InteliDrive Lite, SW version 1.9
ID-FLX-Lite-1.9r1 Reference Guide.pdf,
©ComAp – August 2015
96
Analog input 3 is usually determined to Fuel Level measurement and it is resistive type of input with
range 0-2500Ohm.
7.7.18 Batt overvolt
[V]
High battery voltage Warning limit
Step:
0.1V
Range:
Batt undervolt - 40.0V
Default:
36.0V
7.7.19 Batt undervolt
[V]
Low battery voltage Warning limit.
Step:
0.1V
Range:
8.0 - Batt overvolt
Default:
18.0V
7.7.20 Batt volt del
[s]
Delay for low and high battery voltage alarm.
Step:
1s
Range:
0 - 600s
Default:
5s
7.7.21 AIN4 Level 1
[ ]
Warning limit level for AIN4
Step:
1
Range:
0 - 10000
Default:
20
7.7.22 AIN4 Level 2
[ ]
Shutdown limit level for AIN4
Step:
1
Range:
0 - 10000
Default:
10
7.7.23 AIN4 Del
[s]
Delay for Wrn/Sd AIN4 alarm.
Step:
1s
Range:
0 - 3600s
Default:
10s