of binary or analog input as alarm.
ECU alarms
The ECU alarms are received from the ECU. The alarms are represented by the Diagnostic Trouble Code,
which contains information about the subsystem where the alarm occurred, the alarm type and the alarm
occurrence counter.
The most common fault codes are translated into text form. Other fault codes are displayed as a numeric code
and the engine fault codes list must be used to determine the reason.
Built-in alarms
Events
specification
Protection
type
Description
Analog Input 1 Wrn
WRN
Value measured on analog input 1 is </> than
setpoint.
Analog Input 1 Sd
SD
Value measured on analog input 1 is </> than
setpoint.
Analog Input 2 Wrn
WRN
Value measured on analog input 2 is </> than
setpoint.
Содержание InteliLite AMF25
Страница 34: ...InteliLite Global Guide 34 ConnectionType SplPhL1L2 Image 4 11 Split phase L1L2 application ...
Страница 36: ...InteliLite Global Guide 36 Image 4 14 Typical Split Phase generator wiring ...
Страница 91: ...InteliLite Global Guide 91 Image 5 13 Flowchart of start of diesel engine ...
Страница 93: ...InteliLite Global Guide 93 Image 5 14 Flowchart of start of gas engine ...
Страница 199: ...InteliLite Global Guide 199 nominal speed Image 8 3 Idle Time 1 Image 8 4 Idle Time 2 6 back to List of setpoints ...
Страница 638: ...InteliLite Global Guide 638 Image 9 1 Configuration of OR AND block 6 back to List of PLC blocks ...
Страница 708: ...InteliLite Global Guide 708 Image 9 30 Inteli AIN8 Image 9 31 Inteli AIN8 dimensions Note All dimensions are in mm ...
Страница 714: ...InteliLite Global Guide 714 Image 9 32 Inteli IO8 8 Image 9 33 Inteli IO8 8 dimensions Note All dimensions are in mm ...
Страница 721: ...InteliLite Global Guide 721 Image 9 34 IGS PTM Image 9 35 IGS PTM dimensions ...
Страница 727: ...InteliLite Global Guide 727 Image 9 36 Inteli AIN8TC Image 9 37 Inteli AIN8TC dimensions ...
Страница 731: ...InteliLite Global Guide 731 Image 9 38 Inteli AIO9 1 Image 9 39 Inteli AIO9 1 dimensions ...