InteliLite 9 Global Guide
385
Alarm Type
BOC
Alarmlist message
BOC Generator < Frequency
Alarm evaluated
Generator excited only
Related applications
AMF, MRS
Description
This alarm evaluates the generator frequency in the phase L1. The following
setpoints are related to it:
Generator Underfrequency BOC (page 196)
Generator <> Frequency Delay (page 196)
BOC Generator < Frequency
back to List of alarms level 2
Alarm Type
BOC
Alarmlist message
BOC Overload
Alarm evaluated
All the time
Related applications
AMF, MRS
Description
The alarm is issued when the gen-set power is over the limit for time period longer
than the delay. The behavior of the overload alarm is adjusted by the following
setpoints:
adjusts the overload limit.
adjusts the delay
BOC Overload
back to List of alarms level 2
Alarm Type
BOC
Alarmlist message
BOC Short Circuit
Alarm evaluated
All the time
Related applications
AMF, MRS
Description
This is a fast overcurrent protection. The following setpoints are related to this
alarm:
adjusts the short current limit
Short Circuit BOC Delay (page 193)
adjusts the delay in fine steps
BOC Short Circuit
back to List of alarms level 2
8.2.3 Fail sensor and other types
For full list of Fails sensor and other types of alarms go to
List of fail sensor alarms (page 387)
What Fail sensor and other types of alarms are
Содержание InteliLite 9
Страница 17: ...InteliLite 9 Global Guide 17 Image 3 2 MRS application overview 6 back to Applications overview ...
Страница 41: ...InteliLite 9 Global Guide 41 4 4 12 Example of AMF Wiring ...
Страница 42: ...InteliLite 9 Global Guide 42 4 4 13 Example of MRS Wiring ...
Страница 80: ...InteliLite 9 Global Guide 80 Image 5 11 Flowchart of start of diesel engine ...
Страница 101: ...InteliLite 9 Global Guide 101 5 4 15 Flowchart Image 5 26 Basic flowchart of controller sequences ...
Страница 173: ...InteliLite 9 Global Guide 173 Image 8 7 Idle Time 1 Image 8 8 Idle Time 2 6 back to List of setpoints ...