ID-FLX Lite Global Guide
131
Setpoint group
Load limit
Related FW
2.5.0
Range [units]
-10000 .. +10000 [-]
Default value
0
YES
Step
1
Comm object
11845
Related applications
Description
Regulator requested value when LBI Request2 is active.
Value of this Setpoint should be given in value of quantity without decimal point.
Example:
When AIN is configured in such way that Load limit set on 5 V to maintain the value
8.54 bar, then the value inserted to this Setpoint is 854.
Request 2
Setpoint group
Load limit
Related FW
2.5.0
Range [units]
-2000.0 .. +2000.0 [%]
Default value
10
YES
Step
0.1
Comm object
11846
Related applications
Description
This setpoint is giving regulator gain factor. See Note below.
Reg Gain
Setpoint group
Load limit
Related FW
2.5.0
Range [units]
0.0 .. 1000.0 [%]
Default value
YES
Step
0.1
Reg Integral
Содержание InteliDrive FLX LITE
Страница 19: ...ID FLX Lite Global Guide 19 4 3 Terminal diagram and dimension ...
Страница 21: ...ID FLX Lite Global Guide 21 Example Default analog output curves ...
Страница 22: ...ID FLX Lite Global Guide 22 Example Wiring for Dacon gauges and IL NT AOUT8 ...
Страница 43: ...ID FLX Lite Global Guide 43 When you finish with adjusting the values click OK and Write to controller ...
Страница 44: ...ID FLX Lite Global Guide 44 5 2 Binary inputs and outputs ...
Страница 57: ...ID FLX Lite Global Guide 57 5 14 Display screens and pages structure ...
Страница 83: ...ID FLX Lite Global Guide 83 7 Communication 6 back to Table of contents ...
Страница 92: ...ID FLX Lite Global Guide 92 10 Appendix 10 2 Extension modules 225 6 back to Table of contents ...