InteliDrive Lite, SW version 1.9
ID-FLX-Lite-1.9r1 Reference Guide.pdf,
©ComAp – August 2015
84
The Binary inputs SpeedUp and SpeedDown ramp function is for
the 0.6s constant 5RPM/s. Does not depend on
Engine params
:
Speed Ramp
setting. This enables fine setting of Engine speed
to specific value e.g. 1500 RPM.
5RPM/s
0,6s
E
ng
in
e
pa
ra
m
s
:
S
pe
ed
R
am
p
Time
R
e
q
u
e
s
te
d
S
p
e
e
d
Step:
1RPM/s
Range:
1 -
MaxSpeedLim
Default:
50RPM
7.4.26 0%ofSpeedReq
[RPM]
Limit for Speed Request transformation from RPM to % range for ECU engines using % format. See
practical example below.
Step:
1RPM
Range:
0 - 3000RPM
Default:
0RPM
Practical example:
If ECU is configured, then on one of the measurement screen you can see two lines SpeedReq Abs
and SpeedReq Rel.
In default setting:
0RPM = 0%
800RPM = 33.3%
2400RPM = 100%
Different setting:
800RPM = 0%
1200RPM = 33.3%
2400RPM = 100%
It is possible easily configure own output curve and use it for analog output Speed Request.
Engine params:
BI Speed ramp
Speed Up
Speed Down
Binary Inputs:
Engine params:
MinSpeedLim
MaxSpeedLim
Engine params:
BI Speed Sel 1
Speed Sel 1
Engine params:
BI Speed Sel 2
Speed Sel 2
Engine params:
BI Speed Sel 3
Speed Sel 3
Speed request
ECU