ID-Mobile Global Guide
27
Example of 5V inputs measuring.
Sensors from this group have to be connected directly
to COM terminal 33.
Note:
To use analog input AIN9-AIN16 the corresponding B group jumper. – MUST be disconnected!!!
2.8.3 Analog outputs
AOUT1 to
AOUT8
Jumpers
A
B
C
Range
Position
0 to 10V
1-2
1-2
OFF
0 to +VBat(*)
2-3
OFF
0/4 to 20 mA
1-2
2-3
OFF
X … opened or closed
1-2 … jumper on position 1- 2
OFF … no jumper (both 1-2 and 2-3 open)
IMPORTANT: To use any analog output AOUT1-8 the corresponding C Group jumper has to be
disconnected. E.g. for AOUT1 has to be disconnected all C Group jumper AIN9. Connected jumper
has influence on AOUT.
Note:
Restriction for HW version 1.2 and lower:
Power supply must be more than 18VDC to achieve full range of AOUT.
IMPORTANT: Power supply should be not less than 10V if output 10 V must be achieved.
Note:
AOUT range value is in mV i.e. 10000 = 10,000Volts
Analog output is disconnected when corresponding B GROUP jumper is removed.
General example of Analog outputs wiring.
Jumpers (A, B group) selectable range
0 to 10,000V (A=2-1 B=2-1) or
0 to – Vbatt (A=3-2 B=2-1) or
0/4 to 20 mA. (A=2-1 B=3-2)
AIN/AOUT terminals group is variable. Different combination of AIN and AOUTS can be configured.