InteliDrive DCU Industrial 3.4.0 Global Guide
168
Related FW
3.4.0
Related applications
AS, SS
Comm object
152
Description
Binary input for Alarm acknowledge (level sensitive) has the same function as controller front panel button
Fault reset (i.e. the acknowledge function is screen sensitive).
Note:
There is separated acknowledge for ECU Alarms – see Binary input
Fault Reset
Related FW
3.4.0
Related applications
AS, SS
Comm object
153
Description
Binary input
Horn Reset
is level sensitive.
Horn Reset
Related FW
3.4.0
Related applications
AS, SS
Comm object
12
Description
Controller is switched to OFF mode if input is closed and back to previous mode after is opened. Input is not
active in LOC (Local) mode. Active binary input Remote OFF is indicated by “
L
” character in the right upper
corner on ID-DCU Industrial screen.
Note:
Remote OFF will switch controller to OFF mode even if the
or
is active or Controller mode is password protected.
Remote OFF
Related FW
3.4.0
Related applications
AS, SS
Comm object
14
Description
Controller is switched to
HRB
mode if closed and back to previous mode if opened. Input is not active in
LOC
(Local) mode.
Remote HRB
Related FW
3.4.0
Related applications
AS, SS
Comm object
161
Description
is closed/opened depends on the state of Remote On/Off binary input when engine
RPM is over
. Remote On/Off is not active in LOC mode.
Remote On/Off
Содержание InteliDrive DCU Industrial
Страница 5: ...InteliDrive DCU Industrial 3 4 0 Global Guide 5 8 2 13 Theory of binary inputs and outputs 347...
Страница 29: ...InteliDrive DCU Industrial 3 4 0 Global Guide 29...
Страница 97: ...InteliDrive DCU Industrial 3 4 0 Global Guide 97 8 Appendix 6 back to Table of contents...
Страница 246: ...InteliDrive DCU Industrial 3 4 0 Global Guide 246 Analog inputs from J1939 configuration...
Страница 263: ...InteliDrive DCU Industrial 3 4 0 Global Guide 263 6 back to List of setpoints...
Страница 281: ...InteliDrive DCU Industrial 3 4 0 Global Guide 281 6 back to Appendix 6 back to Table of contents...
Страница 294: ...InteliDrive DCU Industrial 3 4 0 Global Guide 294 Dimensions Note Unit is 35 mm DIN rail mounted Terminals...
Страница 306: ...InteliDrive DCU Industrial 3 4 0 Global Guide 306 Dimensions Note Unit is 35 mm DIN rail mounted...
Страница 314: ...InteliDrive DCU Industrial 3 4 0 Global Guide 314 Dimensions Unit is 35 mm DIN rail mounted Terminals...
Страница 350: ...InteliDrive DCU Industrial 3 4 0 Global Guide 350 6 back to Theory of binary inputs and outputs...