InteliLite 9 Global Guide
86
Breaker open and cool down (BOC)
The event appears in the alarmlist and is recorded into the history log. It causes immediate opening of the GCB
and then the standard stop sequence with cooling follows. The gen-set cannot be started again while there is a
BOC alarm in the alarmlist. Activates the output
as well as the standard alarm
outputs (
and
).
Sensor fail detection (FLS)
If the measured resistance on an analog input exceeds the valid range, a sensor fail will be detected and a
sensor fail message will appear in the
. The valid range is defined by the most-left (RL) and
most-right (RH) points of the sensor characteristic ±12.5% from RH-RL.
Note:
Sometimes there can be problem with lower limit of valid range which can be counted as negative
number. In this case the lower limit is set as one half of the RL point of the sensor curve characteristic.
Image 5.14 Sensor fail detection principle
Remote alarm messaging
If communication plug-in module is connected to the controller, the controller can send SMS messages and
emails at the moment when a new alarm appears in the
or new event is written in
. The message will contain a copy of the
or reasons from
. To enable this function, adjust setpoints
,
and
to ON. Also enter a valid GSM phone number or email address to the
setpoints
.
The list of all supported terminals shows the table below:
Содержание InteliLite 9
Страница 17: ...InteliLite 9 Global Guide 17 Image 3 2 MRS application overview 6 back to Applications overview ...
Страница 41: ...InteliLite 9 Global Guide 41 4 4 12 Example of AMF Wiring ...
Страница 42: ...InteliLite 9 Global Guide 42 4 4 13 Example of MRS Wiring ...
Страница 80: ...InteliLite 9 Global Guide 80 Image 5 11 Flowchart of start of diesel engine ...
Страница 101: ...InteliLite 9 Global Guide 101 5 4 15 Flowchart Image 5 26 Basic flowchart of controller sequences ...
Страница 173: ...InteliLite 9 Global Guide 173 Image 8 7 Idle Time 1 Image 8 8 Idle Time 2 6 back to List of setpoints ...