InteliLite 9 Global Guide
145
Group: Basic settings
Subgroup: Name
Setpoint group
Basic settings
Related FW
1.1.0
Range [units]
0 .. 15 characters [-]
Default value
InteliLite
Alternative config
NO
Step
[-]
Comm object
8637
Related applications
AMF, MRS
Config level
Standard
Setpoint visibility
Always
Description
User defined name, used for the controller identification at remote phone or mobile connection. Gen-Set
Name is maximally 15 characters long and can be entered using InteliConfig or from controller’s
configuration menu.
Note:
If the Gen-Set Name is "TurboRunHours", the running hours will be counted faster - 1 minute in
real will represent 1 hour.
Gen-Set Name
Subgroup: Power settings
Setpoint group
Basic settings
Related FW
1.1.0
Range [units]
1 .. 5 000 [kW]
Default value
200 kW
Alternative config
Yes
Step
1 kW
Comm object
9977
Related applications
AMF, MRS
Config level
Standard
Setpoint visibility
Conditioned by the setpoint
Description
Nominal power of the gen-set for detected split-phase or mono phase connection. Generator
protection is based on this setpoint.
Note:
This setpoint is used when setpoint
is adjusted to Autodetect and
Autodetect detects connection type as Monophase or Splitphase.
Note:
To lock this setpoint against editing you also have to lock setpoint
,
Nominal Power Split Phase 2 (page 245)
and
Nominal Power Split Phase 3 (page 249)
.
Nominal Power Split Phase
Содержание InteliLite 9
Страница 17: ...InteliLite 9 Global Guide 17 Image 3 2 MRS application overview 6 back to Applications overview ...
Страница 41: ...InteliLite 9 Global Guide 41 4 4 12 Example of AMF Wiring ...
Страница 42: ...InteliLite 9 Global Guide 42 4 4 13 Example of MRS Wiring ...
Страница 80: ...InteliLite 9 Global Guide 80 Image 5 11 Flowchart of start of diesel engine ...
Страница 101: ...InteliLite 9 Global Guide 101 5 4 15 Flowchart Image 5 26 Basic flowchart of controller sequences ...
Страница 173: ...InteliLite 9 Global Guide 173 Image 8 7 Idle Time 1 Image 8 8 Idle Time 2 6 back to List of setpoints ...