ID-FLX Lite Global Guide
102
Setpoint group
Basic settings
Related FW
2.5.0
Range [units]
[Pickup, AIO-AIN1, AIO-AIN2, AIO-AIN3, AIO-AIN4]
Default value
-
Step
-
Comm object
12142
Related applications
Description
Switch from where the RPM is measured. When source is Analog input the converted value is going to be in
RPM range.
RPM source
Setpoint group
Basic settings
Related FW
2.5.0
Range [units]
ENABLED / DISABLED [-]
Default value
ENABLED
-
Step
-
Comm object
14599
Related applications
N/A
Description
This setpoint is used to enable or disable fail detect function of RA15 module which enables or disables
alarm announcement in case RA15 is configured but not communicating.
RA-FailDetect