InteliDrive DCU Industrial 3.4.0 Global Guide
28
OFF
mode is available in all applications –
RUN
mode.
RUN mode
Controller starts and stops the engine according to the binary inputs
Blackout Start
or
Remote Start
,
Rem
Start/Stop
,
Remote Stop
or to the ID-DCU Industrial
Start / Stop
buttons. Binary inputs Blackout Start and
Remote Start and Remote Stop are inactive in
LOC
(Local) mode.
All engine protections and all configured shutdown protections are active. Controller continuously monitors
all available engine parameters (oil pressure, water temperature, RPM, fuel level etc.). The engine will stop
and activates
Common Warning
and
Common Shutdown
outputs and writes record to the history file
when detects any active Shut down alarm. This condition can be signaled by Active call feature to remote
operator via modem, SMS or e-mail.
Other functions
Controller (except OFF mode) accepts when engine is started outside controller (by hand) or when controller
power supply is switched-on on already running engine.
3.1.3 Universal states
State is a value joined to each Analog input or value. State indicates if any protection configured on
corresponding analog input is active or not. When there is any state configured as protection the corresponding
Binary output appears in Analog protection list and can be used for selective external indication of the Alarm.
State is resetted (output is opened) when corresponding Alarm is not active and confirmed (Fault reset was
pressed).
There are seven universal (free) states available in ID-DCU Industrial-3.4.0 that are not joined to any value or
input.
They can be used mostly for some values that have not state (e.g. RPM or other that are not measured on
Analog input). This way can be configured protection to any ID-DCU Industrial internal value or more levels
external indication.
Example of Universal state1 configuration to Engine speed (Warning for Engine speed > 1600RPM, 1s):
This configuration is available in DriveConfig – Expert mode.
Содержание InteliDrive DCU Industrial
Страница 5: ...InteliDrive DCU Industrial 3 4 0 Global Guide 5 8 2 13 Theory of binary inputs and outputs 347...
Страница 29: ...InteliDrive DCU Industrial 3 4 0 Global Guide 29...
Страница 97: ...InteliDrive DCU Industrial 3 4 0 Global Guide 97 8 Appendix 6 back to Table of contents...
Страница 246: ...InteliDrive DCU Industrial 3 4 0 Global Guide 246 Analog inputs from J1939 configuration...
Страница 263: ...InteliDrive DCU Industrial 3 4 0 Global Guide 263 6 back to List of setpoints...
Страница 281: ...InteliDrive DCU Industrial 3 4 0 Global Guide 281 6 back to Appendix 6 back to Table of contents...
Страница 294: ...InteliDrive DCU Industrial 3 4 0 Global Guide 294 Dimensions Note Unit is 35 mm DIN rail mounted Terminals...
Страница 306: ...InteliDrive DCU Industrial 3 4 0 Global Guide 306 Dimensions Note Unit is 35 mm DIN rail mounted...
Страница 314: ...InteliDrive DCU Industrial 3 4 0 Global Guide 314 Dimensions Unit is 35 mm DIN rail mounted Terminals...
Страница 350: ...InteliDrive DCU Industrial 3 4 0 Global Guide 350 6 back to Theory of binary inputs and outputs...