ID-FLX Lite Global Guide
145
Setpoint group
Engine protection
Related FW
2.5.0
Range [units]
0 .. 180 [s]
Default value
10
-
Step
1
Comm object
8377
Related applications
Description
Delay for ANALOG INPUT 3.
Note:
Analog input 3 is usually determined to Fuel Level measurement and it is resistive type of input
with range 0-2500 Ω.
AIN3 Del
Setpoint group
Engine protection
Related FW
2.5.0
Range [units]
.. 40.0 [V]
Default value
36.0
-
Step
0.1
Comm object
9587
Related applications
Description
High battery voltage Warning limit.
Batt overvolt
Setpoint group
Engine protection
Related FW
2.5.0
Range [units]
80.0 ..
[-]
Default value
18.0
-
Step
0.1
Comm object
8387
Related applications
Description
Low battery voltage Warning limit.
Batt undervolt
Setpoint group
Engine protection
Related FW
2.5.0
Range [units]
0 .. 600 [s]
Default value
5
-
Step
1
Comm object
8383
Related applications
Description
Delay for low and high battery voltage alarm.
Batt volt del
Содержание InteliDrive FLX LITE
Страница 19: ...ID FLX Lite Global Guide 19 4 3 Terminal diagram and dimension ...
Страница 21: ...ID FLX Lite Global Guide 21 Example Default analog output curves ...
Страница 22: ...ID FLX Lite Global Guide 22 Example Wiring for Dacon gauges and IL NT AOUT8 ...
Страница 43: ...ID FLX Lite Global Guide 43 When you finish with adjusting the values click OK and Write to controller ...
Страница 44: ...ID FLX Lite Global Guide 44 5 2 Binary inputs and outputs ...
Страница 57: ...ID FLX Lite Global Guide 57 5 14 Display screens and pages structure ...
Страница 83: ...ID FLX Lite Global Guide 83 7 Communication 6 back to Table of contents ...
Страница 92: ...ID FLX Lite Global Guide 92 10 Appendix 10 2 Extension modules 225 6 back to Table of contents ...