InteliLite4 AMF20 Global Guide
284
Group: Load Management
Subgroup: Load Shedding
Load Shedding Active
Setpoint group
Load Management
Related FW
1.3.0
Range [units]
Disabled / Gen only [-]
Default value
Disabled
Alternative config
NO
Step
[-]
Comm object
11001
Related applications
AMF, MRS
Config level
Advanced
Setpoint visibility
Always
Description
This setpoint is used for adjustment when the load shedding function is active.
Disabled
The Load shedding function is disabled. All the outputs are open.
Gen only
The function is active when
= IsOper.
Load shedding outputs are activated / deactivated one by one in island
operation
All Loadshedding outputs are tripped once the Gen-set comes into the
island operation from "NO LOAD" operation (MCB and GCB were opened ->
Gen-set started and GCB closed).
Load Shedding Level
Setpoint group
Load Management
Related FW
1.3.0
Range [units]
Load Reconnection Level .. 200 [%] of
Default value
80 %
Alternative config
NO
Step
1 %
Comm object
8884
Related applications
AMF, MRS
Config level
Advanced
Setpoint visibility
Visible only if
Load Shedding Active (page 284)
is enabled
Description
This setpoint is used to activates the next Load shedding stage.When Gen-set load exceeds this level for
more than
Load Shedding Delay (page 285)
time
Содержание InteliLite 4 AMF 20
Страница 70: ...InteliLite4 AMF20 Global Guide 70 Image 5 13 WinScope 1000 screen select AirGate ...
Страница 107: ...InteliLite4 AMF20 Global Guide 107 Image 5 16 Flowchart of start of gas engine ...
Страница 602: ...InteliLite4 AMF20 Global Guide 602 Image 8 89 IGS PTM Image 8 90 IGS PTM dimensions ...
Страница 608: ...InteliLite4 AMF20 Global Guide 608 Image 8 91 Inteli AIN8TC Image 8 92 Inteli AIN8TC dimensions ...
Страница 612: ...InteliLite4 AMF20 Global Guide 612 Image 8 93 Inteli AIO9 1 Image 8 94 Inteli AIO9 1 dimensions ...