InteliDrive DCU Industrial 3.4.0 Global Guide
292
Impulse
Measurement of pulses by norm DIN 43864 and norm IEC 62053-31– equipment class A.
For flow meter pulses: UH=30V, Imax=30mA, Ton min =10ms,Toff min = 10ms , OC
Galvanic separation
CAN bus is galvanic separated from the measurement and power supply.
All analog inputs are galvanic separated from power supply.
Analog inputs are not galvanic separated between channels
Power supply
8 to 36 V DC
Protection
IP20
Current consumption
35 mA at 24 V ÷ 100 mA at 8 V
Storage temperature
- 40 °C to + 80 °C
Operating temperature
- 30 °C to + 70 °C
Heat radiation
3 W
*RPM input – required level of signal for correct sensing
Minimum input voltage 2 Vpk-pk (from 4 Hz to 4 kHz)
Minimum input voltage 6 Vpk-pk (from 4 kHz to 10 kHz)
*Voltage measurement circuit was designed for lambda probe, for measurement thermocouples please use
Inteli AIN8TC.
The product is fully supported in fw IGS-NT 3.0 or higher and in IGS-NT-branches based on this fw.
8.2.2 Inteli AIN8TC
Image 8.4 Dimensions of Inteli AIN8TC
Inteli AIN8TC unit can be mounted on
DIN rail (35 mm)
.
All dimensions are in mm.
Содержание InteliDrive DCU Industrial
Страница 5: ...InteliDrive DCU Industrial 3 4 0 Global Guide 5 8 2 13 Theory of binary inputs and outputs 347...
Страница 29: ...InteliDrive DCU Industrial 3 4 0 Global Guide 29...
Страница 97: ...InteliDrive DCU Industrial 3 4 0 Global Guide 97 8 Appendix 6 back to Table of contents...
Страница 246: ...InteliDrive DCU Industrial 3 4 0 Global Guide 246 Analog inputs from J1939 configuration...
Страница 263: ...InteliDrive DCU Industrial 3 4 0 Global Guide 263 6 back to List of setpoints...
Страница 281: ...InteliDrive DCU Industrial 3 4 0 Global Guide 281 6 back to Appendix 6 back to Table of contents...
Страница 294: ...InteliDrive DCU Industrial 3 4 0 Global Guide 294 Dimensions Note Unit is 35 mm DIN rail mounted Terminals...
Страница 306: ...InteliDrive DCU Industrial 3 4 0 Global Guide 306 Dimensions Note Unit is 35 mm DIN rail mounted...
Страница 314: ...InteliDrive DCU Industrial 3 4 0 Global Guide 314 Dimensions Unit is 35 mm DIN rail mounted Terminals...
Страница 350: ...InteliDrive DCU Industrial 3 4 0 Global Guide 350 6 back to Theory of binary inputs and outputs...