ID-Mobile Global Guide
172
Related FW
2.6.0
Related applications
AMF, MRS
Comm object
6
Description
The output closes when any Sensor fail alarm is active. Output opens when all Fls alarms disappear and
Fault reset is pressed (no Fls alarm in Alarm list).
Common Fls
Related FW
2.6.0
Related applications
AMF, MRS
Comm object
4
Description
The output closes when any Shut-down alarm is active. Output opens when all Sd alarms disappear and
Fault reset is pressed (no Sd alarm in Alarm list).
Common Sd
Related FW
2.6.0
Related applications
AMF, MRS
Comm object
251
Description
Indication of any active Shut-down Overide protection.
Common SdO
Related FW
2.6.0
Related applications
AMF, MRS
Comm object
3
Description
The output closes when any Warning alarm is active. Output opens when all Wrn alarms disappear and Fault
reset is pressed (no Wrn alarm in Alarm list).
Common Wrn
Related FW
2.6.0
Related applications
AMF, MRS
Comm object
40
Description
The output closes when engine starts and opens AfterCoolTime delayed after stop the engine.
Cooling Pump